N2xs (f) 2y 1X630/35mm2 XLPE/Wbt/Cws/MDPE 18/33kv Power Cable

N2xs (f) 2y 1X630/35mm2 XLPE/Wbt/Cws/MDPE 18/33kv Power Cable

N2xs (f) 2y 1X630/35mm2 XLPE/Wbt/Cws/MDPE 18/33kv Power Cable

n2xs(f)2y

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

AC Cable

XLPE

PE

Round Wire

Bare Copper Wire

ISO, CCC

N2xs(F)2y

Hongda

IEC, BS, AS/NZS

as Your Require

as Your Require

6/10 Kv, 12/20 Kv, 18/30 Kv

70c 90c 120c 200c

Steel Wire or Steel Tape

7, 19, 37, 54, 61, 91

99.99%

Extruded Semi-Conductive Skin on Conductor

Extruded Semi-Conductive Skin on Insulation, Longi

Hongda

Wooden Drum/ Steel & Wooden Drum

1mm2-400mm2

Henan China

8544601200

Product Description

n2xs(f)2y 1×630/35mm2 XLPE/WBT/CWS/MDPE 18/33kV power cable

N2XS(F)2Y 6/10 kV, 12/20 kV, 18/30 kV
XLPE-insulated, Cu-conductor, single core, longitudinally watertight, screened, PE-sheath

1. Main Application
Suitable for indoor installation and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switch-boards and power stations. The PE-outer sheath is resistant to high mechanical stress for laying the cables. This PE sheath is not flame retardant acc. to DIN EN 60332-1-2. The inner conducting layer between the conductor and the XLPE insulation and the firmly bonded outer conducting layer on the XLPE insulation assures a construction free of partial discharges with high operational reliability.

2.  Standards
HRN HD 620 S1
IEC 60502-2
DIN VDE 0276 part 620

3.  ProductType

Dimensions – number of cores x conductor cross-section Construction External diameter External diameter Conductor diameter Insulation thickness Conductor resistance at 20 °C Short circuit current 1s Cu weight Cable weight Packing*
    min. max. max. nominal max. nominal   approx.  
N x mm²   mm mm mm mm Ω/km A kg/km kg/km  
6/10 kV
1 x 35/16 RM 23 28 7,5 3,4 0,524 5,00 518   CUT
1 x 50/16 RM 24 29 8,6 3,4 0,387 7,15 662 934 CUT
1 x 70/16 RM 26 31 10,2 3,4 0,268 10,0 854 1154 CUT
1 x 95/16 RM 27 32 12,0 3,4 0,193 13,6 1094 1418 CUT
1 x 120/16 RM 29 34 13,5 3,4 0,153 17,2 1334 1660 CUT
1 x 150/25 RM 30 35 15,0 3,4 0,124 21,4 1723 2016 CUT
1 x 185/25 RM 32 37 16,8 3,4 0,0991 26,5 2059 2357 CUT
1 x 240/25 RM 34 39 19,2 3,4 0,0754 34,3 2587 2911 CUT
1 x 300/25 RM 36 41 21,6 3,4 0,0601 42,9 3163   CUT
1 x 400/35 RM 40 45 24,6 3,4 0,0470 57,2 4234   CUT
1 x 500/35 RM 43 48 27,6 3,4 0,0366 71,5 5194   CUT
12/20 kV
1 x 35/16 RM 27 32 7,5 5,5 0,524 5,00 518   CUT
1 x 50/16 RM 28 33 8,6 5,5 0,387 7,15 662 1091 CUT
1 x 70/16 RM 30 35 10,2 5,5 0,268 10,0 854 1322 CUT
1 x 95/16 RM 31 36 12,0 5,5 0,193 13,6 1094 1596 CUT
1 x 120/16 RM 33 38 13,5 5,5 0,153 17,2 1334 1847 CUT
1 x 150/25 RM 34 39 15,0 5,5 0,124 21,4 1723 2212 CUT
1 x 185/25 RM 36 41 16,8 5,5 0,0991 26,5 2059 2564 CUT
1 x 240/25 RM 39 44 19,2 5,5 0,0754 34,3 2587 3132 CUT
1 x 300/25 RM 41 46 21,6 5,5 0,0601 42,9 3163 3722 CUT
1 x 400/35 RM 44 49 24,6 5,5 0,0470 57,2 4234 4639 CUT
1 x 500/35 RM 47 52 27,6 5,5 0,0366 71,5 5194 5670 CUT
18/30 kV
1 x 50/16 RM 33 38 8,6 8,0 0,387 7,15 662 1312 CUT
1 x 70/16 RM 35 40 10,2 8,0 0,268 10,0 854 1555 CUT
1 x 95/16 RM 36 41 12,0 8,0 0,193 13,6 1094 1842 CUT
1 x 120/16 RM 38 43 13,5 8,0 0,153 17,2 1334 2104 CUT
1 x 150/25 RM 39 44 15,0 8,0 0,124 21,4 1723 2478 CUT
1 x 185/25 RM 41 46 16,8 8,0 0,0991 26,5 2059 2843 CUT
1 x 240/25 RM 43 48 19,2 8,0 0,0754 34,3 2587 3428 CUT
1 x 300/25 RM 46 51 21,6 8,0 0,0601 42,9 3163   CUT
1 x 400/35 RM 49 54 24,6 8,0 0,0470 57,2 4234   CUT
1 x 500/35 RM 52 57 27,6 8,0 0,0366 71,5 5194   CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length

  • rm = round conductor, multi-wire
  • Further types and dimensions on request.
  • AWG sizes are approximate equivalent
    values. The actual cross section is in mm²

4. Technical data

  • XLPE-insulated power cables acc. to
    DIN VDE 0276 part 620, HD 620 S2
    and IEC 60502
  • Temperature range 
    during installation up to -20°C
  • Operating temperature 
    max. +90°C
  • Short circuit temperature 
    +250°C (short circuit duration max. 5 s)
  • Nominal voltage 
    U0/U 6/10 kV, 12/20 kV, 18/30 kV
  • Operating voltage, 50 Hz
    for 6/10 kV = max. 12 kV
    for 12/20 kV = max. 24 kV
    for 18/30 kV = max. 36 kV
  • Test voltage
    for 6/10 kV = 21 kV
    for 12/20 kV = 42 kV
    for 18/30 kV = 63 kV
  • Minimum bending radius 
    15x cable Ø

5. Construction

Conductor: Cu round conductor, multi wire stranded compacted (RM), class 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
Inner screen: extruded semi-conductive skin on conductor
Insulation: XLPE (cross-linked polyethylene, recent mark: PE-X) compound DIX 8 acc. to HRN HD 620 S1
External screen: extruded semi-conductive skin on insulation, longitudinally spliced with insulation (+tape of semi-conductive material)
Swellable tape: watertight, semi-conductive
Concentric conductor: in inner layer corrugated spirally wrapped copper wires, in external layer copper tape wrapped in counter-helix
Separating tape
Sheath: rigid PE (polyethylene) compound DMP 2 acc. to HRN HD 620 S1
sheath colour: black

6. Packing and Transportation
  We provide you with the best product packaging design services, thereby allowing you to save more shipping charges

7. Contact information

   Ms. Vivian Yuan
  Phone: +86 18339931106

 

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.