Product Description

1. Application
Product Description
ABC Cable; Service Drop Cable

The basic construction is as follows:
3 power cores consisting of standard aluminium conductors, insulated withXLPE insulation
+ One sheath lighting aluminium conductor with XLPE insulation(optional)
+ One messenger Al-alloy conductor (bare or covered)

The messenger conductor can be of galvanised steel wire also.
The purpose of messenger wire is
A) It acts as load bearing wire.
B) It acts as earth or neutral conductor.

To be used at cotages of 600V phase-to-phase or less and at conductor temperatures not to exceed 75oC for polyethylene insulated conductors or 90oC for crossliked polyethylene(XLPE) insulated conductors.

It meets or exceeds the following specifications:
1. Aluminum Wire, 1350-H19 for Electrical Purposes.
2. Aluminum Conductors, Concentric-Lay-Stranded.
3. Aluminum Conductor, Concentric-Lay-Stranded, Coated Steel Reinforced(ACSR)
4. Concentric-Lay-Stranded 6201-T81 Conductors
5. Compressed Round Stranded Aluminum Conductors Using Single Input Wire.

It meets or exceeds all applicable requirements of ANSI/ICEA S-76-474

Applications:
To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75C maximum.

Construction:
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.

Standards:
1. B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
2. B-231 Aluminum Conductors, Concentric-Lay-Stranded.
3. B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
4. B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors.
5. B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
6. Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474
0.6/1KV AAC/AAAC/ACSR XLPE/PE Insulation ABC cable AAAC conductor has been widely used in power transmission lines and electricity distribution lines with various voltage levels, because they have such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
2. Standard
We can produce as per the standard of GB, IEC, ASTM,DIN,CSA,JIS and also particularly customize and manufacture according to your special requirement.
Standards / Testing Specifications
IEC 61089, BS 3242, DIN 48201, ASTM B399, BS EN50183, GB/T 1179-2008
Working conditions aerial insulation power cable
1) Rated voltage: 0.6kV/1Kv
2) The tallest working temperature of the cable conductor; XLPE insulation cable: 90°C;
HDPE insulation cable: 75°C;
3) During having a short (lasting less than 5 seconds) the maximum temperature;
XLPE insulated cables is 250°C;
HDPE insulated cable is 150°C
4) During the cable lying, the ambient temperature must be above-20°C
5) Bending radius allowance of the cable;
A)1Kv aerial insulation power cable:
It should be no less than 4D for the cable with outer diameter less than 25mm;
It should be no less than 6D for the cable with outer diameter of 25mm or more;
B) 10kV aerial insulation power cable:
Single core cable: 20 (D+d)±5%mm;
Multi-core cable:15 (D+d)±%mm
Formula inside: D-Actual cable outer diameter;
d-Actual conductor outer diameterl
Standard Packaging
As provided by standards and customer’s requirement.
 

