Nhmh, Electric Wire, 300/500 V, Cu/Hf/Hffr/Hffr (DIN VDE 0250-215)

Nhmh, Electric Wire, 300/500 V, Cu/Hf/Hffr/Hffr (DIN VDE 0250-215)

Nhmh, Electric Wire, 300/500 V, Cu/Hf/Hffr/Hffr (DIN VDE 0250-215)

NHMH

Insulated

Stranded

Installation

Copper

Hffr

Hf

Round Wire

Installation

ISO9001, CCC

Boan

300/500 V

1/2

1.5-25 mm2

1-7

DingAn

Rolls

SGS

Jiangsu Yixing, China

8544492100

Product Description

NHMH, Electric Wire, 300/500 V, CU/HF/HFFR/HFFR (DIN VDE 0250-215)
APPLICATION:
These halogen-free cables are used as lectric installation and lighting cables in dry, moist and wet rooms, for permanent installation above, on, in and under beneath plaster and also for outdoor applications where lots of human life and material assets are to be protected in industrial constructions, schools, hospitals, shopping and cultural centers,energy plants, airports, metros . In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire.

CABLE DESIGN
Conductor : Cu wires,plain, solid-core, multi-stranded
IEC 60228 Cls. 1/2, TS/DIN EN 60228 Cls. 1/2
Insulation : Halogen-free thermoplastic polymer compound
Core identification : According to TS HD 308 S2 & VDE 0293-308;
Lay-up : Cores laid up in layers of optimum pitch
Filler : HFFR filler compound
Outer sheath : HFFR compound, HM5
Sheath colour : RAL 7001,Grey
HFFR: Halogen-free flame retardant

TECHNICAL DATA
Standard : DIN VDE 0250-215
Temp. at conductor : 70 oC
Rated voltage Uo/U : 300 / 500V
Test voltage (AC 50 Hz) : 2000 V
Temperature range : Fixed : – 30 oC ~ + 70 oC
Mobile : – 5 oC ~ + 50 oC
Min. bending radius : Sngle-core: 15 x D
Multi-core : 12 x D
Flame retardance test : IEC 60332-1 & TS/DIN EN 50265-2-1
Smoke density test : IEC 61034-2 & TS/DIN EN 61034-2
Halogen-free properties test : IEC60754-1/2 & TS/DIN EN 50267-2

cross-section Nominal insulation thickness Nominal sheath thickness Outer cable diameter DC resistance at 20°C Current carrying capacity in the plaster Current carrying capacity in duct Rated short-circuit current – conductor (1s) Cable weight
n x mm2 mm mm mm /km A A kA kg/km
1 x 1,5 0,5 1,2 5,3 12,1 17,5 15,5 0,172 36
1 x 2,5 0,5 1,2 5,4 7,41 24,0 21,0 0,287 45
1 x 4 0,6 1,2 6,2 4,61 32,0 28,0 0,460 63
1 x 6 0,6 1,2 7,0 3,08 41,0 36,0 0,690 81
1 x 10 0,7 1,2 7,6 1,83 57,0 50,0 1,15 125
1 x 16 0,7 1,2 9,2 1,15 76,0 68,0 1,84 190
2 x 1.,5 0,4 1,2 7,9 14,5 19,5 16,5 0,172 90
2 x 2,5 0,4 1,2 8,7 8,87 27,0 23,0 0,287 117
2 x 4 0,4 1,2 9,6 5,52 36,0 30,0 0,460 166
2 x 6 0,4 1,2 10,9 3,69 46,0 38,0 0,690 215
2 x 10 0,6 1,4 13,2 2,19 63,0 52,0 1,15 340
3 x 1.,5 0,5 1,2 8,6 14,5 19,5 16,5 0,172 105
3 x 2,5 0,5 1,2 9,2 8,87 27,0 23,0 0,287 140
3 x 4 0,6 1,2 10,8 5,52 36,0 30,0 0,460 200
3 x 6 0,7 1,4 12,4 3,69 46,0 38,0 0,690 280
3 x 10 0,7 1,4 14,4 2,19 63,0 52,0 1,15 425
4 x 2,5 0,5 1,2 10,0 8,87 24,0 21,0 0,287 170
4 x 4 0,6 1,4 12,0 5,52 32,0 28,0 0,460 255
4 x 6 0,6 1,4 13,2 3,69 41,0 36,0 0,690 340
4 x 10 0,7 1,4 16,0 2,19 57,0 50,0 1,15 530
4 x 16 0,7 1,4 20,0 1,38 76,0 68,0 1,84 860
4 x 25 0,9 1,6 25,0 0,870 96,0 80,0 2,88 1350
4 x 35 0,9 1,6 26,2 0,627 119,0 99,0 4,02 1720
5 x 1,5 0,5 1,2 10,0 14,5 17,5 15,5 0,172 145
5 x 2,5 0,5 1,2 10,8 8,87 24,0 21,0 0,287 200
5 x 4 0,6 1,4 13,2 5,52 32,0 28,0 0,460 300
5 x 6 0,6 1,4 14,5 3,69 41,0 36,0 0,690 405
5 x 10 0,7 1,4 17,4 2,19 57,0 50,0 1,15 630
5 x 16 0,7 1,6 22,3 1,38 76,0 68,0 1,84 1040
5 x 25 0,9 1,6 27,0 0,870 96,0 80,0 2,88 1620
7 x 1,5 0,5 1,2 10,5 14,5 17,5 15,5 0,172 180
7 x 2,5 0,5 1,4 11,8 8,87 24,0 21,0 0,287 225