N2xh, N2xh-J, N2xh-O, 0.6/1kv Solid Copper Halogen-Free and Flame-Resistant Power Cable
Product Description
Application:
Halogen-free power cables( N2XH ) with enhanced resistance to fire are used mostly in areas where harm to human life or material must be prevented in case of fire such as industrial and public buildings, hotels, subway systems, hospitals etc. These cables are suitable for dry and wet environments as well as for outer application but are not suitable for direct burial into earth or water.
Cable structure:
- Solid or stranded Cu core according to DIN VDE 0295 cl. 1 or 2, IEC 60228 cl. 1 or 2
- Core insulation of halogen free, cross-linked polyethylene compound
- Cores color coded according to DIN VDE 0293-308, green-yellow earth core in the outer layer, from 3 cores above
- Cores stranded in layers with optimal lay lenght
- For N2XCH version, concentric conductor of Cu tape or Cu wire
- Halogen free sheath of thermoplastic polymer compound, color black
Technical data:
- Power and control cable according to DIN VDE 0276 part 604
- Temperature range during installation from -5°C to +50°C; fixed from -40°C to +90°C
- Nominal voltage Uo/U 0,6/1 kV
- Test voltage a.c. 4000 V
- Minimum bending radius for single core approx. 15 x cable diameter, multicore approx. 12 x cable diameter
Tests:
- Flame-retardant to DIN VDE 0482 part 266-2/HD 405.3/BS 4066 PT3/EN 50266-2/IEC 60332-3
- Low corrosiveness of combustion gases to DIN VDE 0482 part 267/BS 6425 PT2/EN 50267-2-2/IEC 60754-2
- Halogen-free to DIN VDE 0482 part 267/BS 6425 PT1/EN 50267-2-1/IEC 60754-1
- Smoke density to DIN VDE 0482 part 268/HD 606/BS 7622 PT1,PT2/EN 50268-1,-2/IEC 61034-1,-2
Color codes N2XH :
- 2-core cable: blue/brown
- 3-core cable: brown/black/grey
- 4-core cable: blue/brown/black/grey
- from 7 conductors above, black cores with white numbering
Note:
- CE = the product is conformed with the EC Low-Voltage Directive 73/23/EEC.
- rm = round conductor stranded
- re = round conductor plain
- Conforms to RoHS.
Dimensions – Number of cores x cross-section |
Design | Construction of the individual keep the handlers safe | The outer diameter | thickness of insulation | shell thickness | Resistance to keep the handlers safe at 20 ° C | Weight Cu | weight of cable | packaging |
rated | about | rated | rated | max. | about | ||||
N x mm² | n x mm | mm | mm | mm | Ω/km | kg/km | kg/km | ||
1 x 1,5 | RE | 1 x 1,38 | 5,4 | 1,38 | 0,15 | 12,10 | 15,403 | 43 | REZ |
1 x 4 | RE | 1 x 2,25 | 6,4 | 2,25 | 0,20 | 4,61 | 5,869 | 75 | REZ |
1 x 16 | RM | 7 x 1,70 | 9,1 | 5,00 | 0,36 | 1,15 | 1,464 | 202 | REZ |
1 x 25 | RM | 7 x 2,13 | 11 | 6,10 | 0,48 | 0,727 | 0,925 | 302 | REZ |
1 x 70 | RM | 19 x 2,17 | 15 | 10,10 | 0,84 | 0,268 | 0,341 | 745 | REZ |
1 x 95 | RM | 19 x 2,52 | 17 | 11,90 | 0,97 | 0,193 | 0,246 | 986 | REZ |
1 x 185 | RM | 37 x 2,52 | 23 | 16,20 | 1,72 | 0,0991 | 0,126 | 1888 | REZ |
1 x 300 | RM | 61 x 2,50 | 28 | 20,60 | 2,34 | 0,0601 | 0,077 | 2945 | REZ |
2 x 1,5 | RE | 1 x 1,38 | 9 | 1,38 | 0,38 | 12,10 | 15,403 | 120 | REZ |
2 x 2,5 | RE | 1 x 1,78 | 10 | 1,78 | 0,45 | 7,41 | 9,433 | 154 | REZ |
