Power cable
1. Application
(1)XLPE insulated power cable
XLPE insulated power cable is suitable for laying fixed in power transmission and distribution lines with A.C. 50HZ and rated voltage of 0.6/1kV.
XLPE insulated power cable do not has excellent electric, mechanical properties,but also has powerful resistance against chemical corrosion,heat resistance and environmental stress resistance. Its structure is simple. The long period operating temperature is +90 °C. It is convenient to use and can be laid with no restriction of different elevation.

(2)PVC insulated power cable
PVC insulated power cable is suitable for rated AC voltage 0.6/1kv and below electric distribution lines without flame-retardant or fire-resistant requirements.

2.Construction
Conductor: Solid or stranded copper
Insulation: Cross-linked polyethylene (XLPE) or Polyvinyl chloride (PVC)
Filler: Polypropylene filament with lapped binding tape
Binder: Binding tape
Inner sheath: Polyvinyl chloride (PVC)
Amour: Galvanized steel wire armored(SWA) or steel tape armored(STA)
Sheath: Polyvinyl chloride (PVC)
Cores :single core, two cores, three cores, four cores (3+1 cores), five cores (3+2 cores).

Voltage:
0.6/1kV, 1.8/3kV, 3.6/6kV, 6/10kV,6.35/11kV, 8.7/15kV, 12/20kV,12.7/22kV, 18/30kV,19/33kV,26/35kV
In the voltage designation of cables U0/U(Um):
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment maybe used.

