Yjv Yjlv Yjv22 Yjlv22 Yjv32 Yjlv32 4X240mm2 Cu/XLPE/PVC Power Cable
Product Description
DESCRIPTION
CONSTRUCTION
- Conductor: Plain Annealed Copper, Class 2 Stranded Circular, Compacted or Sectored
- Insulation: Cross-linked Polyethylene (XLPE) Compound
- Insulation Color :
- 4 Cores: Brown, Black, Grey,Blue or Red, Yellow, Blue, Black
- Assembly :
- Cores cabled together with filler and covered with Polyester (PET) Tape
- Insulation Color :
- Outer Sheath: Polyvinyl Chloride (PVC) Compound Type ST 2
- Outer Sheath Color : Black
ELECTRICAL CHARACTERISTICS
- Operating Voltage, Uo/U : 0.6/1KV
- Operating Temperature : -15ºC to 90ºC
- Final Short Circuit Temperature : 250ºC
- Test Voltage : 3.5kV for 5 minutes
- Current Carrying Capacity
- Clipped Direct (Ref Method C)
- One 3 or 4-Core Cable, 3-Phase A.C : 73A
- In free air or on a perforated cable tray etc, horizontal or vertical (Ref method E)
- One 3 or 4-Core Cable, 3-Phase A.C : 78A
- Direct in Ground or in ducting in ground, in or around building (Ref method D)
- One 3 or 4-Core Cable, 3-Phase A.C : 58A
- Clipped Direct (Ref Method C)
REFERENCE STANDARD
- Design Specification: IEC60502-1
- Conductor: IEC60228, BS EN60228
- Flame Retardancy: IEC60332-1, BS EN60332-1
INSTALLATION REFERENCE
- Minimum Bending Radius(mm): 8 x cable overall diameter
- Max. Pulling Tension (N/mm2) : 70ºC
Type | Description |
VV 0.6/1kV | 0.6/1kV copper conductor, PVC insulation, PVC sheath, low voltage power cable |
VLV 0.6/1kV | 0.6/1kV aluminum conductor, PVC insulation, PVC sheath, low voltage power cable |
VV22 0.6/1kV | 0.6/1kV copper conductor, PVC insulation, PVC inner sheath, Galvanized steel tape armored, PVC outer sheath, low voltage power cable |
VLV22 0.6/1kV | 0.6/1kV aluminum conductor, PVC insulation, PVC inner sheath, Galvanized steel tape armored, PVC outer sheath, low voltage power cable |
VV32 0.6/1kV | 0.6/1kV copper conductor, PVC insulation, PVC inner sheath, Galvanized steel wire armored, PVC outer sheath, low voltage power cable |
VLV32 0.6/1kV | 0.6/1kV aluminum conductor, PVC insulation, PVC inner sheath, Galvanized steel wire armored, PVC outer sheath, low voltage power cable |
YJV 0.6/1kV | 0.6/1kV copper conductor, XLPE insulation, PVC sheath, low voltage power cable |
YJLV 0.6/1kV | 0.6/1kV aluminum conductor, XLPE insulation, PVC sheath, low voltage power cable |
YJV22 0.6/1kV | 0.6/1kV copper conductor, XLPE insulation, PVC inner sheath, Galvanized steel tape armored, PVC outer sheath, low voltage power cable |
YJLV22 0.6/1kV | 0.6/1kV aluminum conductor, XLPE insulation, PVC inner sheath, Galvanized steel tape armored, PVC outer sheath, low voltage power cable |
YJV32 0.6/1kV | 0.6/1kV copper conductor, XLPE insulation, PVC inner sheath, Galvanized steel wire armored, PVC outer sheath, low voltage power cable |
YJLV32 0.6/1kV | 0.6/1kV aluminum conductor, XLPE insulation, PVC inner sheath, Galvanized steel wire armored, PVC outer sheath, low voltage power cable |
YJY 0.6/1kV | 0.6/1kV copper conductor, XLPE insulation, PE sheath, low voltage power cable |
YJLY 0.6/1kV | 0.6/1kV aluminum conductor, XLPE insulation, PE sheath, low voltage power cable |
YJY23 0.6/1kV | 0.6/1kV copper conductor, XLPE insulation, PE inner sheath, Galvanized steel tape armored, PE outer sheath, low voltage power cable |
