Nayy Cable Nyy XLPE Insulated Sta Armored PVC Sheathed Power Cable N2xy

Nayy Cable Nyy XLPE Insulated Sta Armored PVC Sheathed Power Cable N2xy

Nayy Cable Nyy XLPE Insulated Sta Armored PVC Sheathed Power Cable N2xy

3*240mm2

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

XLPE

PE or PVC

Round Wire

Copper

ISO

Nyy,Nayy,N2xy,Nhxmh

Jytop

ASTM, AS/NZS, BS, CSA, DIN, IEC…

Ce, ISO 9001

300/500V

Nyy-J Cable

Nayy

4 Cores

JYTOP

Packed in Reels

as per popular standards or clients's requirement

Zhengzhou, China

8544601200

Product Description

Nayy Cable Nyy XLPE Insulated STA Armored PVC Sheathed Power cable N2XY cable

Voltage: 0.6/1KV,1.8/3KV, 3.6/6KV ,35kV and below.
Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.

Product Named:
1. The meaning of cable model in letter and number:
T………………………………Copper conductor
L………………………………Aluminum conductor
YJ…………………………….XLPE
V………………………………PVC
Y………………………………PE

Armor code:
2………………………………Double steel tape armor
3………………………………Thin steel wire armor
4………………………………Thick steel wire armor
6………………………………(Double)non-magnetic mental tape armor
7………………………………Non-magnetic wire armor

Oversheath code:
2………………………………PVC oversheath
3………………………………PE oversheath
4………………………………Elastomer oversheath

Using Festures of Power Cable:
1.Rated Voltage 0.6/1kV PVC Insulation Power Cable :
The long-term working temperature of cable conductor should be not more than 70°C.
While short-circuit the highest working temperature of cable conductor should be not more than 160°C(5 seconds maximum duration);
The minimum bending radius for laying cable(D is diameter):single core unarmoured cable shoule be 20D,multi-core unarmoured cable shoule be 15D,single core armoured cable shoule be 15D,multi-core armoured cable should be 12D;
The environment temperature for laying cable should be not less than 0°C.

2. Rated Voltage 0.6/1kV XLPE Insulation Power Cable / Rated Voltage 3.6/6~26/35kV XLPE Insulation Power Cable :
The long-term working temperature of cable conductor should be not more than 90°C.
While short-circuit the highest working temperature of cable conductor should be not more than 250°C(5 seconds maximum duration);

3. Rated Voltage 0.6/1kV and Freqency Inverter Control System Power Cable :
Designed with fully symmetric space structure,cable has excellent electromagnetic compatibility;
Low and uniform positive sequence and zero-sequence impedances have greatly improved power quality compared with ordinary four-core cable;
The environment temperature for laying cable;PVC and XLPE insulation is 0°C;
The maximum working temperature of cable;PVC insulation is 70°C,XLPE insulation is 90°C;
Low-smoke halogen-free flame retardant cable:PH value of burning gas ≥4.3,conductivity≤10us/mm,minimum light transmittance shall not be less than 60% while product burning;
The minimum bending radius for laying cable is 12D(D is diameter).

4. Copper Clad Aluminum Power Cable
Maximum temperature of cable of cable conductors during normal operation and short-circuit (5 seconds maximum duration): PVC insulation is 70oC, the highest temperature should be not more than 160oC while short circuit; XLPE insulation is 90oC,the highest temperature should be not more than 250oC while short circuit;
The minimum bending radius for laying cable (D is diameter):single core unarmoured is 20D,three-core unarmoured is 15D, single core armoured is 15D,three-core armoured is 12D;
The environmental remperature for laying cable should not less than 0oC


