Overhead Line ABC Cable 3*70+54.6mm2

Overhead Line ABC Cable 3*70+54.6mm2

Overhead Line ABC Cable 3*70+54.6mm2

JKLYJ

3X50 + 54.6 + 1X25

90centigrade

XLPE

150

1.4

0.641

Yifang Cable

Wooden Drum or Wooden-Steel Drum

CE SABS RoHS SGS UL CCC

Zhengzhou, China

8544492100

Product Description

Description
Cables for use on urban and rural overhead distribution systems. Cables consist of phase conductors twisted around the neutral messenger made of aluminium alloy Almelec. One or more street lighting conductors may be added to the bundle. Insulation on all conductors. CROSS LINKED POLYETHYLENE (XLPE).
BUNDLE MAIN CHARACTERISTICS TO SABS 1418 – 1986

Bundle Size mm²

Phase Neutral Lighting

Bundle Phase
Conductor
Approx. Ø

Mm

Neutral
Conductor
Approx. Ø

Mm

Lighting
Conductor
Approx. Ø

Mm

Max
Current
Rating
Air at
30°C
3 volt
Drop
PF=1.0
At 30°C
V/A/km
Max Liner
Resistance
Per phase
Conductor
At 30°C-km
Approx
OverallØ
Mm
Approx
Weight
Kg/m
3X25 + 54.6 + 1X25 29 0.70 9 12.4 9 98 2.62 1.200
3X35 + 54.6 + 1X25 31 0.82 10.2 12.4 9 120 1.89 0.868
3X50 + 54.6 + 1X25 33 0.95 11.6 12.4 9 150 1.40 0.641
3X70 + 54.6 + 1X25 37 1.25 13.7 12.4 9 200 0.97 0.443
3X95 + 54.6 + 1X25 41 1.45 15.2 12.4 9 240 0.71 0.320
3X120 + 70 + 1X25 45 1.70 16.5 13.5 9 280 0.57 0.253
3X35 + 35BN 23 0.47 9.65 7.05 N/A 130 1.08 0.868
3X70 + 50BN 30 0.84 11.05 8.05 N/A 205 0.55 0.443
Cable
Description
Size (mm²) Current Rating
(AMP)
Weight
(kg/m)
2X25 25 98 0.23
4X25 25 92 0.46
2X16AI 16 80 0.15
4X16AI 16 74 0.30
4 Airdac 4-Phase & Neutral,
2.5 Earth
50 0.16
6 Airdac 6-Phase & Neutral,
4 Earth
65 0.22
10 Airdac 10-Phase & Neutral,
7.5 Earth
90 0.32
16 Airdac 16-Phase & Neutral,
10 Earth
125 0.49
4 Airdac II 4 50 0.12
10 Airdac II 10 86 0.25
16 Airdac II 16 125 0.41

We can also supply following:
———————————————————————————————-
Duplex Service Drop
AAC-Aluminum Conductor
Applications
To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75 °C maximum.

Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or cross linked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.

Standards
1. B230 aluminum wire, 1350-H19 for electrical purposes
2. B231 aluminum conductors, concentric-lay stranded
3. B232 aluminum conductors, concentric-lay-stranded, coated steel reinforced(ACSR)
4. B399 concentric-lay stranded 6201-T81 aluminum alloy conductors
5. B499 zinc-coated steel core wire for aluminum conductors, steel reinforced(ACSR)
6. Duplex service drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474

Item Phase Condutor
Size AWG
Phase Conductor
Strading
Phase Conductor
Insulatin Thickness
Bare Neutral Messenger
Size AWG
Bare Neutrl
Stranding
Pekingese 6 Solid 45mls 6 7/w
Collie 6 7/w 45mls 6 7/w
Dachshund 4 Solid 45mls 4 7/w
Spaniel 4 7/w 45mls 4 7/w
Doberman 2 7/w 45mls 2 7/w
Malemute 1/0 19/w 60mls 1/0 7/w

Tags: , ,