Triplex Secondary Urd, Urd Cable, 600 V, Al/XLPE (ANSI/ICEA S-105-692)

Triplex Secondary Urd, Urd Cable, 600 V, Al/XLPE (ANSI/ICEA S-105-692)

Triplex Secondary Urd, Urd Cable, 600 V, Al/XLPE (ANSI/ICEA S-105-692)

Triplex 600 V Secondary URD

Insulated

Stranded

Overhead, Underground

Aluminum

XLPE

Round Wire

Distribution

ISO9001, CCC

Boan

ANSI/Icea S-105-692

600 V

6-500 AWG or Kcmil

3

7-37

DingAn or OEM

Fumigated Wooden/Steel-Wooden Drum

SGS

Jiangsu Yixing, China

8544492100

Product Description

Triplex Secondary Urd, Urd Cable, 600 V, Al/XLPE (ANSI/ICEA S-105-692)
TRIPLEX 6OOV SECONDARY URD

INSULATION: CROSS-LINKED POLYETHYLENE XLP
CONDUCTORS: ALUMINUM

APPLICATION:
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts, in areas with soft soils where rodents are not present.

CONSTRUCTION:
Secondary power distribution up to 600V in areas with soft soils where rodents are not present.

SPECIFICATIONS:
Conductors are stranded, compressed 1350-H16/H26 aluminum insulated with vulcanized interlinked polyethylene. Neutrals are triple yellow extruded stripe. Neutrals have sequential footage markers. Conductors are durably surface printed for identification. Two phase conductors and one neutral or three phase conductors are cabled together to produce the triplex configuration.

Triplex or paralleled 600 volt secondary UD cable meets or exceeds the following applicable ASTM specifications.
B-231 Aluminum 1350 Conductors. Concentric-Lay-Stranded
B-609 Aluminum 1350 Round Wire. Annealed and Intermediate Tempers, for Electrical Purposes.
B-786 19 Wire Combination Unilay-Stranded Aluminum Conductors for Subsequent Insulation.

Triplex 600 volt secondary UD cable meets or exceeds all applicable requirements of ICEA S-105-692
for cross-linked polyethylene insulated conductors and UL Standard 854 for Type USE-2.

Code Word Phase Conductor Neutral Diameter Weight Per 1000 feet Allowable Ampacities+
(mils)
Size Strand-ing Insul.Thick. Size Strand-ing Insul.Thick. Single Phase Cond. Complete Cable Direct Burial In Ducts
(AWG) (mils) (AWG) (mils) (lbs.)
TRIPLEXED WITH YELLOW EXTRUDED STRIPE NEUTRAL.
Erskine 6 7 60 6 7 60 298 644 134 95 70
Vassar 4 7 60 4 7 60 345 745 191 125 90
Stephens 2 7 60 4 7 60 403 870 249 165 120
Ramapo 2 7 60 2 7 60 403 870 278 165 120
Brenau 1/0 9 80 2 7 60 512 1106 387 215 160
Bergen 1/0 9 80 1/0 9 80 512 1106 441 215 160
Converse 2/0 11 80 1 9 80 555 1199 478 245 180
Hunter 2/0 11 80 2/0 11 80 555 1199 535 245 180
Hollins 3/0 17 80 1/0 9 80 603 1302 581 280 205
Rockland 3/0 17 80 3/0 17 80 603 1302 651 280 205
Sweetbriar 4/0 18 80 2/0 11 80 658 1421 709 315 240
Monmouth 4/0 18 80 4/0 18 80 658 1421 796 315 240
Pratt 250 26 95 3/0 17 80 732 1581 853 345 265
Wesleyan 350 37 95 4/0 18 80 831 1795 1118 415 320
Holyoke 500 37 95 300 37 95 980 2117 1545 495 395
Rider 500 37 95 350 37 95 980 2117 1598 495 395