15kv 133% Insulation Power Cable Urd Mv Concentric Cable

15kv 133% Insulation Power Cable Urd Mv Concentric Cable

15kv 133% Insulation Power Cable Urd Mv Concentric Cable

Concentric Cable

Construction, Underground, Industrial, Power Station

High Voltage Cable

DC & AC

XLPE

PVC

Round Wire

Bare Copper Wire

ISO, CCC, CE, UL

Kema

Concentric Cable

Yifang

Single Core / Three Core

IEC, DIN , Icea,Bs,etc

XLPE / Tr-XLPE

Yifang cable

Steel Drum

CE, SGS

Zhengzhou, Henan

8544601200

Product Description

15kv 133% Insulation Power Cable URD MV Concentric Cable

APPLICATIONS

URD – TRXLPEMLPE insulated cables are designed and manufactured to meet the applications of primary underground distribution suitable for use in wet or dry location, direct burial, underground duct, and exposed to sunlight, To be used at 15kV upto 35kV at conductor temperatures not to exceed 90 deg. C for normal operation.

SPECIFICATIONS

TRXLPEMLP insulated URD cables meets or exceeds all applicable requirements of thefollowing standards, and guaranteed all cables manufactured and tested under this standards.

– ANSIIICEA S94-649

– AEIC CS-8

– ASTM B-3, ASTM B-8, ASTM B-230 & ASTM B-231

CONSTRUCTION

Conductor : Bare aluminium or copper, stranded class B compressed stranding

Conductor Shield :Extruded semi-conducting compound

Insulation : TRXLP (TreeRetardant XLPE) or XLPE

Insulation Shield : Extruded semi-conducting compound

Concentric Neutral : Uncoated copper concentric neutral wires (coated copper are optional)

Encapsulated Jacket : Non-conducting LLDPE embedded jacket with extruded red stripes.

PVC or Semi-conducting jacket are available upon request

MAXIMUM CONDUCTOR TEMPERATURE

Normal continuous at 90 ºC, Overload at 130 ºC and Short circuit at 250 ºC

FEATURES & BENEFITS, OPTIONS

– Triple extruded construction by dry curing process guarantees excellent quality of cables

– TRXLPE insulation offers proven superior life span than conventional XLPE cables

– Triplex type is optional, it brings you saving installation cost

– Strand-filled conductor & Water-blocking jacket is available upon request

DATE SHEET

Condctor Copper Neutral (1/3) diameter(inch) Weight (Pounds)
AWG orMCM Stranding

Number of Wires

SizeAWG (Solid) Conductor

Over

Insulation

Over Insul.

Shield

Over Neutral

Wires

Over

Encaps. Jkt.

Conductor

Concentric

Neutral

TotalNo

Jacket

Total WithJacket
1/0 19 wire 9 14 0.37 1.12 1.23 1.35 1.46 325.8 119.2 659 4926
2/0 19 wire 11 14 0.42 1.17 1.27 1.40 1.50 410.9 146.3 775 808
3/0 19 wire 14 14 0.47 1.22 1.32 1.48 1.59 518.1 185.9 900 923
4/0 19 wire 11 12 0.53 1.28 1.38 1.54 1.71 653.3 228.0 1110 1055
250 37 wire 13 12 0.57 1.33 1.44 1.64 1.81 771.9 282.1 1330 1292
350 37 wire 12 10 0.68 1.44 1.54 1.70 1.89 1081 398.0 1633 1519
500 37 wire 17 10 0.81 1.57 1.72 1.88 2.04 1544 543.5 2002 1886
750 61 wire 25 10 0.99 1.76 1.93 2.11 2.28 2316 801.5 2650 2289
1000 61 wire 33 10 1.14 1.92 2.06 2.27 2.43 3088 1058 3847