Product description
Rated Voltage 0.6/1kV XLPE Insulation Power Cable

Type Description Application
Cu Al
YJV YJLV Copper-core(aluminum core)XLPE insulation and PVC sheath power cable For laying indoor,in tunnels and in ducts,unable to bear external mechanical forces
YJY YJLY Copper-core(aluminum core)XLPE insulation and PE sheath power cable
YJV22 YJLV22 Copper-core(aluminum core)XLPE insulation steel tape armoured PVC sheath power cable For laying indoor,in tunnels and in ducts,can able to bear external mechanical forces
YJV23 YJLV23 Copper-core(aluminum core)XLPE insulation steel tape armoured PE sheath power cable
YJV32 YJLV32 Copper-core(aluminum core)XLPE insulation steel wire armoured PVC sheath power cable For laying in water or ground along route with large difference of level,can able to bear external mechanical forces
YJV33 YJLV33 Copper-core(aluminum core)XLPE insulation steel wire armoured PE sheath power cable
YJV42 YJLV42 Copper-core(aluminum core)XLPE insulation thick wire armoured PVC sheath power cable
YJV43 YJLV43 Copper-core(aluminum core)XLPE insulation thick wire armoured PE sheath power cable

Notes:1.Ratproof,termite-proof,moisture-proof and other special requiremments cables are available.
2.The single core armoured cable are used for DC system only.As for AC system,non-megnetical materials shoule be used,its corresponding code is 62,63,72,73;
3.It is not recommended AL-core fire retardent cable.When there is a fire,flame temperatures may reach 700°C above due to the meilting point of aluminium is only 660°C,the conductor may be fused;
4.Flame retaradant/fire resistant power cable are available:Representation method of flame retardant grade is the "Z" followed by"A","B","C",such as the "ZA","ZB","ZC".When "ZR" expressed,generally considered to be "C" class of flame retardant.Flame retardant level representation is "ZN" middle "A","B","C",such as the "ZA","ZB","ZC".While using "NH" expressed,it generally considered to be "ZCN".For example;

Notes:1.Flexible power cable is available.Plus "R" after sheath material types.For example,"VVR" refers to cooper core PVC insulation PVC sheath flexible power cable;
2.Hear-resistant 90°C and 105°C power cable are available,Plus "-90" "-105" after the type.For example,VV-105 refers to copper core heat-resistant 105°C PVC insulation and sheath power cable,and the highest temperature of cable conductor is 105°C.
3.Ratproof,termite-proof,moisture-proof and other special requiremments cables are available.
4.The single core armoured cable are used for DC system only.As for AC system,non-megnetical materials shoule be used,its corresponding code is 62,63,72,73;
5.It is not recommended AL-core fire retardent cable.When there is a fire,flame temperatures may reach 700°C above due to the meilting point of aluminium is only 660°C,the conductor may be fused;
6.Flame retaradant/fire resistant power cable are available:Representation method of flame retardant grade is the "Z" followed by"A","B","C",such as the "ZA","ZB","ZC".When "ZR" expressed,generally considered to be "C" class of flame retardant.Flame retardant level representation is "ZN" middle "A","B","C",such as the "ZA","ZB","ZC".While using "NH" expressed,it generally considered to be "ZCN".For example;
Rated Voltage 0.6/1kV PVC Insulation Power Cable :

Type Description Application
Cu Al
VV VLV Copper-core(aluminum core)PVC insulation and PVC sheath power cable For laying indoor,in tunnels and in ducts,unable to bear external mechanical forces
VY VLY Copper-core(aluminum core)PVC insulation and PE sheath power cable
VV22 VLV22 Copper-core(aluminum core)PVC insulation steel tape armoured PVC sheath power cable For laying indoor,in tunnels and in ducts,can able to bear external mechanical forces
VY23 VLY23 Copper-core(aluminum core)PVC insulation steel tape armoured PE sheath power cable
VV32 VLV32 Copper-core(aluminum core)PVC insulation steel wire armoured PVC sheath power cable For laying in water or ground along route with large difference of level,can able to bear external mechanical forces
VY33 VLY33 Copper-core(aluminum core)PVC insulation steel wire armoured PE sheath power cable
VV42 VLV42 Copper-core(aluminum core)PVC insulation thick wire armoured PVC sheath power cable
VY43 VLY43 Copper-core(aluminum core)PVC insulation thick wire armoured PE sheath power cable

