8.7/15kv Copper Core XLPE Insulated PVC Sheathed Power Cable

8.7/15kv Copper Core XLPE Insulated PVC Sheathed Power Cable

Quick Details

8.7/15kv Copper Core XLPE Insulated PVC Sheathed Power Cable

YJV

Zhonghua

YJV

ISO, CCC, UL

Bare Copper Wire

Round Wire

PVC

XLPE

AC Cable

Low and Medium Voltage Cable

Construction, Underground, Industrial, Power Station

ZHONGHUA

Steel&Wooden Drum or as Customer Required

1.5-400mm2

Hubei, Wuhan

8544492100

Product Details

8.7/15kV Copper core XLPE Insulated PVC Sheathed Power Cable

1. Applications
This product is applied to the fixed installation, power transmission and power distribution circuit of rated voltage 35KV and below.
XLPE insulated power cable has a number of advantages compared with paper insulated and PVC insulated cables. XLPE cable has high electric property, mechanical property, heat aging performance, environmental stress crack resistance, chemical corrosion resistance, and it also has simple structure, convenient operation and it is not restricted by laying in large difference of level. It can be applied in high temperature of 90 degree for a long time.

2. Standard
 IEC 60502,  IEC60332,  IEC 60754

3. Specification
 Rated Voltage, No. of Core and Range of Sectional Area

Rated voltage (kv)
Sectional area (mm2)
No. of core
1st class 0.6/1 3.6/6 6/6 8.7/10 12/20 18/20 21/35 26/35
2nd class     6/10 8.7/15   18/30    
1 Core   2.5-400 25-500 25-500 25-500 35-500 50-500 50-500 50-500
2 Core   2.5-300              
3 Core   2.5-300 25-400 25-400 25-400 35-400 50-400 50-400 50-400
4 Core   2.5-300              
5 Core   2.5-300              

4. The main Technical Index of the cable
1).  DC resistance: conductor resistance of finished cable at 20ºC per kilometer is not more than the following values.

Nominal section area (mm2) 1.5 2.5 4 6 10 16 25 35 50 70
Copper core 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268

 2). Voltage Test and Partial Discharge Test

Rate voltage Uo (kv)
Item
0.6/1 1.8/3 3.6/6 6/6 6/10 8.7/10 8.7/15 12/20 18/20 18/30 21/35 26/35
Voltage Test voltage 3.5 6.5 12.5 21 30.5 42 63 73.5 91
Test time 5 5 5 5 5 5 5 5 5
Partial discharge test Test voltage 6.2 10.4 15.1 20.8 31.1 36.3 45
Discharge capacity 10 10 10 10 10 10 10

5. Production Process

Tags: , ,