Triplex Service Drop, ABC Cable, 2/0AWG, Cyclops

Triplex Service Drop, ABC Cable, 2/0AWG, Cyclops

Triplex Service Drop, ABC Cable, 2/0AWG, Cyclops

ABC cable, 2/0AWG, Cyclops

2/0AWG,Cyclops

75 Centigrade

PVC, PE or XLPE

5390lbs

Yifang Cable

Wooden Drum or Wooden-Steel Drum

CE SABS RoHS SGS UL CCC

Zhengzhou, China

8544492100

Product Description

Triplex
Service Drop

Triplex Service Drop,ABC cable,2/0AWG,Cyclops

APPLICATIONS
Used to supply power, usually from a pole-mounted transformer, to the user’s service head where connection to the service
entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to
exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.
SPECIFICATIONS
Southwire’s triplex service drop cable meets or exceeds the following ASTM specifications:
? B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
? B-231 Aluminum Conductors, Concentric-Lay-Stranded.
? B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced(ACSR).
? B-399 Stranded 6201-T81 Aluminum Alloy Conductors.
? B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire.
Southwire’s triplex service drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
CONSTRUCTION
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or crosslinked polyethylene (XLP). Neutral messengers are concentrically stranded 6201, AAC, or ACSR.

The Diagram of Structure:

Code Name

Phase Conductor Bare Neutral Messenger Weight Per 1000ft (lbs) Ampacity(amps)
Size AWG Stranding Insulation Thickness(mls) Size AWG Stranding Breaking Strength(lbs) XLPE Poly XLPE Poly
6201 ALLOY NEUTRAL-MESSENGER
Minex 6 Solid 45 6 7 1, 110 106.6 102.9 85 70
Hippa 6 7 45 6 7 1, 110 113.2 105.7 85 70
Prawn 4 Solid 45 4 7 1, 760 158.4 154.1 115 90
Barnacles 4 7 45 4 7 1, 760 168.3 158.2 115 90
Shrimp 2 7 45 2 7 2, 800 253.7 239.7 150 120
Gammarus 1/0 7 60 1/0 7 4, 460 411.7 386.0 205 160
Leda 1/0 19 60 1/0 7 4, 460 402.7 386.0 205 160
Dungenese 2/0 7 60 2/0 7 5, 390 506.8 476.3 235 185
Cyclops 2/0 19 60 2/0 7 5, 390 495.3 476.3 235 185
Dlustra 3/0 19 60 3/0 7 6, 790 611.4 589.1 275 215
Lepas 4/0 19 60 4/0 7 8, 560 757.1 730.5 315 245
6201 ALLOY REDUCED NEUTRAL-MESSENGER
Artemia 4 Solid 45 6 7 1, 110 141.4 137.1 115 90
Crab 4 7 45 6 7 1, 110 151.3 141.2 115 90
Solaster 2 7 45 4 7 1, 760 226.6 212.6 150 120
Sandcrab 1/0 7 60 2 7 2, 800 368.8 343.1 205 160
Echinus 1/0 19 60 2 7 2, 800 358.8 343.1 205 160
Crayfish 2/0 7 60 1 7 3, 530 452.6 422.5 235 185
Sipho 2/0 19 60 1 7 3, 530 441.0 422.5 235 185
Fulgar 3/0 19 60 1/0 7 4, 460 543.4 521.1 275 215
Arca 4/0 19 60 2/0 7 5, 390 671.2 644.6 315 245

Item

Phase
Conductor
Size/AWG
Phase
Conductor
Stranding
Phase
Conductor
Insulation
Thickness
Bare
Neutral
Messenger
Size/AWG
Bare
Neutral
Messenger
Stranding
Bare
Neutral
Messenger
Breaking
Strength
Weight
Per
MFT
XLP
Weight
Per
MFT
POLY
Ampacity
XLP
Ampacity
Poly
Bay 6 Solid 45 mls 6 7 1110 Lbs 145 Lbs 140.0 Lbs 75 Amps 60 Amps
French Coach 6 7/w 45 mls 6 7 1110 Lbs 155 Lbs 144.3 Lbs 75 Amps 60 Amps
German Coach 4 Solid 45 mls 4 7 1760 Lbs 214 Lbs 208.3 Lbs 100 Amps 80 Amps
Arabian 4 7/w 45 mls 4 7 1760 Lbs 229 Lbs 214.4 Lbs 100 Amps 80 Amps
Belgian 2 7/w 45 mls 2 7 2800 Lbs 344 Lbs 323.1 Lbs 135 Amps 105 Amps
Shetland 1/0 19/w 60 mls 1/0 7 4460 Lbs 546 Lbs 521.1 Lbs 180 Amps 140 Amps
Thoroughbred 2/0 19/w 60 mls 2/0 7 5390 Lbs 670 Lbs 641.5 Lbs 205 Amps 160 Amps
Trotter 3/0 19/w 60 mls 3/0 7 6790 Lbs 825 Lbs 791.8 Lbs 235 Amps 185 Amps
Walking 4/0 19/w 60 mls 4/0 7 8560 Lbs 1019 Lbs 979.7 Lbs 275 Amps 210 Amps