Squirrelshield, Triplex Service Drop, 4/0AWG

Squirrelshield, Triplex Service Drop, 4/0AWG

Squirrelshield, Triplex Service Drop, 4/0AWG

4/0AWG

4/0AWG

75 Centigrade

PVC, PE or XLPE

5926lbs

Yifang Cable

Wooden Drum or Wooden-Steel Drum

CE SABS RoHS SGS UL CCC

Zhengzhou, China

8544492100

Product Description

SquirrelShield, Triplex Service Drop,4/0AWG

SquirrelShield™ Triplex
Service Drop

Aluminum Conductors. Copper Neutral.
Polyethylene or Crosslinked Insulation.

APPLICATIONS
Used to supply power, usually from a pole-mounted transformer, to the user’s service head in areas where squirrels are
known to damage the bare neutral by chewing. Damage can result in complete loss of the neutral, known to cause voltage
stability problems at the service. Used at a maximum voltage of 600 volts phase-to-phase, or 480 volts to ground, and at
conductor temperatures not to exceed 75°C for polyethylene conductors (poly) or 90°C for crosslinked polyethylene (XLP)
insulated conductors.
SPECIFICATIONS
Southwire’s SquirrelShield™ Triplex service drop cable meets or exceeds the following ASTM specifications:
B-1 Hard-Drawn Copper Wire.
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium Hard, or Soft.
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-231 Aluminum Conductors, Concentric-Lay-Stranded.
B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire.
Southwire’s SquirrelShield™ Triplex service drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474
for polyethylene and cross-linked polyethylene insulated conductors and Southwire Raw Material Standard R010411 for
stranded copper. It has been tested effective against gray squirrel chewing activity on the neutral messenger in laboratory
tests at Genesis Laboratories, a licensed animal research facility registered with the USDA in compliance with the Animal
Welfare Act. It has also proven effective in field trials in the state of South Carolina.
CONSTRUCTION
Conductors are concentrically stranded, compressed 1350-H19 aluminum, insulated with either polyethylene or
XLP. Neutral messenger is a bare, hard-drawn concentrically stranded copper SCRAMessenger (Southwire Copper Rodent
Adverse Messenger).

SquirrelShield Triplex Service Drop

Aluminum Phase Conductor Copper Neutral-Messenger Diameter
(inches)
Approx.
Weight
(lb/kft)
Size
(AWG)
Strand-
ing
Insul.
Thick.
(mils)
Size
(AWG)
Strand-
ing
Rated
Strength
(lb)
Single
Phase
Cond.
Complete
Cable
4 7 45 6 7 1228 .315 .68 196
2 7 45 4 7 1938 .373 .806 299
1/0 9 60 2 7 3050 .472 1.02 474
2/0 11 60 1 7 3801 .515 1.112 588
3/0 17 60 1/0 7 4752 .563 1.216 730
4/0 18 60 2/0 7 5926 .618 1.335 909

BS6485 Alumimum Conductor PVC insulated 120 mm ABC cable
Applicat ions
To Supply 120 volt aerial service for temporary service at construction sites,outdoor or street lighting . For service at 600 volts or lower at a conductor temperature of 75 maximum.
Construction
Concentic strand or cmpressed 1350-H19 conductor , polyethylene or cross linked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy nertral messenger.
2,Specification:
0.6/1kv Low Voltage ABC Cable :
Phase Conductor:
a) Conductor: Aluminum
b) Insulation: Cross-lined Polyethylene
Messenger:
a) Conductor : Aluminum Alloy, Aluminum Conductor, Aluminum Conductor Steel Reinforced
b) Insulation: Cross-lined Polyethylene or None
Street Lighting:
a) Conductor: Aluminum
b) Insulation: Cross-lined Polyethylene or None

3.6KV,11KV ABC Cable:
a) Conductor: Hard Drawn Aluminum
b) Conductor Screen: Semi-Conductive Compound
c) Insulation: Cross-Linked Polyethylene
d) Insulation Screen: Sem-conductive Compound
e) Metallic Screen: Copper Type
f) Binder: Polyester Non- Woven Type

g) Outer Sheath: Black PVC (ST2)+ Ultra Violet Resistant

Item Phase
Conductor
Size/AWG
Phase
Conductor
Stranding
Phase
Conductor
Insulation
Thickness
Bare
Neutral
Messenger
Size/AWG
Bare
Neutral
Messenger
Stranding
Bare
Neutral
Messenger
Breaking
Strength
Weight
Per
MFT
XLP
Weight
Per
MFT
POLY
Ampacity
XLP
Ampacity
Poly
Bay 6 Solid 45 mls 6 7 1110 Lbs 145 Lbs 140.0 Lbs 75 Amps 60 Amps
French Coach 6 7/w 45 mls 6 7 1110 Lbs 155 Lbs 144.3 Lbs 75 Amps 60 Amps
German Coach 4 Solid 45 mls 4 7 1760 Lbs 214 Lbs 208.3 Lbs 100 Amps 80 Amps
Arabian 4 7/w 45 mls 4 7 1760 Lbs 229 Lbs 214.4 Lbs 100 Amps 80 Amps
Belgian 2 7/w 45 mls 2 7 2800 Lbs 344 Lbs 323.1 Lbs 135 Amps 105 Amps
Shetland 1/0 19/w 60 mls 1/0 7 4460 Lbs 546 Lbs 521.1 Lbs 180 Amps 140 Amps
Thoroughbred 2/0 19/w 60 mls 2/0 7 5390 Lbs 670 Lbs 641.5 Lbs 205 Amps 160 Amps
Trotter 3/0 19/w 60 mls 3/0 7 6790 Lbs 825 Lbs 791.8 Lbs 235 Amps 185 Amps
Walking 4/0 19/w 60 mls 4/0 7 8560 Lbs 1019 Lbs 979.7 Lbs 275 Amps 210 Amps

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.