Primary Ud Cable, 5 Kv, Al/Tr-XLPE/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)

Primary Ud Cable, 5 Kv, Al/Tr-XLPE/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)

Primary Ud Cable, 5 Kv, Al/Tr-XLPE/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)

Primary UD Cable

Underground

Low and Medium Voltage Cable

DC Cable

XLPE

LLDPE

Round Wire

Aluminum 1350 Wire

ISO, CCC

Primary Ud Cable

Boan

5 Kv

2-1000 AWG or Kcmil

100%

1/3 or Full

Copper Wire

14/12/10/9 AWG

DingAn or OEM

Heated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544601200

Product Description

Primary UD Cable, 5 KV, Al/TR-XLPE/Neutral/LLDPE (AEIC CS 8/ICEA S-94-649)
Applications:
Predominantly used for primary underground distribution; Suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 15, 000 volts or less and at conductor temperatures not to exceed 90° C for normal operation.
Specifications:
Primary UD Cable meets or exceeds the following ASTM specifications:
B-3 Soft Annealed Copper Wire.
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.
B-230 Aluminum, 1350-H19 Wire for Electrical Purposes.
B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded.
B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
Primary UD Cable is manufactured to the latest edition of the following specifications, and in case of specification conflicts, in the order listed:
ANSI/ICEA S-94-649
AEIC CS-8
RUS U-1
Construction:
The phase conductor is concentrically stranded, compressed soft copper or 1350-H16/26 aluminum alloy. The cable is composed of the conductor with moisture block in the strands, covered by a semi-conducting cross-linked polyethylene strand shield, an ethylene propylene rubber primary insulation, and a semi-conducting cross-linked polyethylene insulation shield. Conductors are available with either 100% or 133% insulation levels. A concentric neutral of bare copper wires and an insulating polyethylene jacket is applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. A semi-conducting polyethylene jacket is available upon request.
Maximum Conductor Normal Operation: – 90O C;
Emergency Overload: – 130O C
Temperatures: Short Circuit – 250 C
Application: Medium voltage power cable for single phase underground distribution (UD), including getaway systems in low profile substations. Application:

Features: 1. Simultaneous extrusion of strand shield, insulation, and insulation shield (triple extrusion, dry curing process) forms a virtually perfect cable core, eliminating unequal electrical stress.
2. Ethylene Propylene Rubber (EPR) insulation offers: Excellent heat, moisture and corona resistance; Electrical stability under stress; Low dielectric loss, chemical resistance.

Size AWG or kcmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
Aluminum 100% Insulation Level (90 mil)
2 1 0.48 6 14 50 0.78 311 10 14 50 0.78 360
2 7 0.50 6 14 50 0.81 325 10 14 50 0.81 374
1 19 0.54 6 14 50 0.84 355 13 14 50 0.84 439
1/0 1 0.54 6 14 50 0.85 370 16 14 50 0.85 491
1/0 19 0.58 6 14 50 0.88 389 16 14 50 0.88 510
2/0 19 0.62 7 14 50 0.93 444 13 12 50 0.96 629
3/0 19 0.67 9 14 50 0.98 519 16 12 50 1.01 738
4/0 19 0.73 11 14 50 1.03 606 13 10 50 1.11 921
250 37 0.79 13 14 50 1.09 686 16 10 50 1.17 1071
350 37 0.89 18 14 50 1.19 879 16 9 50 1.29 1356
500 37 1.02 16 12 50 1.38 1208 29 10 50 1.42 1823
750 61 1.22 15 10 80 1.69 1798
1000 61 1.37 16 9 80 1.86 2292