YJLY23 0.6/1kV | 0.6/1kV aluminum conductor, XLPE insulation, PE inner sheath, Galvanized steel tape armored, PE outer sheath, low voltage power cable |
YJY33 0.6/1kV | 0.6/1kV copper conductor, XLPE insulation, PE inner sheath, Galvanized steel wire armored, PE outer sheath, low voltage power cable |
YJLY33 0.6/1kV | 0.6/1kV aluminum conductor, XLPE insulation, PE inner sheath, Galvanized steel wire armored, PE outer sheath, low voltage power cable |
WDZ-YJE 0.6/1kV | 0.6/1kV copper conductor, XLPE insulation, low smoke zero halogen flame retardant sheath, low voltage power cable |
WDZ-YJLE 0.6/1kV | 0.6/1kV aluminum conductor, XLPE insulation, low smoke zero halogen flame retardant sheath, low voltage power cable |
WDZ-YJE23 0.6/1kV | 0.6/1kV copper conductor, XLPE insulation, low smoke zero halogen flame retardant inner sheath, Galvanized steel tape armored, low smoke zero halogen flame retardant outer sheath, low voltage power cable |
WDZ-YJLE23 0.6/1kV | 0.6/1kV aluminum conductor, XLPE insulation, low smoke zero halogen flame retardant inner sheath, Galvanized steel tape armored, low smoke zero halogen flame retardant outer sheath, low voltage power cable |
WDZ-YJE33 0.6/1kV | 0.6/1kV copper conductor, XLPE insulation, low smoke zero halogen flame retardant inner sheath, Galvanized steel wire armored, low smoke zero halogen flame retardant outer sheath, low voltage power cable |
WDZ-YJLE33 0.6/1kV | 0.6/1kV aluminum conductor, XLPE insulation, low smoke zero halogen flame retardant inner sheath, Galvanized steel wire armored, low smoke zero halogen flame retardant outer sheath, low voltage power cable |
Note :
Conductor Shape
1.5 – 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 – 300 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
1.5 – 50 sqmm supplied in wooden drum @ 1000 m
70 – 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%
YJV / YJLV 11,5 – 1kV | YJV / YJLV 12,5 – 1kV | YJV / YJLV 14,0 – 1kV | YJV / YJLV 16,0 – 1kV | YJV / YJLV 110 – 1kV |
YJV / YJLV 116 – 1kV | YJV / YJLV 125 – 1kV | YJV / YJLV 135 – 1kV | YJV / YJLV 150 – 1kV | YJV / YJLV 170 – 1kV |
YJV / YJLV 195 – 1kV | YJV / YJLV 1120 – 1kV | YJV / YJLV 1150 – 1kV | YJV / YJLV 1185 – 1kV | YJV / YJLV 1240 – 1kV |
YJV / YJLV 21,5 – 1kV | YJV / YJLV 21,5+11,0 – 1kV | YJV / YJLV 21,5+11,5 – 1kV | YJV / YJLV 22,5 – 1kV | YJV / YJLV 22,5+11,5 – 1kV |
YJV / YJLV 24,0 – 1kV | YJV / YJLV 24,0+12,5 – 1kV | YJV / YJLV 26,0 – 1kV | YJV / YJLV 26,0+12,5 – 1kV | YJV / YJLV 26,0+14,0 – 1kV |
YJV / YJLV 210 – 1kV | YJV / YJLV 210+14,0 – 1kV | YJV / YJLV 210+16,0 – 1kV | YJV / YJLV 216 – 1kV | YJV / YJLV 216+16,0 – 1kV |
YJV / YJLV 216+110 – 1kV | YJV / YJLV 225 – 1kV | YJV / YJLV 225+110 – 1kV | YJV / YJLV 225+116 – 1kV | YJV / YJLV 235 – 1kV |
YJV / YJLV 235+116 – 1kV | YJV / YJLV 250 – 1kV | YJV / YJLV 250+116 – 1kV | YJV / YJLV 250+125 – 1kV | YJV / YJLV 270 – 1kV * |
YJV / YJLV 270+125 – 1kV | YJV / YJLV 270+135 – 1kV | YJV / YJLV 295 – 1kV * | YJV / YJLV 295+135 – 1kV | YJV / YJLV 295+150 – 1kV |
YJV / YJLV 2120 – 1kV * | YJV / YJLV 2120+135 – 1kV | YJV / YJLV 2120+170 – 1kV | YJV / YJLV 2150 – 1kV * | YJV / YJLV 2150+150 – 1kV |
YJV / YJLV 2150+170 – 1kV | YJV / YJLV 2185 – 1kV * | YJV / YJLV 2185+150 – 1kV | YJV / YJLV 2185+195 – 1kV | YJV / YJLV 2240 – 1kV * |
