Mv-105, Power Cable, 5 Kv, 3/C, Cu/Epr/Cts/CPE (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-105, Power Cable, 5 Kv, 3/C, Cu/Epr/Cts/CPE (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-105, Power Cable, 5 Kv, 3/C, Cu/Epr/Cts/CPE (ICEA S-93-639/NEMA WC71/UL 1072)

MV-105

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

Rubber

CPE

Round Wire

Bare Copper Wire

ISO, CCC

Mv-105

Boan

5 Kv

3

8 AWG-1000 Mcm

B

Tinned Copper Tape

DingAn

Heated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544601200

Product Description

MV-105, Power Cable, 5 KV, 3/C, Cu/EPR/Cts/CPE (ICEA S-93-639/NEMA WC71/UL 1072)

Features
UL Listed as MV-105. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application
Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry
locations, installed in raceways, duct, and open air, aerially or directly buried as permitted by NEC.

Standards
UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 kV – 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded Power Cables Rated 5 kV – 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 kV- 46 kV.

Specifications
Maximum operating voltage: 5 kV to 25 kV 100% and 133% IL
Maximum conductor operation temperatures: Wet and dry locations, Normal: 105°C, Emergency: 140°C, Short Circuit: 250°C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset ethylene propylene rubber (EPR). On request, Amorphous EPR.
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Metallic Shield: Soft annealed tinned copper tape, 5 mil thick, 25% minimum overlap.
6. Grounding (Optional): One or three tinned copper or covered conductors cabled with phase conductors.
7. Assembly: Conductors cabled with non-hygroscopic fillers, as required and binder tape.
8. Jacket: Black sunlight resistance and flame retardant chlorinated polyethylene (CPE) compound.

100% and 133% Insulation Levels (90 mil)
Size Number of Strands Conductor Nominal Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper Aluminum
AWG of kcmil in mil in lb/kft
8 7 0.13 80 1.2 810
6 7 0.17 80 1.27 990 816
4 7 0.21 80 1.37 1218 941
2 7 0.27 80 1.49 1556 1115
1 19 0.3 80 1.55 1815 1260
1/0 19 0.34 80 1.63 2094 1393
2/0 19 0.38 110 1.79 2557 1674
3/0 19 0.42 110 1.89 3017 1902
4/0 19 0.48 110 2 3548 2144
250 37 0.52 110 2.13 4072 2411
300 37 0.57 110 2.23 4657 2665
350 37 0.62 110 2.33 5243 2917
400 37 0.66 110 2.42 5861 3205
500 37 0.74 110 2.64 7091 3771
600 61 0.81 140 2.9 8462 4475
750 61 0.91 140 3.11 10132 5155
1000 61 1.06 140 3.43 12986 6352

Tags: , ,