Copper Core Steel Tape Armoured Cable (YJV22/YJV32/YJV)

Copper Core Steel Tape Armoured Cable (YJV22/YJV32/YJV)

Copper Core Steel Tape Armoured Cable (YJV22/YJV32/YJV)

YJV22/YJV32/YJV

Construction, Underground

Low and Medium Voltage Cable

DC Cable

XLPE

ISO, CE

SABS

Henan Jiapu

0.6/1 Kv 3.6/6 Kv

1-5 Cores

IEC60502 IEC60331 DIN BS

90 Degrees

jiapu

Wooden Drum or Wooden&Steel Drum

IEC, BS, DIN, ASTM

Henan China

4101962331

Product Description

Copper Core Steel Tape Armoured Cable (YJV22/YJV32/YJV)

XLPE Insulated Armoured Power Cables (6KV—35KV)

Application:
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.

Prpperty:

1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.

Specification:
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.

1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal Cross Section of Conductor Nominal Diameter of Conductor Nominal Thickness of Insulation Nominal Thickness of Copper Tape Screen Nominal Thickness of Inner Sheath Nominal Thickness of Steel Tape Armouring Nominal Thickness of PVC Sheath Approx. Overall Diameter Approx. Weight
Al Conductor Cu Conductor
No. X mm2 mm mm mm mm mm mm mm kg/m kg/m
3 X 25 6.0 2.5 0.1 1.2 0.2 1.9 37.9 1.87 2.32
3 X 35 6.9 2.5 0.1 1.3 0.5 2.0 41.5 2.10 2.73
3 X50 8.2 2.5 0.1 1.3 0.5 2.0 44.3 2.37 3.22
3 X 70 9.7 2.5 0.1 1.4 0.5 2.1 47.9 2.77 4.00
3 X 95 11.3 2.5 0.1 1.4 0.5 2.2 51.6 3.21 4.91
3 X 120 12.8 2.5 0.1 1.5 0.5 2.4 55.4 3.69 5.84
3 X 150 14.2 2.5 0.1 1.5 0.5 2.5 58.6 4.15 6.85
3 X 185 15.9 2.5 0.1 1.5 0.5 2.6 62.5 4.73 8.11
3 X 240 18.3 2.6 0.1 1.6 0.5 2.7 68.5 5.62 10.05
3 X 300 20.4 2.8 0.1 1.7 0.5 2.9 74.5 6.55 12.11
3 X 400 23.2 3.0 0.1 1.9 0.8 3.2 83.6 8.78 15.86
3 X 500 26.4 3.2 0.1 2.1 0.8 3.4 93.0 10.52 18.85

2)6/10(12)kV,6.35/11(12)kV,,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal Cross Section of Conductor Nominal Diameter of Conductor Nominal Thickness of Insulation Nominal Thickness of Copper Tape Screen Nominal Thickness of Inner Sheath Nominal Thickness of Steel Tape Armouring Nominal Thickness of PVC Sheath Approx. Overall Diameter Approx. Weight
Al Conductor Cu Conductor
No. X mm2 mm mm mm mm mm mm mm kg/m kg/m
3 X 25 6.0 3.4 0.1 1.3 0.5 2.0 43.4 2.16 2.61
3 X 35 6.9 3.4 0.1 1.3 0.5 2.0 45.4 2.36 2.99
3 X50 8.2 3.4 0.1 1.4 0.5 2.2 48.8 2.69 3.54
3 X 70 9.7 3.4 0.1 1.5 0.5 2.3 52.4 3.10 4.33
3 X 95 11.3 3.4 0.1 1.5 0.5 2.4 56.1 3.56 5.26
3 X 120 12.8 3.4 0.1 1.5 0.5 2.5 59.5 4.04 6.19
3 X 150 14.2 3.4 0.1 1.5 0.5 2.6 62.7 4.49 7.19
3 X 185 15.9 3.4 0.1 1.6 0.5 2.6 66.6 5.12 8.49
3 X 240 18.3 3.4 0.1 1.7 0.5 2.8 72.4 5.99 10.42
3 X 300 20.4 3.4 0.1 1.8 0.5 3.0 77.5 6.86 12.42
3 X 400 23.2 3.4 0.1 1.9 0.8 3.2 85.4 8.97 16.05
3 X 500 26.4 3.4 0.1 2.0 0.8 3.4 93.7 10.65 19.50

