Product Details
10kV Aluminum core XLPE Insulated unarmoured power cable
1. Applications
This product is applied to the fixed installation, power transmission and power distribution circuit of rated voltage 10KV and below.
XLPE insulated power cable has a number of advantages compared with paper insulated and PVC insulated cables. XLPE cable has high electric property, mechanical property, heat aging performance, environmental stress crack resistance, chemical corrosion resistance, and it also has simple structure, convenient operation and it is not restricted by laying in large difference of level. It can be applied in high temperature of 90 degree for a long time.
2. Standard
IEC 60502, IEC60332, IEC 60754
3. Specification
Rated Voltage, No. of Core and Range of Sectional Area
1. Applications
This product is applied to the fixed installation, power transmission and power distribution circuit of rated voltage 10KV and below.
XLPE insulated power cable has a number of advantages compared with paper insulated and PVC insulated cables. XLPE cable has high electric property, mechanical property, heat aging performance, environmental stress crack resistance, chemical corrosion resistance, and it also has simple structure, convenient operation and it is not restricted by laying in large difference of level. It can be applied in high temperature of 90 degree for a long time.
2. Standard
IEC 60502, IEC60332, IEC 60754
3. Specification
Rated Voltage, No. of Core and Range of Sectional Area
Rated voltage (kv) Sectional area (mm2) No. of core |
1st class | 0.6/1 | 3.6/6 | 6/6 | 8.7/10 | 12/20 | 18/20 | 21/35 | 26/35 |
2nd class | 6/10 | 8.7/15 | 18/30 | ||||||
1 Core | 2.5-400 | 25-500 | 25-500 | 25-500 | 35-500 | 50-500 | 50-500 | 50-500 | |
2 Core | 2.5-300 | ||||||||
3 Core | 2.5-300 | 25-400 | 25-400 | 25-400 | 35-400 | 50-400 | 50-400 | 50-400 | |
4 Core | 2.5-300 | ||||||||
5 Core | 2.5-300 |
4. The main Technical Index of the cable
1). DC resistance: conductor resistance of finished cable at 20ºC per kilometer is not more than the following values.
Nominal section area (mm2) | 1.5 | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 |
Aluminum core | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.91 | 1.20 | 0.868 | 0.641 | 0.443 |
2). Voltage Test and Partial Discharge Test
Rate voltage Uo (kv) Item |
0.6/1 | 1.8/3 | 3.6/6 | 6/6 6/10 | 8.7/10 8.7/15 | 12/20 | 18/20 18/30 | 21/35 | 26/35 | |
Voltage | Test voltage | 3.5 | 6.5 | 12.5 | 21 | 30.5 | 42 | 63 | 73.5 | 91 |
Test time | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | |
Partial discharge test | Test voltage | – | – | 6.2 | 10.4 | 15.1 | 20.8 | 31.1 | 36.3 | 45 |
Discharge capacity | – | – | 10 | 10 | 10 | 10 | 10 | 10 | 10 |