Product Description
NOTE: If you want to know more details about this kind of products, please visit our website(homepage) because we have no ways to show so much information on this platform. Thank you.
Size | Calculated area | Stranding and wire diameter |
Overall diameter |
Linear mass |
Rated strength | Max. DC resistance at 20ºC |
mm 2 | mm 2 | mm | mm | kg/km | daN | Ω/km |
16 | 15.89 | 7/1.70 | 5.1 | 44 | 290 | 1.8018 |
25 | 24.25 | 7/2.10 | 6.3 | 67 | 425 | 1.1808 |
35 | 34.36 | 7/2.50 | 7.5 | 94 | 585 | 0.8332 |
50 | 49.48 | 7/3.00 | 9.0 | 135 | 810 | 0.5786 |
50 | 48.36 | 19/1.80 | 9.0 | 133 | 860 | 0.5950 |
70 | 65.82 | 19/2.10 | 10.5 | 181 | 1150 | 0.4371 |
95 | 93.27 | 19/2.50 | 12.5 | 256 | 1595 | 0.3084 |
120 | 117.00 | 19/2.80 | 14.0 | 322 | 1910 | 0.2469 |
150 | 147.10 | 37/2.25 | 15.2 | 406 | 2570 | 0.1960 |
185 | 181.60 | 37/2.50 | 17.5 | 501 | 3105 | 0.1587 |
240 | 242.54 | 61/2.25 | 20.2 | 670 | 4015 | 0.1191 |
300 | 299.43 | 61/2.50 | 22.5 | 827 | 4850 | 0.09650 |
400 | 400.14 | 61/2.89 | 26.0 | 1105 | 6190 | 0.07221 |
500 | 499.83 | 61/3.23 | 29.1 | 1381 | 7600 | 0.05781 |
625 | 626.20 | 91/2.96 | 32.6 | 1733 | 9690 | 0.04625 |
800 | 802.10 | 91/3.35 | 36.8 | 2219 | 12055 | 0.03611 |
1000 | 999.71 | 91/3.74 | 41.1 | 2766 | 14845 | 0.02897 |