Single Core XLPE Insulated Copper Wire Shield 11kv Aluminum Power Cable

Single Core XLPE Insulated Copper Wire Shield 11kv Aluminum Power Cable

Single Core XLPE Insulated Copper Wire Shield 11kv Aluminum Power Cable

xlpe insulated cable

Jinyuan

Yjv Vlv

ISO, CCC

Bare Copper Wire

Round Wire

PVC

XLPE

AC Cable

Low and Medium Voltage Cable

Construction, Underground, Industrial, Power Station, Telecommunication

IEC 60502

1-4

100000mm2

CCC ISO

15 Days

Power Cable

Jinyuan

Wood Drum or Steel- Wood Drum

Aluminium wire armoured

China

8544492100

Product Description

Single Core XLPE Insulated Copper Wire Shield 11kv Aluminum Power Cable

1. Object
This document defines the design and manufacturing characteristics of the cables type
RHZ1-OL 12/20 kV Al+H16 manufactured by HuaTong Cables.
2. Design
This type of cables is designed, manufactured and tested according to UNE-HD 620-10E and
IEC 60502-2.
3. Applications
Cables for fixed installations. Suitable for transport and distribution of electric power in
medium voltage networks. Halogen free. These cables are suitable for indoor, outdoor and
buried installations.
 4. Characteristics
Nominal voltage: 12/20 (24) kV
Minimum service temperature: -15 °C
Maximum conductor temperature: 90 °C
Maximum short-circuit temperature: 250 °C (maximum 5 s)
Minimum bending radius: 15 x cable Ø
Halogen free: according EN 50267 / IEC 60754
HCl content < 0,5 %
pH > 4,3
conductivity < 10 μS/mm
5. General make-up of the cable
5.1 Conductor
Electrolytic annealed aluminium conductor, class 2 according to EN 60228 / IEC 60228.
Optionally, hygroscopic tapes can be applied in order to achieve longitudinal watertightness
on the conductor (cable type -2OL)
5.2 Inner semi-conducting screen
Cross-linked semiconductor screen applied over conductor in a triple-extrussion process.
5.3 Insulation
Cross-linked polyethylene insulation, type DIX-3 according to HD 620-1 and type XLPE
according to IEC 60502-2; natural color. Cross-linked in catenary line with nitrogen
atmosphere.
5.4 Outer semi-conducting screen
Cross-linked semiconductor screen applied over insulation in a triple-extrussion process.
Strippable.
Optionally, under customer request, it can supplied non strippable (bonded to insulation).
5.5 Metalic screen
Metalic screen made with Cu wires and Cu binder tape, applied over the outer semiconducting
layer. 
5.6 Water blocking
Hygroscopic tape applied over metalic screen.
5.7 Outer sheath
Polyolefine outer sheath, type DMZ1 according to HD 620-1 and type ST7 according to IEC
60502-2; red color.

6 Data sheet:

Cross-section Screen Conductor Insulation Outer  Weight
mm2 mm2 mm mm mm KG/KM
1×50 16 8 20.2 27.9 770
1×70  16 10.1 22.3 30.4 905
1×95 16 11.3 23.5 31.5 1000
1×120 16 12.7 24.9 33.6 1140
1×150 16 14.2 26.4 35.1 1260
1×185 16 16 28.2 36.9 1405
1×240 16 18 30.2 39.4 1635
1×300 16 21 33.2 42.4 1865
1×400 16 23.4 36.4 45.6 2225
1×500 16 27 40.4 49.2 2585
1×630 16 31.5 44.5 53.7 3130
1×800 16 34 47 57.2 3775
1×1000 16 39 51.7 60.5 4450

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.