Low Voltage BS5467 Swa XLPE Cable Armoured Power Cables

Low Voltage BS5467 Swa XLPE Cable Armoured Power Cables

Low Voltage BS5467 Swa XLPE Cable Armoured Power Cables

bs5467

Hongda

BS5467 Cable

ISO, CCC, CE

Bare Copper Wire

Round Wire

PVC

XLPE

AC Cable

Low and Medium Voltage Cable

Construction, Underground, Industrial, Power Station

Steel Wire or Steel Tape

600/1000V

8 X Overall Diameter

Hongda Cable

Steel & Wooden Drum

1.5mm2 to 400mm2

China

8544492100

Product Description

BS5467 SWA/PVC Cable IEC 60502 600/1000V

Applications: Power cable suitable for power networks, direct burial, outdoors, indoors and in cable ducts.

Conductors: Plain annealed stranded copper

Insulation: XLPE (Cross linked polyethylene)

Bedding: PVC (Polyvinyl-Chloride)

Armour/Protection: SWA (Galvanised single wire armour)

Sheath/Jacket: PVC (Polyvinyl-Chloride)

Colour: Black

Voltage: 600/1000v

Operating temperature: Maximum 90°C. Minimum bending 0°C

Minimum bending radius:

1.5 sq.mm – 16 sq.mm -6 x overall diameter (circular cond.)

25 sq.mm and above – 8 x overall diameter (shaped cond.)

Core identification:
Two Core – Brown, Blue
Three Core – Brown, Black & Grey (Optional: Brown, Blue & Green/Yellow)
Four Core – Brown, Black, Grey & Blue (Optional: Brown, Black, Grey & Green/Yellow)
Five Core – Numbered Cores (Optional: Brown, Black, Grey, Blue + Green/Yellow)
Six Core and Above – Numbered Cores (optional numbered + Green and Yellow)

Conductor stranding:
Class 2 stranded copper:
2 circular or circular compacted conductors
2* shaped or circular conductors or circular compacted conductors.
2S shaped conductors
(Dimensions and weights based on circular)

Standard:
BS5467: Electric cables. Thermosetting insulated, armoured cables for voltages of 600/1000V and 1900/3300V
IEC60502: Power cables with extruded insulation and their accessories for rated voltages from 1kV to 30kV
Flame Propagation Test to BS EN 60332-1-2 for single cable

Note:If you are considering installing in high UV exposure and/or high/low ambient temperatures i.e. desert/arctic conditions then special sheathing may be required.

Dimensions – BS5467 XLPE/PVC/AWA/PVC (Copper)

No. of Cores Nominal Cross Sectional Area Nominal Thickness of Insulation Nominal Overall Diameter mm Nominal Weight
mm² mm Under Armour Overall kg/km
2 1.5 0.6 7.3 12.1 302
2 2.5 0.7 8.5 13.6 346
2 4 0.7 9.4 14.7 410
2 6 0.7 10.5 15.9 499
2 10 0.7 12.3 18 648
2 16 0.7 14.3 20.4 978
2 25 0.9 14.7 20.4 1290
2 35 0.9 16.8 23.3 1500
2 50 1 19 25.8 1890
2 70 1.1 22 29 2450
2 95 1.1 25.1 33.1 3300
2 120 1.2 27.9 36.1 4020
2 150 1.4 30.9 39.3 4750
3 1,5 0.6 7.8 12.6 330
3 2.5 0.7 9.2 14.1 390
3 4 0.7 10 15.3 464
3 6 0.7 11.2 16.6 568
3 10 0.7 13.1 19.5 866
3 16 0.7 15.3 21.6 1152
3 25 0.9 18.9 23.6 1800
3 35 0.9 21.3 25.7 2230
3 50 1 21.7 28.5 2490
3 70 1.1 25.2 32.2 3290
3 95 1.1 28.8 37 4440
3 120 1.2 32 40.4 5470
3 150 1.4 35.9 45.5 6930
3 185 1.6 40 49.8 8350
3 240 1.7 44.9 55.1 10400
3 300 1.8 49.8 60.2 12600
3 400 2 55.8 66.6 14600
4 1.5 0.6 8.5 13.3 365
4 2.5 0.7 9.9 15 438
4 4 0.7 11 16.4 532
4 6 0.7 12.3 18.7 764
4 10 0.7 14.5 21.1 1013
4 16 0.7 17 23.4 1360
4 25 0.9 21 26.1 2160
4 35 0.9 23.6 28.6 2690
4 50 1 25 32 3130
4 70 1.1 29.5 37.7 4500
4 95 1.1 33.3 41.7 5600
4 120 1.2 37.5 47.1 7400
4 150 1.4 41.6 51.4 8780
4 185 1.6 46.4 56.6 10630
4 240 1.7 52.6 63 13390
4 300 1.8 58 68.8 16290
4 400 2 65.4 78.1 19800
5 1.5 0.6 9.7 14.3 410
5 2.5 0.7 11.7 16.1 470
5 4 0.7 13 17.8 710
5 6 0.7 14.5 20 876
5 10 0.7 17.2 22.9 1165
5 16 0.7 20 26.6 1742
5 25 0.9 24.7 31.5 2323
5 35 0.9 27.8 34.8 2932
5 50 1 32.4 40.4 4192
7 1.5 0.6 10.2 15.2 470
7 2.5 0.7 12.3 17.1 600
7 4 0.7 13.6 19.1 881
12 1.5 0.6 13.7 19.4 780
12 2.5 0.7 16.3 22.4 1000
19 1.5 0.6 16.2 22.2 1000
19 2.5 0.7 19.9 26.6 1540
27 1.5 0.6 20 26.7 1500
27 2.5 0.7 24 30.7 1950
37 1.5 0.6 22.3 29 1800
37 2.5 0.7 26.9 33.8 2350

Class 2 Stranded Conductors for Single Core and Multi-Core Cables

Nominal Cross 
Sectional Area
Minimum No. Of Wires In Conductor Maximum Resistance 
of Conductor At 20ºC
mm² Circular Circular Compacted Shaped Annealed Copper Conductor
Cu Al Cu Al Cu Al Plain Wires ohms/km
1.5 7 6 12.1
2.5 7 6 7.41
4 7 6 4.61
6 7 6 3.08
10 7 7 6 6 1.83
16 7 7 6 6 1.15
25 7 7 6 6 6 6 0.727
35 7 7 6 6 6 6 0.524
50 19 19 6 6 6 6 0.387
70 19 19 12 12 12 12 0.268
95 19 19 15 15 15 15 0.193
120 37 37 18 15 18 15 0.153
150 37 37 18 15 18 15 0.124
185 37 37 30 30 30 30 0.0991
240 37 37 34 30 34 30 0.0754
300 61 61 34 30 34 30 0.0601
400 61 61 53 53 53 53 0.047

Whilst HONGDA CABLE plc endeavours to ensure the information on the website, specification sheets and all other technical information is accurate, the information is for guidance only and it is subject to change without notice or liability. HONGDA Cable Plc is not responsible for the consequences of any inadequacies, inaccuracies or other deficiencies contained therein. When selecting cable accessories, please note that the actual cable dimensions may vary due to manufacturing tolerances. 

 