Mv Single Core 1X120mm2 Aluminum or Copper XLPE/PVC Power Cable
Product Description
1. Description
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC or PE outer sheath.
2. Operating Characteristics
Rated voltage U0/U(Um): 26/35(40.5)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For three core cable: Not less than 15 times of the diameter of cable
Voltage grade is up to 35kv, cross-section area can be up to 400 sqmm (copper or alumimum conductor). Conductor long-time operating temperature is 90° C. In short circuit, conductor highest temperature should be not more than 250° C
3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel or in cable trench, unable to bear external mechanical force.
Single core cable in magnetic duct is not permissible.
4. Manufacturing Standards IEC 60502-2 and Chinese National Standard GB/T 12706-2008.
5.Parameter of 26/35kV single core AL or CU/XLPE/PVC(or PE) Power Cable
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 20ºC(Ω/km) |
1x50mm 2 | 10.5 | 0.12 | 2.1 | 38.2 | 0.387 |
1x70mm 2 | 10.5 | 0.12 | 2.2 | 40.1 | 0.268 |
1x95mm 2 | 10.5 | 0.12 | 2.2 | 41.7 | 0.193 |
1x120mm 2 | 10.5 | 0.12 | 2.3 | 43.3 | 0.153 |
1x150mm 2 | 10.5 | 0.12 | 2.3 | 44.9 | 0.124 |
1x185mm 2 | 10.5 | 0.12 | 2.4 | 46.7 | 0.0991 |
1x240mm 2 | 10.5 | 0.12 | 2.5 | 49.3 | 0.0754 |
1x300mm 2 | 10.5 | 0.12 | 2.5 | 51.3 | 0.0601 |
1x400mm 2 | 10.5 | 0.12 | 2.6 | 54.7 | 0.0470 |
1x500mm 2 | 10.5 | 0.12 | 2.7 | 58.2 | 0.0366 |
1x630mm 2 | 10.5 | 0.12 | 2.8 | 62.0 | 0.0283 |
1x800mm 2 | 10.5 | 0.12 | 3.0 | 66.2 | 0.0221 |
Working Frequency Voltage Test: .
For cable with Uo of 3.6kV or lower: 2.5Uo+2kV/5min without puncture.
For cable with Uo of 3.6Kv~18kV: 3.5Uo/5min without puncture.
For cable with Uo of 21kV and 26 kV: 2.5Uo/30min without puncture.
Chinese Type | Description | Application | |
Cu | Al | ||
YJV | YJLV | Cu conductor(Al conductor)XLPE insulated PVC sheathed power cable | Laying indoors, in tunnel, fixed on the bracket, pipe and buried in the soil, the cable can not bear external mechanical forces. |
YJY | YJLY | Cu conductor(Al conductor)XLPE insulated PE sheathed power cable | |
YJV22 | YJLV22 | Cu conductor(Al conductor)XLPE insulated double of steel-tape armored PVC sheathed power cable | For laying indoors, in tunnel, cable trench, or direct in ground, able to bear external mechanical forces, but unable to bear large pulling force. |
YJV23 | YJLV23 | Cu conductor(Al conductor)XLPE insulated double of steel-tape armored PE sheathed power cable | |
YJV62 | YJLV62 | Cu conductor(Al conductor)XLPE insulated double of aluminium-tape armored PVC sheathed power cable | |
YJV32 | YJLV32 | Cu conductor(Al conductor)XLPE insulated steel-wire armored PVC sheathed power cable | For laying indoors, in tunnel, cable trench, well or direct in ground, able to bear external mechanical forces and certain pulling force |
YJV33 | YJLV33 | Cu conductor(Al conductor)XLPE insulated steel-wire armored PE sheathed power cable | |
YJV72 | YJLV72 | Cu conductor(Al conductor)XLPE insulated aluminium-wire armored PE sheathed power cable |
- Next: High Voltage 18/30kv Copper Conductor XLPE Insulated Power Cable
- Previous: High Voltage18/30kv Copper Conductor XLPE Insulated Power Cable