3.Standard
IEC60502,and BS6346, VDE, AS/NZS,etc

4.Specification
IEC 60502

Section Conductor Diameter Insulation Thickness Bedding Thickness Armour Diameter Sheath Thickness Overall Diameter Cable Weight
No.xmm² mm mm mm mm mm mm Kg/Km
Two Cores XLPE Insulated SWA Armoured Power Cable
2×1.5 1.6 0.7 1 0.9 1.8 13.5 360
2×2.5 2 0.7 1 0.9 1.8 14.5 405
2×4 2.6 0.7 1 0.9 1.8 15.8 470
2×6 3.1 0.7 1 0.9 1.8 17 505
2×10 4 0.7 1 1.25 1.8 19.3 900
2×16 5 0.7 1 1.25 1.8 21.2 950
2×25 6.3 0.9 1 1.6 1.8 24 1205
2×35 7.4 0.9 1 1.6 1.8 24.8 1800
2×50 8.8 1 1 1.6 1.8 26 1850
2×70 10.6 1.1 1 2 2 29 2335
2×95 12.4 1.1 1.2 2 2.1 33.2 3165
2×120 14 1.2 1.2 2 2.3 36.1 3750
2×150 15.5 1.4 1.2 2.5 2.3 39.3 4410
2×185 17.4 1.6 1.3 2.5 2.5 44.8 5710
2×240 20.3 1.7 1.4 2.5 2.7 53.5 7150
2×300 22.5 1.8 1.5 2.5 2.9 58 8565
2×400 25.4 2 1.6 2.5 3.1 63 10695
Three Cores XLPE Insulated SWA Armoured Power Cable
3×1.5 1.6 0.7 1.2 0.9 1.8 15 380
3×2.5 2 0.7 1.2 0.9 1.8 15.5 400
3×4 2.6 0.7 1.2 0.9 1.8 16.5 460
3×6 3.1 0.7 1.2 0.9 1.8 18 540
3×10 4 0.7 1.2 0.9 1.8 19.5 750
3×16 5 0.7 1.2 1.25 1.8 22.5 1000
3×25 6.3 0.9 1.2 1.6 1.8 26 1510
3×35 7.4 0.9 1.2 1.6 1.8 28 1950
3×50 8.8 1 1.2 1.6 1.9 32 2350
3×70 10.6 1.1 1.2 2 2 35 3230
3×95 12.4 1.1 1.2 2 2.1 39 4050
3×120 14 1.2 1.2 2 2.3 43 5230
3×150 15.5 1.4 1.4 2.5 2.4 47 6750
3×185 17.4 1.6 1.4 2.5 2.6 52 8230
3×240 20.3 1.7 1.5 2.5 2.7 59 10510
3×300 22.5 1.8 1.6 2.5 2.9 64 13210
3×400 25.4 2 1.6 2.5 3.2 74 16100
3+1 Cores XLPE Insulated SWA Armoured Power Cable
3x 16/10 5 4 0.7 0.7 1 1.6 1.8 25.5 1550
3x 25/16 6.3 5 0.9 0.7 1 1.6 1.8 27.5 2010
3x 35/16 7.4 5 0.9 0.7 1 1.6 1.8 29 2375
3x 50/25 8.8 6.3 1 0.9 1 1.6 2 33 3100
3x 70/35 10.6 7.4 1.1 0.9 1.2 2 2.1 38 4290
3x 95/50 12.4 8.8 1.1 1 1.2 2 2.3 43.5 5540
3×120/70 14 10.6 1.2 1.1 1.2 2 2.4 49 7150
3×150/70 15.5 10.6 1.4 1.1 1.4 2.5 2.5 52 8330
3×185/95 17.4 12.4 1.6 1.1 1.4 2.5 2.7 57.2 10110
3×240/120 20.3 14 1.7 1.2 1.6 2.5 3 64 12740
3×300/150 22.7 15.5 1.8 1.4 1.6 2.5 3 69.8 15430
3×400/185 25.4 17.4 2 1.6 1.6 3.15 3.3 78.6 19990
4 Cores XLPE Insulated SWA Armoured Power Cable
4×1.5 1.6 0.7 1 0.9 1.8 15 415
4×2.5 2 0.7 1 0.9 1.8 17.5 490
4×4 2.6 0.7 1 0.9 1.8 19 600
4×6 3.1 0.7 1 0.9 1.8 20 730
4×10 4 0.7 1 1.25 1.8 23 970
4×16 5 0.7 1 1.6 1.8 26 1520
4×25 6.3 0.9 1 1.6 1.8 29 2010
4×35 7.4 0.9 1 1.6 1.9 31 2560
4×50 8.8 1 1 1.6 2.1 36 3350
4×70 10.6 1.1 1.2 2 2.2 40 4680
4×95 12.4 1.1 1.2 2 2.4 44 5710
4×120 14 1.2 1.4 2.5 2.5 50 7500
4×150 15.5 1.4 1.4 2.5 2.6 55 9010
4×185 17.4 1.6 1.4 2.5 2.8 61 10820
4×240 20.3 1.7 1.6 2.5 3.1 69 13630
4×300 22.7 1.8 1.6 2.5 3.2 75 16820
4×400 25.4 2 1.8 3.15 3.4 83 22230

5.Package
Packing in plastic reel, paper reel ,wooden drum,steel wooden drum or as customer’s requirement.

6.About us
People’s Cable Group Co., Ltd. was founded in 2007, located in Zhengzhou Gongyi economic development zone. Our company has 2 factories (Zhitian factory and Zhulin factory), occupies total area of more than 300,000 square meters, with building area 230,000 square meters. The real capital assets more than USD 10 million , with total 500 staff members, 65 of which are professional and technical experts.

7.Certificate:
As first rank of the cable supplier in China, we have obtained CCC, ISO9001, ISO14001, OHSAS certificates, passed the SGS and BV test, and our brand "RMJT" be given China famous brand.

8.Customer Visit
We have a professional sales team with each of them has engaged in this job for 3-10 years, so that we can provide the comprehensive and professional technology for you. With the perfect quality and after sales service, till now we have exported to more than 80 countries, welcome to visit us and establish win-win relationship!

9.Contact us
Factory ADD:No.13th,YongDing Road, Goingyi,Zhengzhou city, Henan province, China.
TEL:+86-371-55632827
FAX: +86-371-55367868
Mobile:+86-13938408065

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.