3)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal Cross Section of Conductor Nominal Diameter of Conductor Nominal Thickness of Insulation Nominal Thickness of Copper Tape Screen Nominal Thickness of Inner Sheath Nominal Thickness of Steel Tape Armouring Nominal Thickness of PVC Sheath Approx. Overall Diameter Approx. Weight
Al Conductor Cu Conductor
No. X mm2 mm mm mm mm mm mm mm kg/m kg/m
3 X 25 6.0 4.5 0.1 1.4 0.5 2.1 48.6 2.53 2.98
3 X 35 6.9 4.5 0.1 1.4 0.5 2.2 50.7 2.76 3.39
3 X50 8.2 4.5 0.1 1.5 0.5 2.3 53.9 3.10 3.95
3 X 70 9.7 4.5 0.1 1.5 0.5 2.4 57.4 3.51 4.74
3 X 95 11.3 4.5 0.1 1.5 0.5 2.6 61.2 4.05 5.75
3 X 120 12.8 4.5 0.1 1.6 0.5 2.6 64.7 4.56 6.72
3 X 150 14.2 4.5 0.1 1.6 0.5 2.7 67.9 5.04 7.74
3 X 185 15.9 4.5 0.1 1.7 0.5 2.8 71.9 5.66 9.04
3 X 240 18.3 4.5 0.1 1.8 0.5 3.0 77.7 6.56 11.00
3 X 300 20.4 4.5 0.1 1.9 0.8 3.2 84.1 8.39 13.96
3 X 400 23.2 4.5 0.1 2.0 0.8 3.3 90.5 9.71 16.79
3 X 500 26.4 4.5 0.1 2.1 0.8 3.5 98.8 11.45 20.57

4)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal Cross Section of Conductor Nominal Diameter of Conductor Nominal Thickness of Insulation Nominal Thickness of Copper Tape Screen Nominal Thickness of Inner Sheath Nominal Thickness of Steel Tape Armouring Nominal Thickness of PVC Sheath Approx. Overall Diameter Approx. Weight
Al Conductor Cu Conductor
No. X mm2 mm mm mm mm mm mm mm kg/m kg/m
3 X 25
3 X 35 6.9 5.5 0.1 1.5 0.5 2.4 55.6 3.14 3.77
3 X50 8.2 5.5 0.1 1.5 0.5 2.5 58.6 3.49 4.34
3 X 70 9.7 5.5 0.1 1.5 0.5 2.6 62.1 3.93 5.16
3 X 95 11.3 5.5 0.1 1.6 0.5 2.6 65.7 4.46 6.16
3 X 120 12.8 5.5 0.1 1.7 0.5 2.7 69.4 5.00 7.15
3 X 150 14.2 5.5 0.1 1.7 0.5 2.8 72.6 5.49 8.19
3 X 185 15.9 5.5 0.1 1.8 0.5 3.0 76.9 6.16 9.53
3 X 240 18.3 5.5 0.1 1.9 0.8 3.2 83.9 7.87 12.31
3 X 300 20.4 5.5 0.1 2.0 0.8 3.2 88.6 8.96 14.52
3 X 400 23.2 5.5 0.1 2.1 0.8 3.5 95.4 10.35 17.43
3 X 500 26.4 5.5 0.1 2.2 0.8 3.7 103.7 12.45 20.23

5)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/STA/PVC Armoured Power Cable

No.X Nominal Cross Section of Conductor Nominal Diameter of Conductor Nominal Thickness of Insulation Nominal Thickness of Copper Tape Screen Nominal Thickness of Inner Sheath Nominal Thickness of Steel Tape Armouring Nominal Thickness of PVC Sheath Approx. Overall Diameter Approx. Weight
Al Conductor Cu Conductor
No. X mm2 mm mm mm mm mm mm mm kg/m kg/m
3 X 25
3 X 35
3 X50 8.2 8.0 0.1 1.7 0.5 2.8 70.4 4.56 5.41
3 X 70 9.7 8.0 0.1 1.7 0.5 2.9 73.9 5.04 6.26
3 X 95 11.3 8.0 0.1 1.8 0.5 3.0 77.7 5.62 7.32
3 X 120 12.8 8.0 0.1 1.9 0.8 3.2 82.8 6.99 9.15
3 X 150 14.2 8.0 0.1 1.9 0.8 3.2 85.8 7.56 10.26
3 X 185 15.9 8.0 0.1 2.0 0.8 3.3 89.9 8.30 11.67
3 X 240 18.3 8.0 0.1 2.1 0.8 3.5 95.7 9.36 13.79
3 X 300 20.4 8.0 0.1 2.2 0.8 3.6 100.6 10.51 16.07
3 X 400 23.2 8.0 0.1 2.3 0.8 3.8 107.2 11.99 19.07
3 X 500 26.4 8.0 0.1 2.4 0.8 4.0 120.1 14.15 23.85