Single Core Aluminum Conductor XLPE Insulation Covered Line Wire

Single Core Aluminum Conductor XLPE Insulation Covered Line Wire

Single Core Aluminum Conductor XLPE Insulation Covered Line Wire

single strand

Insulated

Stranded

Overhead

Aluminum

PVC

XLPE

Round Wire

Primarily Overhead Secondary Distribution

ISO9001, CCC

Jytop

Asrm B-230 / Asrm B-231/ Asrm B-232/Asrm B-399

25 ºC

75ºC

0.91

0.95

JYTOP

500m / Rolls

ASTM standards

Zhengzhou, China

8544492100

Product Description

Covered line overhead wire with aluminum conductor

Construction:
Conductors are aluminum alloy 1350 H19, 6201-T81, or ACSR Conductors, concentrically Stranded and covered for weather proofing with Polyethylene, High Density Polyethylene (HDPE) or Cross-linked Polyethylene (XLPE)

Applications:
Covered line wire is used for primarily for overhead secondary distribution lines. It is not an electrically insulated conductor and is treated as bare conductor when installed.

Standards:
Covered line wire meets or exceeds the following ASTM specifications:
ASTM B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
ASTM B-231 Aluminum Conductors, Concentric-Lay-Stranded.
ASTM B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
ASTM B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
Covered line wire meets or exceeds all applicable requirement of ANSI/ ICEA-S-70-547:

Covered Line Wire, ACSR/AAC/AAAC, Aluminum Conductor with XLPE/PE Insulated.

Item #

Size
AWG or MCM

Strand

Insulation
Thickness
(mils)

Outside
Diameter

Rated
Breaking
Strength

Weight
Per
MFT
XLP

Weight
Per
MFT
Poly

Ampacity
XLP

Walnut 6 6/1 30 mls .258 Inches 1131 Lbs 49 Lbs 47 Lbs 105 Amps
Butternut 4 6/1 30 mls .303 Inches 1170 Lbs 71.8 Lbs 70.0 Lbs 135 Amps
Hickory 4 7/1 30 mls .309 Inches 2240 Lbs 81.6 Lbs 79.8 Lbs 135 Amps
Pignut 2 6/1 45 mls .397 Inches 2710 Lbs 118.1 Lbs 114.8 Lbs 180 Amps
Beech 2 7/1 45 mls .405 Inches 3460 Lbs 134.1 Lbs 130.7 Lbs 180 Amps
Chestnut 1 6/1 45 mls .434 Inches 3370 Lbs 145.5 Lbs 141.8 Lbs 210 Amps
Almond 1/0 6/1 60 mls .506 Inches 4160 Lbs 190.4 Lbs 184.9 Lbs 235 Amps
Pecan 2/0 6/1 60 mls .554 Inches 5040 Lbs 234.2 Lbs 227.9 Lbs 270 Amps
Filbert 3/0 6/1 60 mls .607 Inches 6290 Lbs 288.5 Lbs 281.4 Lbs 305 Amps
Buckeye 4/0 6/1 60 mls .666 Inches 7930 Lbs 356.5 Lbs 348.5 Lbs 345 Amps
Hackberry 266.8 18/1 60 mls .711 Inches 6540 Lbs 354.8 Lbs 346.8 Lbs 435 Amps
Notes

  • The code words as given apply to conventional polyethylene line wire.
  • For 6201 aluminum conductors diameter equivalent to ACSR construction or 1350 aluminum equivalent.
  • Ampacity ratings based on 75 ºC conductor temperature, 25 ºC ambient temperature elevation – sea level. Emissivity 0.91 coefficient of absorption 0.95. Thermal reisitivity of covering -3ºC-Cm2/Watt-CM. Wind speed 2ft/sec in sun.
  • To determine correct ampacity by conductor size, please consult the National Electric Code.