0.6/1kv 4 Core 95mm2 PVC Insulated Armour Power Cable

0.6/1kv 4 Core 95mm2 PVC Insulated Armour Power Cable

0.6/1kv 4 Core 95mm2 PVC Insulated Armour Power Cable

VV32 VLV32

Construction, Underground, Power Station

Low and Medium Voltage Cable

AC Cable

PVC

PVC

Round Wire

Bare Copper Wire

ISO, CE

VV32 Vlv32

JYTOP

600/1000V

1.5mm-800mm2

1,2,3,4,5,3+2,4+1,3+

Steel Wire Armour or Steel Tape Armour

CE, Kema, SABS, TUV

RNE DA

Standard Export Drum

IEC60502

Henan, China

85444921

Product Description

0.6/1kv 4 core 95mm2 pvc insulated armour power cable

The products can be produced and provided according to Chinese standard GB/T12706-2002(equivalent to IEC 60505).The factory can also manufacture the products that are based on British Standard(BS) and other standards.In addition,under the requirement of customers we can design and manufacture the products that have special performance.The products are used in fixed laying on transmission and distribution electrical lines of 50 HZ AC rated voltage up to 6 kV.

Specific Property for Using

1.The long-time permissible working temperature of cable conductive core is not more than 70ºC.
2.During short circuit(max permanent time is not more than 5 seconds),the max temperature of cable conductor is not more than 165ºC.
3.The difference level of laying cable is not restricted.When laying the cable,ambient temperature is not lower than 0ºC.
4.They have good chemical stability,and properties of acid resistance,alkali resistance,salt resistance,oil resistance,solvent resistance and flame resistance.
5.Light weight,good bending property and easy installation and maintenance

3.1Type and Name:

Type

Name

VV VLV

Copper(aluminum)Conductor,PVC insulated and Sheathed Power Cable

VY VLY

Copper(aluminum)Conductor,PVC insulated,PE Sheathed Power Cable

VV22VLV22

Copper(aluminum)Conductor,PVC insulated,Steel-tape Armoured,PVC Sheathed Power Cable

VV23VLV23

Copper(aluminum)Conductor,PVC insulated,Steel-tape Armoured,PE Sheathed Power Cable

VV32VLV32

Copper(aluminum)Conductor,PVC insulated,Fine Steel-wire Armoured,PVC Sheathed Power Cable

VV33VLV33

Copper(aluminum)Conductor,PVC insulated,PE Sheathed Power Cable

VV42VLV42

Copper(aluminum)Conductor,PVC insulated,Thick Steel-wire Armoured,PVC Sheathed Power Cable

VV43VLV43

Copper(aluminum)Conductor,PVC insulated,Thick Steel-wire Armoured,PE Sheathed Power Cable

3.2 Nominal thickness of insulation

Nominal Cross
Sectrion (mm2)

Insulated
Thickness(mm)

Voltage(KV)

1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000

0.6/1

0.8 0.8 0.8 1 1 1 1 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 2.8 2.8 2.8 3.0

3.6/6

3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4

3.3 DC resistance of conductor

Nominal
Cross
Section
(mm2)

at 20ºC,DC resistance is
not more than (Ω/km)

Nominal
Cross
Section
(mm2)

at 20ºC,DC resistance is
not more than (Ω/km)

Nominal
Cross
Section
(mm2)

at 20ºC,DC resistance is
not more than (Ω/km)

Copper Core

Aluminum Core

Copper Core

Aluminum Core

Copper Core

Aluminum Core

1.5

12.1

18.1

35

0.524

0.868

240

0.0754

0.125

2.5

7.41

12.1

50

0.387

0.641

300

0.0601

0.100

4

4.61

7.41

70

0.268

0.443

400

0.0470

0.0778

6

3.08

4.61

95

0.193

0.320

500

0.0366

0.0605

10

1.83

3.08

120

0.153

0.253

630

0.0283

0.0469

16

1.15

1.91

150

0.124

0.206

800

0.0221

0.0369

25

0.727

1.20

185

0.0991

0.164

1000

0.0176

0.0291

3.4 Insulation Resistance

Test item

PVC insulated Cable

XLPE insulated Power Cable

0.6/1KV

3.6/6KV

volume resistivity (ρΩ.cm)
min.at 20ºC
at top rated temperature min.

1013
1010

1014
1011


1012

Ki insulation resistivity constant(MΩ.km)
min.at 20ºC
at top rated temperature min.

36.7
0.037

367
0.37


3.67

3.5 insulation resistance

UO/U(KV)

Us(KV)

T(min

0.6/1

3.5

5

3.6/6

12.5

5

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.