Product Description

Medium Voltage XLPE Insulated Unarmoured Power Cable

Application
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.

Property
1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.


Workshop

Shipment

FAQ

1. How many years has Henan Jiapu Cable Group been in production?
Founded in October 1998 by Mr. Gu, our facility has three separate manufacturing workshops within its 100,000-sq.-ft. building. In 2012, we operates in a new 666,000 sq. foot state-of-the-art facility in Xiaodian Industry Park.,Xinxiang, Henan ,China

2. What kinds of products does Jiapu Cable manufacture?

1)Bare Conductor ,such as AAC,AAAC,ACSR,ACAR,AACSR,ACSR/AW and so on;

2)Aerial Bundled Cable (1kV-35kV ),such as Duplex,Triplex,Quadruplex Drop Wires and so on;

3)PVC Insulated (Flexible ) Wire ;

4) PVC Insulated and Sheathed (Armoured) Power Cable;

5)Low, Medium, High Voltage (1kV-220kV) XLPE Insulated (Armoured) Power Cable;

6)Welding Cable, Control Cable, Concentric Cable, Rubber Sheathed Cable and so on;

3. What kind of certifications do you have?

SABS, CE, ISO9001-2000, SGS

4.Which markets do you involve mainly in?

Our products have been exported mainly to Africa, Middle East, South-east Asia, South America,Central America,North America, Europe ,Australia, etc.

5. Which standards do you comply with when you produce the electrical wires and cables ?

We are able to produce electrical wires and cables based on GB, JB, IEC, BS, DIN, ASTM, JIS, NF, AS/NZS, CSA, etc. Meanwhile, we can design and manufacture the cables according to the samples and technical specification the customer supply.

6. What is the min.order quantity ?

It depends on the type and size of electrical wires and cables. For some small electrical wires, 100 meters can be accepted .But for the power cables with medium or high voltage, that should comply with the property of installed equipments. Anyhow,we will try our best to solve the problem and meet with the requirement If you have special request.

7. What is the production capacity per week or per month ?

For the bare conductor, we can finish 3000 tons within one month. For power cables, that depends on the type and size. The total output value per month is approx. USD3,000,000.00 for insulated aluminum cables and that is approx. USD8,000,000.00 for insulated copper cables.

8. Do you supply the customers with installation service in foreign country ?

We don’t have professional installation teams in foreign country.But if that is necessary, we will recommend our partners to cooperate with you.

Specifications:

