11kv 1 Core 55sqmm Triple Extruded Longitudanally Water Covered AAAC Cable
Product Description
SCOPE:
This specification covers details of All Aluminium Alloy Stranded Covered Conductors for use on 33 kV , 22 kV,11 kV distribution system. The conductor covered insulation shall mark EN 50397-1:2006 by embossing/printing on it at every meter throughout the length.
CONDUCTOR SIZES
7/ 2.00 mm (22 sq.mm)
7/ 2.50 mm (34 sq.mm)
7/ 3.15 mm (55 sq.mm)
7/ 3.81 mm (80 sq.mm)
7/4.26 mm (100 sq.mm)
19/ 3.15 mm (148 sq.mm)
19/ 3.94 mm (232 sq.mm)
ALUMINIUM ALLOY STRANDED CONDUCTOR Specifications:
Area sqmm |
Stranding & wire dia. mm |
Approx overall dia. mm |
Approx. mass mm |
Resistance at 20ºC DC (max.) ohm/km | Approx. calculated Breaking Load kN |
22 | 7/2.00 | 6.0 | 60.16 | 1.5410 | 6.45 |
34 | 7/2.50 | 7.5 | 94.00 | 0.9900 | 10.11 |
55 | 7/3.15 | 9.45 | 149.20 | 0.6210 | 16.03 |
80 | 7/3.81 | 11.43 | 218.26 | 0.4250 | 23.41 |
100 | 7/4.26 | 12.78 | 272.86 | 0.3390 | 29.26 |
148 | 19/3.15 | 15.75 | 406.91 | 0.2290 | 43.50 |
232 | 19/3.94 | 19.70 | 636.67 | 0.1471 | 68.05 |
Please contact us for technical support with the right cable selection for your power distribution projects and to discuss your maintenance or project specific requirements. We provide tailored solutions for this cable range which include storage, cutting to length, and 2 days collection as standard.
Any problem and inquiry pls contact with Vivian Yuan.
- Next: BS 6724 Standards Armour Power Cable 1core 3core 1900/3300 V Cables
- Previous: 3X95mm2 BS6724 Halogen Free Flame Retardant 1.9/3.3kv Shpd Cu XLPE Swa Hffr Cable