2 x 16 | RM | 7 x 1,70 | 16 | 5,00 | 1,06 | 1,15 | 1,464 | 563 | REZ |
2 x 25 | RM | 7 x 2,13 | 20 | 6,10 | 1,52 | 0,727 | 0,925 | 840 | REZ |
2 x 35 | RM | 7 x 2,52 | 22 | 7,20 | 1,79 | 0,524 | 0,667 | 1106 | REZ |
2 x 120 | RM | 37 x 2,03 | 36 | 13,00 | 4,23 | 0,153 | 0,195 | 3343 | REZ |
2 x 300 | RM | 61 x 2,50 | 55 | 20,60 | 9,39 | 0,0601 | 0,077 | 8072 | REZ |
3 x 1,5 | RE | 1 x 1,38 | 9 | 1,38 | 0,44 | 12,10 | 15,403 | 135 | REZ |
3 x 2,5 | RE | 1 x 1,78 | 10 | 1,78 | 0,51 | 7,41 | 9,433 | 181 | REZ |
3 x 4 | RE | 1 x 2,25 | 11 | 2,25 | 0,60 | 4,61 | 5,869 | 242 | REZ |
3 x 10 | RE | 1 x 3,56 | 14 | 3,57 | 0,83 | 1,83 | 2,330 | 464 | REZ |
3 x 16 | RM | 7 x 1,70 | 17 | 5,00 | 1,22 | 1,15 | 1,464 | 697 | REZ |
N2XH | |||||||||
3 x 35 | RM | 7 x 2,52 | 23 | 7,20 | 2,08 | 0,524 | 0,667 | 1393 | REZ |
3 x 50 | RM | 19 x 1,83 | 26 | 8,30 | 2,56 | 0,387 | 0,493 | 1847 | REZ |
3 x 70 | RM | 19 x 2,17 | 31 | 10,10 | 3,43 | 0,268 | 0,341 | 2666 | REZ |
3 x 95 | RM | 19 x 2,52 | 36 | 11,90 | 4,17 | 0,193 | 0,246 | 3535 | REZ |
3 x 120 | RM | 37 x 2,03 | 38 | 13,00 | 4,74 | 0,153 | 0,195 | 4322 | REZ |
3 x 185 | RM | 37 x 2,52 | 48 | 16,20 | 7,40 | 0,0991 | 0,126 | 6742 | REZ |
3 x 300 | RM | 61 x 2,50 | 59 | 20,60 | 10,79 | 0,0601 | 0,077 | 10522 | REZ |
4 x 1,5 | RE | 1 x 1,38 | 10 | 1,38 | 0,52 | 12,10 | 15,403 | 163 | REZ |
4 x 2,5 | RE | 1 x 1,78 | 11 | 1,78 | 0,60 | 7,41 | 9,433 | 214 | REZ |
4 x 10 | RE | 1 x 3,56 | 16 | 3,57 | 1,03 | 1,83 | 2,330 | 586 | REZ |
4 x 16 | RM | 7 x 1,70 | 19 | 5,00 | 1,50 | 1,15 | 1,464 | 874 | REZ |
4 x 35 | RM | 7 x 2,52 | 26 | 7,20 | 2,57 | 0,524 | 0,667 | 1777 | REZ |
4 x 50 | RM | 19 x 1,83 | 29 | 8,30 | 3,15 | 0,387 | 0,493 | 2343 | REZ |
4 x 120 | RM | 37 x 2,03 | 43 | 13,00 | 5,98 | 0,153 | 0,195 | 5558 | REZ |
4 x 185 | RM | 37 x 2,52 | 53 | 16,20 | 9,35 | 0,0991 | 0,126 | 8657 | REZ |
4 x 240 | RM | 61 x 2,24 | 60 | 18,80 | 11,54 | 0,0754 | 0,096 | 11385 | REZ |
4 x 300 | RM | 61 x 2,50 | 65 | 20,60 | 13,44 | 0,0601 | 0,077 | 13539 | REZ |
N2XH | |||||||||
5 x 1,5 | RE | 1 x 1,38 | 11 | 1,38 | 0,62 | 12,10 | 15,403 | 193 | REZ |
5 x 4 | RE | 1 x 2,25 | 13 | 2,25 | 0,85 | 4,61 | 5,869 | 352 | REZ |
5 x 6 | RE | 1 x 2,76 | 15 | 2,76 | 0,99 | 3,08 | 3,921 | 475 | REZ |
5 x 16 | RM | 7 x 1,70 | 21 | 5,00 | 1,87 | 1,15 | 1,464 | 1081 | REZ |
5 x 25 | RM | 7 x 2,13 | 26 | 6,10 | 2,61 | 0,727 | 0,925 | 1631 | REZ |
5 x 50 | RM | 19 x 1,83 | 33 | 8,30 | 3,89 | 0,387 | 0,493 | 2915 | REZ |
REZ = cable in different lengths on reels or spools, and it is possible to cut the desired length
- Next: Copper PVC Indualted PVC Sheathed Flexible LSZH Electric Wire Cable
- Previous: 2.5mm Solid Copper Electric Wiring Price List of Wire Electrical House Wiring
Contact us
Similar Or Related
-
XLPE LSZH Cable Copper N2xh 1kv N2xh J N2xh O Flame Retardant Power Cable
-
0.6/1kv N2xh Flame-Retardant Halogen-Free Cable for Public Buildings
-
N2xh N2xh-J 4*150mm Halogen Free Flame Retardant Copper XLPE Insulated Cable
-
N2xh, N2xh-J, N2xh-O, 0.6/1kv Solid Copper Halogen-Free and Flame-Resistant Power Cable