Middle Voltage XLPE Insulated Power Cable with Copper Conductor
Product Description
12/20kV CU/XLPE/PVC(or PE) Power Cable
1. Description
Construction: Compacted stranded circular copper conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC or PE outer sheath.
2. Operating Characteristics
Rated voltage U0/U(Um): 12/20(24)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For three core cable: Not less than 15 times of the diameter of cable
3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel or in cable trench, unable to bear external mechanical force.
Single core cable in magnetic duct is not permissible.
4. Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
NOTE:
If you want to know more details about this kind of products, please visit our website(homepage) because we have no ways to show so much information on this platform. Thank you.
Main technical data of 12/20KV, Single core, Copper conductor, XLPE insulated, and PVC or PE sheath cable CABLE CONSTRUCTION: 12/20KV CU/XLPE/PVC or PE
Size | Nominal thickness of XLPE insulation(mm) | Approx. thickness of copper tape screen (mm) | Nominal thickness of PVC or PE(mm) | Approx. overall diameter of finished cable(mm) | Max. conductor D.C resistance @ 20 0 C (Ω/km) |
1x35mm 2 | 5.5 | 0.12 | 1.7 | 25.5 | 0.524 |
1x50mm 2 | 5.5 | 0.12 | 1.8 | 26.8 | 0.387 |
1x70mm 2 | 5.5 | 0.12 | 1.8 | 28.5 | 0.268 |
1x95mm 2 | 5.5 | 0.12 | 1.9 | 30.3 | 0.193 |
1x120mm 2 | 5.5 | 0.12 | 1.9 | 31.7 | 0.153 |
1x150mm 2 | 5.5 | 0.12 | 2.0 | 33.5 | 0.124 |
1x185mm 2 | 5.5 | 0.12 | 2.0 | 35.1 | 0.0991 |
1x240mm 2 | 5.5 | 0.12 | 2.1 | 37.7 | 0.0754 |
1x300mm 2 | 5.5 | 0.12 | 2.2 | 39.9 | 0.0601 |
1x400mm 2 | 5.5 | 0.12 | 2.3 | 43.3 | 0.0470 |
1x500mm 2 | 5.5 | 0.12 | 2.4 | 47.2 | 0.0366 |
1x630mm 2 | 5.5 | 0.12 | 2.5 | 51.0 | 0.0283 |
1x800mm 2 | 5.5 | 0.12 | 2.6 | 55.0 | 0.0221 |
- Next: 8.7/15kv XLPE Insulated Cable with Steel Tape Armored
- Previous: Copper Conductor XLPE Insulated Power Cable for Middle Voltage 12/20kv
Contact us
Similar Or Related
-
15kV 3 Core 4/0AWG Aluminum Conductor XLPE Insulated SWA Armored MV Power Cable
-
XLPE Insulated Aerial Service Drop Cable Conductor #3AWG Duplex ICEA S-66-524 NEMA WC7
-
3Cx185mm2 XLPE Insulated Copper Tape Screened Galvanized Steel Wire Armored Power Cable 33kV
-
0.6/1kV 4Cx500mm2 Copper Conductor PVC Insulated SWA Armored LV Power Cable IEC 60502-1
-
Low Voltage Single Core Power Cable 1X300 mm2 N2XCH CU/XLPE/CWS/LSF 0.6/1kV
-
Middle Voltage XLPE Insulated Power Cable with Copper Conductor