N2xsyry 10 Kv XLPE Insulated Round Steel Wire Armoured Single Copper Cable

N2xsyry 10 Kv XLPE Insulated Round Steel Wire Armoured Single Copper Cable

N2xsyry 10 Kv XLPE Insulated Round Steel Wire Armoured Single Copper Cable

N2XSYRY

Construction, Underground, Power Station

Low and Medium Voltage Cable

DC & AC

XLPE

PVC/PE

Round Wire

Red Copper Wire

ISO, CCC, CE

Cu/XLPE/PVC

Jytop

ASTM/BS/GB/IEC

CCC/Ce/SGS

Black, Red

JYTOP

Drums or as Your Request

ASTM, BS, IEC, CCC, ISO9001

Henan, Zhengzhou

8544492100

Product Description

N2XSYRY 20.3/35 kV XLPE INSULATED ROUND STEEL WIRE ARMOURED, SINGLE -CORE CABLES WITH COPPER CONDUCTOR

Application:
They are used in cable ducts, outdoor and indoor installations, under ground where the short circuit levels are high and industrial areas fed by electrical also these cables use where there is risk of mechanical damage.

Standards:
DIN VDE 0276-620
HD 620 S1: 1996
IEC 60502-2

DIN EN 60228 class 2 (construction)

Construction:

Conductor:Copper or Aluminium
Insulation:XLPE/PVC
Inner sheath:PVC or PE
Outer Sheath:PVC or PE
NO. of cable cross: 1 core(Single core),2cores(Double cores),3cores, 4cores(4 equal-section-area cores OR 3 equal-section-area+1 small section area neutral core),5cores(5 3 equal-section-area cores+2 small area neutral cores OR 4 equal-section-area +1 small area neutral cores).We provide armored type and non-armored type for the cables stated above.
Also can do according to the customer’s request.
Characters:
a.Max Long-time operating temperature of PVC insulated cable is 70°C
b.Installing temperature of cable should not be less than 0°C
c.Max short-circuit temperature is not exceed 160°C,Not more than5 Sec.
d.Permitting bending radius cable: Not less than 10 D times (D:external diameter of cable)

Description & Application:

Maximum operating temp.:90°C

Max.short circuit temp.:250°C (+≥ 5 sn)

Installation temp.min:-5 °C

Standarts: IEC 60502-2 VDE 0276

TECHNICAL FEATURES

Rated Cross
Section

Overall Diameter
Of Cable

Current Carrying
Capacity

Operating
Inductance

Operating
Capacity

Conductor DC
Resistance at (20 oC)

Net
Weight

Delivery
Lenght

mm2

mm

Air (A)

Ground (A)

mH/Km

µF/Km

Ohm/Km

Kg/Km

Mt

1×35/16

40.00

177

165

0,73

0,12

0,524

2840

1000

1×50/16

41.00

253

232

0,71

0,13

0,387

3070

1000

1×70/16

43.00

312

282

0,68

0,14

0,268

3400

1000

1×95/16

46.00

373

332

0,64

0,15

0,193

4200

1000

1×120/16

47.50

425

373

0,62

0,17

0,153

4580

1000

1×150/25

49.00

476

410

0,60

0,18

0,214

5040

1000

1×185/25

51.00

536

456

0,58

0,19

0,0991

5600

1000

1×240/25

53.50

613

517

0,56

0,21

0,0754

6320

500

1×300/25

56.50

687

569

0,54

0,23

0,0601

7170

500

1×400/35

60.00

770

621

0,51

0,25

0,0470

8410

500

1×500/35

63.50

859

678

0,50

0,27

0,0366

9710

500

1×630/35

68.50

947

732

0,49

0,30

0,0283

11490

500

Advantages:
a. Excellent electric and mechanical characteristics
b. Best Resistance chemical corrosion and heat-ageing,environment stress and flame-retardant
c. Simple in structure
d. Convenient to use
e. Light weight,perfect bending properties

Tags: , ,