Xtmu, Power Cable, 600V, Cu/XLPE/PVC/PVC (ICEA S-95-658)
Product Description
600 V Multiple Copper Conductor, XLPE Insulation and Outer PVC Jacket
Application
Primary power and distribution circuits in industrial, commercial and power circuit generating plants. XTMU cables can be marked for CT
Use to be installed in ladder cable tray, according NEC Article 318.
Standards / Testing Specifications
? XTMU meets or exceeds the requirements of ICEA S-95-658.
Detail Description or Construction
Conductor
Compressed or Compacted copper conductor class B
Insulation
Cross-linked Polyethylene (XLPE) 90° C
Jacket
Extruded black sunlight resistant, flame retardant, oils resistant PVC jacket with excellent mechanical properties
Packaging
Non-returnable wooden drums
Options
? CT USE applications
? Black polyethylene jacket
Marking
CT Use.
Installation
XTMU cables may be installed in wet or dry locations at maximum operating temperature of 90° C on the conductor for normal operation; 130° C for emergency and 250° C for short circuit conditions. Cables may be installed indoor and outdoor, exposed to sunlight, in raceway, conduit, duct or aerially supported by a messenger and directly buried according NEC 250-51.
Conductor Size | Nominal Area | Nominal Insulation Thickness | Nominal Jacket Thickness | Total OD | Total Weight | Ampacity (A) | ||
AWG / MCM | mm2 | mm | mm | mm | kg / km | Buried Duct 20°C Amb. Temp | Direct Buried 20°C Amb. Temp | Free Air 40°C Amb. Temp |
CABLE TYPE XTMU 90°C 600 VOLTS 3 CONDUCTORS | ||||||||
14 | 2.08 | 0.76 | 1.14 | 10.2 | 155 | 25 | 35 | 25 |
12 | 3.31 | 0.76 | 1.14 | 11.2 | 206 | 32 | 47 | 32 |
10 | 5.26 | 0.76 | 1.14 | 12.7 | 285 | 43 | 62 | 43 |
8 | 8.37 | 1.14 | 1.52 | 16.7 | 483 | 59 | 83 | 59 |
6 | 13.3 | 1.14 | 1.52 | 18.7 | 673 | 78 | 106 | 79 |
4 | 21.2 | 1.14 | 1.52 | 20.7 | 931 | 102 | 137 | 104 |
2 | 33.6 | 1.14 | 2.03 | 24.9 | 1,448 | 133 | 178 | 138 |
1 | 42.4 | 1.40 | 2.03 | 29.3 | 1,867 | 154 | 201 | 161 |
1/0 | 53.5 | 1.40 | 2.03 | 31.8 | 2,285 | 177 | 229 | 186 |
2/0 | 67.4 | 1.40 | 2.03 | 34.3 | 2,794 | 202 | 260 | 215 |
3/0 | 85.0 | 1.40 | 2.03 | 37.2 | 3,415 | 231 | 297 | 249 |
4/0 | 107 | 1.40 | 2.03 | 40.3 | 4,173 | 264 | 335 | 287 |
250 | 127 | 1.65 | 2.79 | 44.0 | 4,952 | 292 | 367 | 320 |
350 | 177 | 1.65 | 2.79 | 49.4 | 6,619 | 354 | 442 | 394 |
500 | 253 | 1.65 | 2.79 | 56.5 | 9,137 | 429 | 531 | 487 |
CABLE TYPE XTMU 90°C 600 VOLTS 4 CONDUCTORS | ||||||||
14 | 2.08 | 0.76 | 1.14 | 11.1 | 185 | 20 | 28 | 20 |
12 | 3.31 | 0.76 | 1.14 | 12.4 | 250 | 25 | 37 | 25 |
10 | 5.26 | 0.76 | 1.52 | 14.7 | 379 | 34 | 49 | 34 |
8 | 8.37 | 1.14 | 1.52 | 18.4 | 596 | 47 | 66 | 47 |
6 | 13.3 | 1.14 | 1.52 | 20.6 | 834 | 62 | 85 | 63 |
4 | 21.2 | 1.14 | 2.03 | 24.7 | 1,272 | 82 | 110 | 83 |
2 | 33.6 | 1.14 | 2.03 | 27.5 | 1,823 | 106 | 142 | 110 |
1 | 42.4 | 1.40 | 2.03 | 32.5 | 2,375 | 123 | 161 | 129 |
1/0 | 53.5 | 1.40 | 2.03 | 35.0 | 2,876 | 142 | 183 | 149 |
2/0 | 67.4 | 1.40 | 2.03 | 37.9 | 3,515 | 162 | 208 | 172 |
3/0 | 85.0 | 1.40 | 2.03 | 41.0 | 4,313 | 185 | 238 | 199 |
4/0 | 107 | 1.40 | 2.79 | 46.2 | 5,474 | 211 | 268 | 230 |
250 | 127 | 1.65 | 2.79 | 48.5 | 6,276 | 234 | 294 | 256 |
350 | 177 | 1.65 | 2.79 | 54.6 | 8,427 | 283 | 354 | 315 |
500 | 253 | 1.65 | 2.79 | 62.6 | 11,703 | 343 | 425 | 390 |