Patameter fof sinle core power cable

Size Nominal thickness of XLPE insulation(mm) Approx. thickness of copper tape screen (mm) Nominal thickness of PVC or PE(mm) Approx. overall diameter of finished cable(mm) Max. conductor D.C resistance @ 20ºC(Ω/km)
1x50mm 2 10.5 0.12 2.1 38.2 0.387
1x70mm 2 10.5 0.12 2.2 40.1 0.268
1x95mm 2 10.5 0.12 2.2 41.7 0.193
1x120mm 2 10.5 0.12 2.3 43.3 0.153
1x150mm 2 10.5 0.12 2.3 44.9 0.124
1x185mm 2 10.5 0.12 2.4 46.7 0.0991
1x240mm 2 10.5 0.12 2.5 49.3 0.0754
1x300mm 2 10.5 0.12 2.5 51.3 0.0601
1x400mm 2 10.5 0.12 2.6 54.7 0.0470
1x500mm 2 10.5 0.12 2.7 58.2 0.0366
1x630mm 2 10.5 0.12 2.8 62.0 0.0283
1x800mm 2 10.5 0.12 3.0 66.2 0.0221

Patameter fof 3 core Power cable

Size Nominal thickness of XLPE insulation(mm) Approx. thickness of copper tape screen (mm) Nominal thickness of steel tape(mm) Nominal thickness of PVC or PE(mm) Approx. overall diameter of finished cable(mm) Max. conductor D.C resistance @ 20ºC(Ω/km)
3x25mm 2 3.4 0.10 0.5 2.3 45.7 0.727
3x35mm 2 3.4 0.10 0.5 2.4 48.1 0.524
3x50mm 2 3.4 010 0.5 2.5 50.9 0.387
3x70mm 2 3.4 0.10 0.5 2.6 54.8 0.268
3x95mm 2 3.4 0.10 0.5 2.7 58.8 0.193
3x120mm 2 3.4 0.10 0.5 2.9 62.4 0.153
3x150mm 2 3.4 0.10 0.5 3.0 66.2 0.124
3x185mm 2 3.4 0.10 0.5 3.1 70.1 0.0991
3x240mm 2 3.4 0.10 0.5 3.3 75.9 0.0754
3x300mm 2 3.4 0.10 0.5 3.4 80.7 0.0601
3x400mm 2 3.4 0.10 0.8 3.7 89.8 0.0470

Patameter fof 4 core Power cable

Cable size Conductor type Nominal thickness of XLPE insulation(mm) Nominal thickness of PVC or PE sheath(mm) Approx. cable overall diameter (mm) Max. D.C resistance @ 20ºC(Ω/km)
4×1.5mm 2 RE or RM 0.7 1.8 10.5 18.1
4×2.5mm 2 RE or RM 0.7 1.8 11.5 12.1
4x4mm 2 RE or RM 0.7 1.8 12.6 7.41
4x6mm 2 RE or RM 0.7 1.8 13.8 4.61
4x10mm 2 RM 0.7 1.8 16.9 3.08
4x16mm 2 RM 0.7 1.8 19.5 1.91
4x25mm 2 SM 0.9 1.8 21.3 1.20
4x35mm 2 SM 0.9 1.8 23.4 0.868
4x50mm 2 SM 1.0 1.9 26.8 0.641
4x70mm 2 SM 1.1 2.0 30.6 0.443
4x95mm 2 SM 1.1 2.1 34.9 0.320
4x120mm 2 SM 1.2 2.3 38.4 0.253
4x150mm 2 SM 1.4 2.4 42.5 0.206
4x185mm 2 SM 1.6 2.6 47.4 0.164
4x240mm 2 SM 1.7 2.8 53.4 0.125
4x300mm 2 SM 1.8 3.0 59.0 0.100