3X95mm2 BS6724 Halogen Free Flame Retardant 1.9/3.3kv Shpd Cu XLPE Swa Hffr Cable

3X95mm2 BS6724 Halogen Free Flame Retardant 1.9/3.3kv Shpd Cu XLPE Swa Hffr Cable

3X95mm2 BS6724 Halogen Free Flame Retardant 1.9/3.3kv Shpd Cu XLPE Swa Hffr Cable

1.9/3.3kV Cable

Hongda

Cu/XLPE/Hffr/Swa/Hffr

ISO, CCC, CE, SGS

Bare Copper Wire

Round Wire

Hffr/Losh/LSZH

XLPE

DC & AC

Low and Medium Voltage Cable

Construction, Underground, Industrial, Power Station

Awa (Aluminum Wire Armour)

Swa (Steel Wire Armour)

1900/3300V, 1.9/3.3kv

0°c to +90°c

IEC60332 Part 1, BS4066 Part 1

IEC 61034, En50268

Hongda Cable

Steel & Wooden Drum

1.5mm2 to 400mm2

China

8544492100

Product Description

BS 6724 Standards Armoured Power Cables, 1900/3300V
Three-core 1900/3300 V cables with stranded copper conductors

Thermosetting insulated armoured cables – 600/1000V to 1900/3300V – with low emission of smoke and corrosive gases when affected by fire. Manufactured in accordance with British Standard BS6724

1. Application

These cables are used for power and control circuits, they can offer excellent protection through the use of a heavy galvanized steel wire armour. The GSWA makes them suitable for use inside and outside buildings or for direct burial in the ground. For installation where fire, smoke emission and toxic fumes create a potential threat to life and equipment.

2. Construction

CONDUCTOR Solid Aluminum or Copper conductor, round stranded or shaped, Class 2 to BS 6460,
  IEC 60228.
INSULATION XLPE (Cross-Linked Polyethylene) Type GP 8 or ethylene propylene rubber (GP 6)
COLOUR CODE 1 Core : Brown
  2 Cores : Brown or Blue
  3 Cores: Brown, Black, Grey
  4 Cores: Blue, Brown, Black, Grey
  5 Cores: Green/Yellow, Blue, Brown, Black, Grey
  Above 5 Cores: White Cores with black numerals
BEDDING LSOH (Low Smoke Zero Halogen)
ARMOUR Single Core: AWA (Aluminum Wire Armour)
  Multi Core: SWA (Steel Wire Armour)
OUTER SHEATH LSOH (Low Smoke Zero Halogen)

Technical Information

Voltage rating 1900/3300V
Temperature rating 0°C to +90°C
Bending radius 1.5mm² to 16mm²: 6 x overall diameter
                         25mm² and above: 8 x overall diameter
Flame retardant IEC60332 part 1, BS4066 part 1
Halogen free IEC 60754, EN 50267
Smoke density IEC 61034, EN50268

3. Three-core 1900/3300 V cables with stranded copper conductors

 

NOMINAL CROSS-SECTIONAL AREA STRAND TYPE NOMINAL INSULATION THICKNESS NOMINAL BEDDING THICKNESS NOMINAL STEEL WIRE ARMOR DIA. NOMINAL SHEATH THICKNESS APPROX OVERALL DIAMETER APRROX WEIGHT
MM² NO./MM MM MM MM MM MM KG/KM
3×16 7/1.70 2 1 1.6 1.8 29.3 1600
3×25 7/2.14 2 1 1.6 1.8 32.2 2060
3×35 7/2.52 2 1 1.6 1.9 34.8 2400
3×35* 7/2.52 2 1 1.6 1.9 31.1 2400
3×50* 19/1.78 2 1.2 2 2 34.7 3200
3×70* 19/2.14 2 1.2 2 2.1 38 3800
3×95* 19/2.52 2 1.2 2 2.2 41.4 4730
3×120* 37/2.03 2 1.4 2.5 2.3 45.7 6070
3×150* 37/2.25 2 1.4 2.5 2.4 48.5 7010
3×185* 37/2.52 2 1.4 2.5 2.5 51.9 8270
3×240* 61/2.25 2 1.6 2.5 2.6 56.9 10310
3×300* 61/2.52 2 1.6 2.5 2.7 61.2 12300
3×400* 61/2.85 2 1.6 2.5 2.9 66.6 14500

4. Notes
1. Due to mechanical protection provided by their armours, cables manufactured to BS6724 are suitable for applications in industrial wiring and mains distribution where there is a risk of mechanical damage and for direct burial.
2. If you are considering installing in high UV exposure and/or high/low ambient temperatures i.e. desert/arctic conditions then special sheathing may be required.
3. Whilst HONGDA CABLE plc endeavours to ensure the information on the website, specification sheets and all other technical information is accurate, the information is for guidance only and it is subject to change without notice or liability. Hongda Cable Plc is not responsible for the consequences of any inadequacies, inaccuracies or other deficiencies contained therein. When selecting cable accessories, please note that the actual cable dimensions may vary due to manufacturing tolerances.

For more information, don’t hesitate to call us  or send inquiry to me.

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.