Product Description

Aluminium Secondary UD Cable
Aluminium Conductors. Polythylene or Crosslinked Polyethylene Insulation.
ABC Cables Applications:
Used to supply 3 phase power, usually from a pole-mounted transformer, to the user’s service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors. 
ABC Cables Construction:
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC, or ACSR.One conductor is manufactured with an extruded ridge for phase identification.
ABC Cables Standards:
1.B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
2.B-231 Aluminum conductors, Concentric-Lay-Stranded.
3.B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
4.B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
5.B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
6.Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
ABC Cables Using Properties
1.Rated Voltage:0.6/1kV
2.Cable installation temperature not less than -20°C
3.Max. temperature of cable at short circuit(The max. duration does not exceed 5 minutes)
   For XLPE insulation is 250°C.
   For HDPE insulation is 150 °C.
4.The Max. bending radius of cable shall not be less than 20Dmm(D overall diameter of cable)
Type of ABC Cable
1.Duplex Service Drop:To supply 120 volt aerial service for temporary service at construction sites,outdoor or street lighting . For service at 600 volts or lower at a conductor temperature of 75 maximum.
2.Triplex Service Drop: To supply power from the ulility`s lines to the consumer`s weatherhead. For service at 600 volts or less(phase to phase ) at a conductor temperature of 75 maximum for PE insulation or 90 maximum for XLPE insulation .
3.Quadruplex Service Drop: Used to supply 3 phase power , usually from a pole-mounted transformer to the use`s servic head where connection to the service entance cable is made . To be used at voltages of 600 volts or less phase to phase and at conductor temperature not to exceed 75 for PE insulated conductors or 90 for XLPE insulated conductors.
ASTM B-230, B-231 and ICEA S-66-524
UL Standard 854 for type USE
Federal Specification JC-30B NEC

Code Name Phase Conductor Neutral Single Phase Conductor(in) Outside diameter(in) Weight Per 1000ft (lbls) Ampacity
Size AWG Strand Insulation Thickness (mls) Size AWG Strand Insulation Thickness (mls) Direct Burial In Duct
Tulsa 4 7/w 60 4 7/w 60 .345 .833 258 119 85
Dyke 2 7/w 60 4 7/w 60 .403 .938 346 153 115
Wittenberg 2 7/w 60 2 7/w 60 .403 .973 375 153 115
Notre Dame 1/0 19/w 80 2 7/w 60 .522 1.188 541 198 150
Purdue 1/0 19/w 80 1/0 19/w 80 .522 1.260 596 198 150
Syracuse 2/0 19/w 80 1/0 19/w 80 .566 1.316 664 225 170
Lafayette 2/0 19/w 80 2/0 19/w 80 .566 1.367 720 225 170
Swarthmore 3/0 19/w 80 1/0 19/w 80 .616 1.430 805 250 195
Davidson 3/0 19/w 80 3/0 19/w 80 .616 1.487 874 250 195
Wake Forest 4/0 19/w 80 2/0 19/w 80 .672 1.560 979 290 225
Earlham 4/0 19/w 80 4/0 19/w 80 .672 1.623 1066 290 225
Slippery Rock 350 37/w 95 4/0 19/w 80 .851 1.945 1544 385 305
Wofford 500 37/w 95 350 37/w 95 .851 2.348 2174 467 420
Windham 750 61/w 110 500 37/w 95 .979 2.850 2542 615 492

 