PV1-F Solar Photovoltaic Tinned Copper Cable

PV1-F Solar Photovoltaic Tinned Copper Cable

PV1-F Solar Photovoltaic Tinned Copper Cable

PV1-F

Jinyuan

ISO9001, CCC

LSOH

Round Wire

Electron Beam Cross-Linked, Halogen Free and Flame

Electron Beam Cross-Linked, Halogen Free and Flame

Stranded Tinned Copper Conductor

Heating, Photovoltaic System

Stranded

Insulated

DC

Jinyuan

Roll Reel or Drum

0.75-240mm2

China

8544422100

Product Description

Product Description

Tinned Copper PV1-F UV #4 6AWG Solar Panel PV Cable

Applications

These cables are designed for connecting photovoltaic system components inside and outside of buildings and equipment with high mechanical requirements and extreme weather conditions.

Standards

DIN EN 50618 (H1Z2Z2-K)
2Pfg 1169 PV1-F
 

Construction

Conductor Stranded copper conductor per DIN VDE 0295 and IEC 60228 Class 5.
Insulation Electron beam cross-linked, halogen free and flame retardant compound.
Sheath Electron beam cross-linked, LSZH and flame retardant compound, Black.

Electrical Properties

Rated Voltage U0/U 1/1 kV AC; 1.5/1.5 kV DC
Maximum Permitted DC Voltage 1.8 kV DC (conductor/conductor, non earthed system, circuit not under load)
Insulation Resistance 1000 MΩ-km
Spark Test 6000 Vac (8400 Vdc)
Voltage Withstand 6500 Vac for 5 minElectron

Thermal Properties

Maximum Voltage 1.2KV (AC), 1.8KV (DC)
Ambient Temperature -40ºC ~ +90ºC
Maximum Temperature At Conductor 120ºC (20000h) according to IEC/EN 60216-1
Short Circuit Temperature 200ºC/5 sec
Thermal Endurance Test According to EN 60216-2 (temperature index +120° C)
Damp-Heat Resistance According to EN 50618, Table 2with 85% humidity(test acc. to EN 60068-2-78)

Mechanical Properties

Minimum Bending Radius 4×OD (fixed), 5×OD (flexing)
Dynamic Penetration According to Acc. to EN 50618, Annex D,Meets requirements of EN 50618.
Tensile Strength And Elongation Of Insulation And Jacket 250ºC
Anticipated Period Of Use 25 years
Ovality ≤15%

Chemical Properties

Ozone Resistance According to EN 60811-403(25ºC,24h,(250 to 300) × 10-4%) ;Method B: EN 50396(40ºC,72h,55%RH, (200 × 10-6%)
Weathering- UV Resistance (Resistance on sheath) Tensile strength and elongation at break after 720h (360 Cycles) of exposure to UV lights (acc. to EN 50289-4-17, Method A According to HD 605/A1)
Ammoniac resistant
Very good resistance to oils and chemicals
High wear and robust, abrasion resistant

Dimensions and Weight

No. of Cores × Nominal Cross Section No. of Stranding Nominal Conductor Diameter Nominal Insulation Thickness Nominal Sheath Thickness Nominal Overall Diamater Nominal Weight
No. ×mm^2   mm mm mm mm kg/km
1×1.5 30/0.25 1.58 0.70 0.80 5.4 40
1×2.5 50/0.25 2.04 0.70 0.80 5.9 50
1×4.0 56/0.30 2.59 0.70 0.80 6.6 70
1×6.0 84/0.30 3.17 0.70 0.80 7.4 80
1×10 78/0.40 4.07 0.70 0.80 8.8 130
1×16 128/0.40 5.22 0.70 0.90 10.1 200
1×25 199/0.40 6.51 0.90 1.00 12.5 290
1×35 279/0.40 7.71 0.90 1.10 14.0 400
1×50 396/0.40 9.00 1.00 1.20 16.3 550
1×70 360/0.50 10.8 1.10 1.20 18.7 750
1×95 475/0.50 12.6 1.10 1.30 20.8 970
1×120 608/0.50 14.2 1.20 1.30 22.8 1220
1×150 756/0.50 15.8 1.40 1.40 25.5 1510
1×185 925/0.50 17.4 1.60 1.60 28.5 1850
1×240 1221/0.50 20.4 1.70 1.70 32.1 2400

Other specification can produce depending on customer require.

Why Choose Us ?
1. We have a large production base, and advanced production equipment 
2. Have an competitive price and high quality
3. Excellent after-sale service
4. Free issue:packaging list,invoice
5. Powerful technology team
6. Strict quality assurance system and perfect testing means
7. Advanced process equipment
8. Delivery on time
9. Our cable sales to Middle East,Africa,Russia,Southeast Asia, etc.
10.We have a good reputation in the overseas
FAQ
Q: Are you trading company or manufacturer ?
A: We are factory.

Q: How long is your delivery time?
A: Generally it is 5-10 days if the goods are in stock. or it is 10-20 days if the goods are not in stock,
it is according to quantity.

Q: Do you provide samples ? is it free or extra ?
A: Yes, we could offer the sample for free charge but do not pay the cost of freight.

Q: What is your terms of payment ?
A: 30% T/T in advance,70% T/T balance before shipment

*In order to quote you accurate price, kindly tell us your needed cable length quantity. Larger quantity, more discount benefit ready for you!
Any needs or question, please contact me Mobile:+86-156 0374 9203   we will be more pleasure to service you.
We are looking forward to your inquiry and nice cooperation.

Tags: ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.

Similar Or Related