Product Description

RHH/RHW-2, Wire, 600 V, Cu/XLP (UL 44)

Underground Service Entrance Cable ? 600 Volts ? Oxygen Free Copper Conductor ? Dead Soft Annealed Cross-Linked Polyethylene (XLP) Insulation High-Heat and Moisture Resistant Sizes 6 through 4/0 AWG Also Rated SIS

Applications

? Pro-Line Type RHH or RHW-2 conductors are used with conduit as specified in the National Electrical Code1
? When used as RHH, conductor temperatures shall not exceed 90°C in dry locations
? When used as RHW-2 , conductor temperatures shall not exceed 90°C in wet or dry locations
? Voltage rating for RHH or RHW-2 conductors is 600 volts

Standards and References

Pro-Line Type RHH or RHW-2 meets or exceeds UL Standard 44 (for RHH or RHW-2).

Construction

? Pro-Line Type RHH or RHW-2 copper conductors are annealed (soft copper).
? Insulation is an abrasion, moisture, heat, and sunlight resistant black cross-linkedpolyethylene (XLP).

Specifications

PROLINESAFETY.COM / 800.554.3424
? Pro-Line Type RHH or RHW-2 or USE-2 conductors are used with conduit as specified in the National Electrical Code1
? When used as Type USE-2, conductor is suitable for use as underground service entrance cable for direct burial at conductor temperatures not to exceed 90°C
? When used as RHH, conductor temperatures shall not exceed 90°C in dry locations
? When used as RHW-2 or USE-2, conductor temperatures shall not exceed 90°C in wet or dry locations
? Voltage rating for RHH or RHW-2 or USE-2 conductors is 600 volts
RHH RHW-2 USE-2 COPPER BUILDING WIRE
Underground Service Entrance Cable ? 600 Volts ? Oxygen Free Copper Conductor ? Dead Soft Annealed
Cross-Linked Polyethylene (XLP) Insulation High-Heat and Moisture Resistant
Sizes 6 through 4/0 AWG Also Rated SIS
RHH RHW-2 USE- 2
1 of 2
Applications
Pro-Line Type RHH or RHW-2 or USE-2 meets or exceeds UL Standard 44 (for RHH or RHW-2), UL Standard 854 (for USE-2), Federal Specification A-A-59544, and requirements of the National Electrical Code.
Standards and References
? Pro-Line Type RHH or RHW-2 or USE-2 copper conductors are annealed (soft copper.
? Insulation is an abrasion, moisture, heat, and sunlight resistant black cross-linkedpolyethylene (XLP).
Construction
Conductors shall be UL-listed Type RHH or RHW-2, suitable for operation at 600 volts or less in wet or dry locations, including direct burial in the earth. Conductors shall be annealed copper, cross-linked polyethylene (XLP) insulated. Type RHH or RHW-2 shall be PRO-LINE WIRE & CABLE or approved equal.

CONDUCTOR SIZE NUMBER OF STRANDS INSULATION THICKNESS NOMINAL O.D. ALLOWABLE AMPACITIES APPROX. NET WEIGHT PER 1000 FT.
(AWG or kcmil) (mils) (mils) 60°C 75°C 90°C (lbs)
14 7 45 160 15 15 15 21
12 7 45 177 20 20 20 30
10 7 45 201 30 30 30 44
8 7 60 262 40 50 55 72
6 7 60 297 55 65 75 106
4 7 60 344 70 85 95 156
2 7 60 400 95 115 130 238
1 19 80 484 110 130 150 309
1/0 19 80 523 125 150 170 381
2/0 19 80 567 145 175 195 472
3/0 19 80 617 165 200 225 586
4/0 19 80 673 195 230 260 729
250 37 95 751 215 255 290 867
300 37 95 804 240 285 320 1029
350 37 95 854 260 310 350 1191
400 37 95 899 280 335 380 1352
500 37 95 983 320 380 430 1674
600 61 110 1089 355 420 475 2012
750 61 110 1191 400 475 535 2492
1000 61 110 1340 455 545 615 3288