1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of Normal Thickness of Outer Sheath Approx. Approx. Net Weight Max. D.C. Resistance of Conductor at 20
Copper Tape Overall Dia. Al Conductor Cu Conductor Al Conductor Cu Conductor
mm 2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6 2.5 0.12 1.5 17.6 0.34 0.49 1.2 0.727
35 7 2.5 0.12 1.5 18.5 0.39 0.6 0.868 0.524
50 8.3 2.5 0.12 1.6 20 0.46 0.74 0.641 0.387
70 9.7 2.5 0.12 1.6 21.5 0.55 0.96 0.443 0.268
95 11.3 2.5 0.12 1.7 23.3 0.66 1.23 0.32 0.193
120 13 2.5 0.12 1.7 24.8 0.77 1.48 0.253 0.153
150 14.6 2.5 0.12 1.8 26.4 0.87 1.77 0.206 0.124
185 15.9 2.5 0.12 1.8 28.1 1.01 2.13 0.164 0.0991
240 18.3 2.6 0.12 1.9 30.9 1.23 2.71 0.125 0.0754
300 20.4 2.8 0.12 2 33.6 1.48 3.32 0.1 0.0601
400 23.2 3 0.12 2.1 37 1.81 4.16 0.0778 0.047
500 26.4 3.2 0.12 2.2 41.1 2.24 5.27 0.0605 0.0366
630 30.1 3.2 0.12 2.3 45 2.73 6.62 0.0469 0.0283
2)6/10(12)kV,6.35/11(12)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of Normal Thickness of Outer Sheath Approx. Approx. Net Weight Max. D.C. Resistance of Conductor at 20
Copper Tape Overall Dia. Al Conductor Cu Conductor Al Conductor Cu Conductor
mm 2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6 3.4 0.12 1.5 19.4 0.4 0.55 1.2 0.727
35 6.9 3.4 0.12 1.6 20.5 0.45 0.66 0.868 0.524
50 8.2 3.4 0.12 1.6 21.8 0.52 0.8 0.641 0.387
70 9.7 3.4 0.12 1.7 23.5 0.62 1.03 0.443 0.268
95 11.3 3.4 0.12 1.7 25.1 0.73 1.3 0.32 0.193
120 12.8 3.4 0.12 1.8 26.8 0.85 1.56 0.253 0.153
150 14.2 3.4 0.12 1.8 28.2 0.95 1.85 0.206 0.124
185 15.9 3.4 0.12 1.9 30.1 1.1 2.22 0.164 0.0991
240 18.3 3.4 0.12 2 32.7 1.33 2.8 0.125 0.0754
300 20.4 3.4 0.12 2 34.8 1.54 3.39 0.1 0.0601
400 23.2 3.4 0.12 2.2 38 1.87 4.22 0.0778 0.047
500 26.4 3.4 0.12 2.2 41.5 2.26 5.29 0.0605 0.0366
630 30.1 3.4 0.12 2.4 45.6 2.78 6.67 0.0469 0.0283
3)8.7/10(15)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of Normal Thickness of Outer Sheath Approx. Approx. Net Weight Max. D.C. Resistance of Conductor at 20
Copper Tape Overall Dia. Al Conductor Cu Conductor Al Conductor Cu Conductor
mm 2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6 4.5 0.12 1.6 21.8 0.48 0.63 1.2 0.727
35 6.9 4.5 0.12 1.7 22.9 0.54 0.75 0.868 0.524
50 8.2 4.5 0.12 1.7 24.2 0.61 0.89 0.641 0.387
70 9.7 4.5 0.12 1.8 25.9 0.72 1.13 0.443 0.268
95 11.3 4.5 0.12 1.8 27.5 0.84 1.4 0.32 0.193
120 12.8 4.5 0.12 1.9 29.2 0.96 1.67 0.253 0.153
150 14.2 4.5 0.12 1.9 30.6 1.06 1.96 0.206 0.124
185 15.9 4.5 0.12 2 32.5 1.22 2.34 0.164 0.0991
240 18.3 4.5 0.12 2.1 35.1 1.46 2.93 0.125 0.0754
300 20.4 4.5 0.12 2.1 37.2 1.68 3.52 0.1 0.0601
400 23.2 4.5 0.12 2.2 40.2 2 4.35 0.0778 0.047
500 26.4 4.5 0.12 2.3 43.9 2.43 5.45 0.0605 0.0366
630 30.1 4.5 0.12 2.4 47.8 2.93 6.83 0.0469 0.0283
4)12/20(24)kV, 12.7/22(24)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of Normal Thickness of Outer Sheath Approx. Approx. Net Weight Max. D.C. Resistance of Conductor at 20
Copper Tape Overall Dia. Al Conductor Cu Conductor Al Conductor Cu Conductor
mm 2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25
35 6.9 5.5 0.12 1.7 24.9 0.62 0.83 0.868 0.524
50 8.2 5.5 0.12 1.8 26.4 0.7 0.98 0.641 0.387
70 9.7 5.5 0.12 1.8 27.9 0.8 1.21 0.443 0.268
95 11.3 5.5 0.12 1.9 29.7 0.94 1.5 0.32 0.193
120 12.8 5.5 0.12 1.9 31.2 1.05 1.77 0.253 0.153
150 14.2 5.5 0.12 2 32.8 1.17 2.07 0.206 0.124
185 15.9 5.5 0.12 2 34.5 1.33 2.45 0.164 0.0991
240 18.3 5.5 0.12 2.1 37.1 1.57 3.04 0.125 0.0754
300 20.4 5.5 0.12 2.2 39.4 1.81 3.66 0.1 0.0601
400 23.2 5.5 0.12 2.3 42.4 2.14 4.49 0.0778 0.047
500 26.4 5.5 0.12 2.4 46.1 2.58 5.61 0.0605 0.0366
630 30.1 5.5 0.12 2.4 49.8 3.1 6.99 0.0469 0.0283
5)18/30(36)kV,19/33(36)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of Normal Thickness of Outer Sheath Approx. Approx. Net Weight Max. D.C. Resistance of Conductor at 20
Copper Tape Overall Dia. Al Conductor Cu Conductor Al Conductor Cu Conductor
mm 2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25
35
50 8.2 8 0.12 2 31.8 0.95 1.23 0.641 0.387
70 9.7 8 0.12 2 33.3 1.07 1.47 0.443 0.268
95 11.3 8 0.12 2.1 35.1 1.21 1.78 0.32 0.193
120 12.8 8 0.12 2.1 36.6 1.34 2.05 0.253 0.153
150 14.2 8 0.12 2.2 38.2 1.47 2.37 0.206 0.124
185 15.9 8 0.12 2.2 39.9 1.64 2.76 0.164 0.0991
240 18.3 8 0.12 2.3 42.5 1.9 3.37 0.125 0.0754
300 20.4 8 0.12 2.4 44.8 2.16 4.01 0.1 0.0601
400 23.2 8 0.12 2.4 47.6 2.52 4.87 0.0778 0.047
500 26.4 8 0.12 2.5 51.3 2.98 6.01 0.0605 0.0366
630 30.1 8 0.12 2.6 55.2 3.54 7.43 0.0469 0.0283
6)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable
Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of Normal Thickness of Outer Sheath Approx. Approx. Net Weight Max. D.C. Resistance of Conductor at 20
Copper Tape Overall Dia. Al Conductor Cu Conductor Al Conductor Cu Conductor
mm 2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6 2.5 0.1 2 34.6 1.13 1.58 1.2 0.727
35 6.9 2.5 0.1 2.1 36.8 1.29 1.92 0.868 0.524
50 8.2 2.5 0.1 2.2 39.8 1.51 2.36 0.641 0.387
70 9.7 2.5 0.1 2.3 43.2 1.81 3.04 0.443 0.268
95 11.3 2.5 0.1 2.4 46.9 2.17 3.87 0.32 0.193
120 12.8 2.5 0.1 2.4 50.1 2.53 4.69 0.253 0.153
150 14.2 2.5 0.1 2.5 53.3 2.9 5.6 0.206 0.124
185 15.9 2.5 0.1 2.6 57.2 3.4 6.77 0.164 0.0991
240 18.3 2.6 0.1 2.8 63.2 4.12 8.55 0.125 0.0754
300 20.4 2.8 0.1 3 69 4.89 10.46 0.1 0.0601
400 23.2 3 0.1 3.4 76.7 6.1 13.18 0.0778 0.047
500 26.4 3.2 0.1 3.6 85.7 8.1 16.55 0.0605 0.0366