BS7884-1997
Nominal Area Stranding Diameter of conductor Linear mass Rated strength D.C. resistance at 20°C
mm2 No./mm mm Kg/km KN Ω/km
10 7/1.35 4.05 89.82 3.752 1.829
14 7/1.6 4.8 126.2 5.627 1.30300
16 3/2.65 5.72 148.30 6.194 1.10600
16 7/1.7 5.10 142.40 5.946 1.15400
25 7/2.1 6.30 217.30 9.073 0.75630
32 3/3.75 8.10 296.90 12.4 0.55200
32 7/2.46 7.38 298.20 12.442 0.54970
35 7/2.5 7.50 308.00 12.86 0.53370
50 7/3.00 9.00 443.50 18.52 0.37060
50 19/1.8 9.00 435.80 17.7 0.38190
70 7/3.55 10.65 621.10 25.93 0.26460
70 19/2.1 10.50 593.20 24.09 0.28060
95 19/2.5 12.50 840.70 34.14 0.19800
100.0 7/4.3 12.90 911.20 36.54 0.18100
120.0 19/2.8 14.00 1055.00 42.83 0.15780
125.0 19/2.9 14.50 1131.00 45.94 0.14710
150.0 19/3.2 16.00 1377.00 55.94 0.12080
150.0 37/2.25 15375.00 1334.00 53.88 0.12640
185.0 19/3.55 17.75 1695.00 68.86 0.09815
185.0 37/2.5 17.75 1647.00 66.49 0.10240
Phase Phase Phase Approx.Overall Diameter Max. D.C. Resistance of Conductor at 20 Centigrade
AAC+UV-XLPE Compact Conductor UV-XLPE Insulation
No.X Normal Cross Section of Cores No.of Al Wires Overall Diameter Normal Thickness Min. Diameter
No. X mm 2 mm mm mm mm mm ohm/km
1 X 10 7 4.05 1.0 0.8 6.05 6.05 3.08
1 X 16 7 4.8 1.2 0.98 7.2 7.20 1.91
1 X 25 7 6 1.2 0.98 8.4 8.40 1.20
1 X 35 7 7.0 1.4 1.16 9.8 9.80 0.868
1 X 50 7 8.3 1.4 1.16 11.1 11.10 0.641
1 X 70 19 9.8 1.4 1.16 12.6 12.60 0.443
1 X 95 19 11.6 1.6 1.34 14.8 14.80 0.320
1 X 120 19 13 1.6 1.34 16.2 16.20 0.253
1 X 150 19 14.6 1.8 1.52 18.2 18.20 0.206
1 X 185 36 16.2 2.0 1.70 20.2 20.20 0.164
1 X 240 36 18.4 2.2 1.88 22.8 22.80 0.125
2 X 10 7 4.05 1.0 0.8 6.05 12.10 3.08
2 X 16 7 4.8 1.2 0.98 7.2 14.40 1.91
2 X 25 7 6 1.2 0.98 8.4 16.80 1.20
2 X 35 7 7.0 1.4 1.16 9.8 19.60 0.868
2 X 50 7 8.3 1.4 1.16 11.1 22.20 0.641
2 X 70 19 9.8 1.4 1.16 12.6 25.20 0.443
2 X 95 19 11.6 1.6 1.34 14.8 29.60 0.320
2 X 120 19 13 1.6 1.34 16.2 32.40 0.253
2 X 150 19 14.6 1.8 1.52 18.2 36.40 0.206
2 X 185 36 16.2 2.0 1.70 20.2 40.40 0.164
2 X 240 36 18.4 2.2 1.88 22.8 45.60 0.125
3 X 10 7 4.05 1.0 0.8 6.05 13.07 3.08
3 X 16 7 4.8 1.2 0.98 7.2 15.55 1.91
3 X 25 7 6 1.2 0.98 8.4 18.14 1.20
3 X 35 7 7.0 1.4 1.16 9.8 21.17 0.868
3 X 50 7 8.3 1.4 1.16 11.1 23.98 0.641
3 X 70 19 9.8 1.4 1.16 12.6 27.22 0.443
3 X 95 19 11.6 1.6 1.34 14.8 31.97 0.320
3 X 120 19 13 1.6 1.34 16.2 34.99 0.253
3 X 150 19 14.6 1.8 1.52 18.2 39.31 0.206
3 X 185 36 16.2 2.0 1.70 20.2 43.63 0.164
3 X 240 36 18.4 2.2 1.88 22.8 49.25 0.125
4 X 10 7 4.05 1.0 0.8 6.05 14.64 3.08
4 X 16 7 4.8 1.2 0.98 7.2 17.42 1.91
4 X 25 7 6 1.2 0.98 8.4 20.33 1.20
4 X 35 7 7.0 1.4 1.16 9.8 23.72 0.868
4 X 50 7 8.3 1.4 1.16 11.1 26.86 0.641
4 X 70 19 9.8 1.4 1.16 12.6 30.49 0.443
4 X 95 19 11.6 1.6 1.34 14.8 35.82 0.320
4 X 120 19 13 1.6 1.34 16.2 39.20 0.253
4 X 150 19 14.6 1.8 1.52 18.2 44.04 0.206
4 X 185 36 16.2 2.0 1.70 20.2 48.88 0.164
4 X 240 36 18.4 2.2 1.88 22.8 55.18 0.125