YJV / YJLV 2240+170 – 1kV | YJV / YJLV 2240+1120 – 1kV | YJV / YJLV 31,5 – 1kV | YJV / YJLV 31,5+11,0 – 1kV | YJV / YJLV 31,5+11,5 – 1kV |
YJV / YJLV 32,5 – 1kV | YJV / YJLV 32,5+11,5 – 1kV | YJV / YJLV 34,0 – 1kV | YJV / YJLV 34,0+12,5 – 1kV | YJV / YJLV 36,0 – 1kV |
YJV / YJLV 36,0+12,5 – 1kV | YJV / YJLV 36,0+14,0 – 1kV | YJV / YJLV 310 – 1kV | YJV / YJLV 310+14,0 – 1kV | YJV / YJLV 310+16,0 – 1kV |
YJV / YJLV 316 – 1kV | YJV / YJLV 316+16,0 – 1kV | YJV / YJLV 316+110 – 1kV | YJV / YJLV 325 – 1kV | YJV / YJLV 325+110 – 1kV |
YJV / YJLV 325+116 – 1kV | YJV / YJLV 335 – 1kV | YJV / YJLV 335+116 – 1kV | YJV / YJLV 350 – 1kV | YJV / YJLV 350+116 – 1kV |
YJV / YJLV 350+125 – 1kV | YJV / YJLV 370 – 1kV | YJV / YJLV 370+125 – 1kV | YJV / YJLV 370+135 – 1kV | YJV / YJLV 395 – 1kV |
YJV / YJLV 395+135 – 1kV | YJV / YJLV 395+150 – 1kV | YJV / YJLV 3120 – 1kV | YJV / YJLV 3120+135 – 1kV | YJV / YJLV 3120+170 – 1kV |
YJV / YJLV 3150 – 1kV | YJV / YJLV 3150+150 – 1kV | YJV / YJLV 3150+170 – 1kV | YJV / YJLV 3185 – 1kV | YJV / YJLV 3185+150 – 1kV |
YJV / YJLV 3185+195 – 1kV | YJV / YJLV 3240 – 1kV | YJV / YJLV 3240+170 – 1kV | YJV / YJLV 3240+1120 – 1kV | YJV / YJLV 41,5 – 1kV |
YJV / YJLV 41,5+11,0 – 1kV | YJV / YJLV 41,5+11,5 – 1kV | YJV / YJLV 42,5 – 1kV | YJV / YJLV 42,5+11,5 – 1kV | YJV / YJLV 44,0 – 1kV |
YJV / YJLV 44,0+12,5 – 1kV | YJV / YJLV 46,0 – 1kV | YJV / YJLV 46,0+12,5 – 1kV | YJV / YJLV 46,0+14,0 – 1kV | YJV / YJLV 410 – 1kV |
YJV / YJLV 410+14,0 – 1kV | YJV / YJLV 410+16,0 – 1kV | YJV / YJLV 416 – 1kV | YJV / YJLV 416+16,0 – 1kV | YJV / YJLV 416+110 – 1kV |
YJV / YJLV 425 – 1kV | YJV / YJLV 425+110 – 1kV | YJV / YJLV 425+116 – 1kV | YJV / YJLV 435 – 1kV | YJV / YJLV 450 – 1kV |
YJV / YJLV 470 – 1kV | YJV / YJLV 495 – 1kV | YJV / YJLV 4120 – 1kV | YJV / YJLV 4150 – 1kV | YJV / YJLV 4185 – 1kV |
YJV / YJLV 4240 – 1kV | YJV / YJLV 51,5 – 1kV | YJV / YJLV 52,5 – 1kV | YJV / YJLV 54,0 – 1kV | YJV / YJLV 56,0 – 1kV |
YJV / YJLV 510 – 1kV | YJV / YJLV 516 – 1kV | YJV / YJLV 525 – 1kV | YJV / YJLV 535 – 1kV | YJV / YJLV 550 – 1kV |
YJV / YJLV 570 – 1kV | YJV / YJLV 595 – 1kV | YJV / YJLV 5120 – 1kV | YJV / YJLV 5150 – 1kV | YJV / YJLV 5185 – 1kV |
YJV / YJLV 5240 – 1kV |
*Further information about rating factor for certain cable arrangement can be found on supplementary technical information.
Electrical Data
Conductor | Inductance | Current – Carrying Capacity at 30° C * | Short circuit current at 1 sec | |||
Nom. Cross Section Area | DC Resistance at 20°C | AC Resistance at 90°C | ||||
in air | in ground | |||||
(mm²) | Max. (Ω/km) | Max. (Ω/km) | (mH/km) | Max. (A) | Max. (A) | Max. (kA) |
1.5 | 12.1 | 15.429 | 0.315 | 27 | 32 | 0.21 |
2.5 | 7.41 | 9.449 | 0.293 | 36 | 42 | 0.36 |
4 | 4.61 | 5.878 | 0.275 | 48 | 55 | 0.57 |
6 | 3.08 | 3.927 | 0.263 | 60 | 68 | 0.86 |
10 | 1.83 | 2.334 | 0.248 | 83 | 91 | 1.43 |
16 | 1.15 | 1.467 | 0.238 | 110 | 118 | 2.29 |
25 | 0.727 | 0.927 | 0.240 | 148 | 152 | 3.58 |
35 | 0.524 | 0.669 | 0.233 | 183 | 183 | 5.01 |
50 | 0.387 | 0.494 | 0.232 | 214 | 210 | 7.15 |
70 | 0.268 | 0.343 | 0.229 | 269 | 256 | 10.01 |
95 | 0.193 | 0.247 | 0.224 | 334 | 309 | 13.59 |
120 | 0.153 | 0.197 | 0.223 | 386 | 350 | 17.16 |
150 | 0.124 | 0.160 | 0.224 | 449 | 395 | 21.45 |
185 | 0.0991 | 0.129 | 0.225 | 512 | 444 | 26.46 |
240 | 0.0754 | 0.099 | 0.223 | 604 | 513 | 34.32 |
300 | 0.0601 | 0.081 | 0.221 | 692 | 577 | 42.90 |