Manufacture Bare Aluminium Alloy Conductor AAAC Conductor for ASTM B399
APPLICATION:
Used as bare overhead conductor for primary and secondary distribution. Designed for utilizing a high-strength aluminum-alloy to achieve a high strength-to-weight ratio; affords good sag characteristics.
1.AAAC conductors are extensively used for overhead distribution and transmission lines adjacent to ocean coastlines where there can be a problem of corrosion in the steel of an ACSR construction.
2.The aluminum alloy conductors are used in replace of single-layer ACSR conductors to reduce power loss in overhead distribution and transmission lines,when replacing the aluminum conductor steel reinforced , the AAAC can save 5-8% of the construction cost.
3.AAAC referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to replace the conventional ACSR.
CONSTRUCTION:
AAAC is concentric-lay- stranded, similar in
construction and appearance with1350 grade aluminum conductors. They were developed to the need of economical conductor for overhead applications requiring higher strength than that of 1350 grade aluminum conductors, but without a steel core.
STANDARDS:
ASTM B399, BS EN50183 ,BS 3242,DIN 48201,IEC 61089
All Aluminlum Alloy Conductors(AAAC) BS EN 50183
Code Name | Area | No.of wires | Diameter | Mass per unit length | Rated strength | DC resistance | |
Wire | Cond. | ||||||
mm2 | mm | mm | kg/km | kN | Ω/km | ||
BOX | 18.8 | 7 | 1.85 | 5.55 | 51.4 | 5.55 | 1.7480 |
ACACLA | 23.8 | 7 | 2.08 | 6.24 | 64.9 | 7.02 | 1.3828 |
ALMOND | 30.1 | 7 | 2.34 | 7.02 | 82.2 | 8.88 | 1.0926 |
CEDAR | 35.5 | 7 | 2.54 | 7.62 | 96.8 | 10.46 | 0.9273 |
DEODAR | 42.2 | 7 | 2.77 | 8.31 | 115.2 | 12.44 | 0.7797 |
FIR | 47.8 | 7 | 2.95 | 8.85 | 130.6 | 14.11 | 0.6875 |
HAZEL | 59.9 | 7 | 3.3 | 9.90 | 163.4 | 17.66 | 0.5494 |
PLNE | 71.6 | 7 | 3.61 | 10.8 | 195.6 | 21.14 | 0.4591 |
HOLLY | 84.1 | 7 | 3.91 | 11.7 | 229.5 | 24.79 | 0.3913 |
WILLOW | 89.7 | 7 | 4.04 | 12.1 | 245.0 | 26.47 | 0.3665 |
OAK | 118.9 | 7 | 4.65 | 14.0 | 324.5 | 35.07 | 0.2767 |
MULBERRY | 150.9 | 19 | 3.18 | 15.9 | 414.3 | 44.52 | 0.2192 |
ASH | 180.7 | 19 | 3.48 | 17.4 | 496.1 | 53.31 | 0.1830 |
ELM | 211 | 19 | 3.76 | 18.8 | 579.2 | 62.24 | 0.1568 |
POPLAR | 239.4 | 37 | 2.87 | 20.1 | 659.4 | 70.61 | 0.1387 |
SYCAMORE | 303.2 | 37 | 3.23 | 22.6 | 835.2 | 89.40 | 0.1095 |
UPAS | 362.1 | 37 | 3.53 | 24.7 | 997.5 | 106.82 | 0.0917 |
YEW | 479 | 37 | 4.06 | 28.4 | 1319.6 | 141.31 | 0.0693 |
TOTARA | 498.1 | 37 | 4.14 | 29.0 | 1372.1 | 146.93 | 0.0666 |
RUBUS | 586.9 | 61 | 3.5 | 31.5 | 1622.0 | 173.13 | 0.0567 |
SORBUS | 659.4 | 61 | 3.71 | 33.4 | 1822.5 | 194.53 | 0.0505 |
ARAUCARIA | 821.1 | 61 | 4.14 | 37.3 | 2269.4 | 242.24 | 0.0406 |
REDWOOD | 996.2 | 61 | 4.56 | 41.0 | 2753.2 | 293.88 | 0.0334 |
All Aluminium Alloy Conductors (AAAC) BS EN 50183
Designation | Area | Stranding wire Dia. | Overall Diameter | Nominal Breaking Load | Nominal DC Resistance at 20ºC | Standard Weight | |
mm2 | No | Φ | mm | kN | Ohm/km | kg/km | |
ASTER 22 | 22 | 7 | 2 | 6 | 7.15 | 1.4989 | 60 |
ASTER 34.4 | 34.4 | 7 | 2.5 | 7.5 | 11.17 | 0.9593 | 93.8 |
ASTER 54.6 | 54.6 | 7 | 3.15 | 9.45 | 17.73 | 0.6042 | 148.9 |
ASTER 75.5 | 75.5 | 19 | 2.25 | 11.3 | 24.55 | 0.4388 | 207.4 |
ASTER 117 | 117 | 19 | 2.8 | 14 | 38.02 | 0.2833 | 321.2 |
ASTER 148 | 148.1 | 19 | 3.15 | 15.8 | 48.12 | 0.2239 | 406.5 |
ASTER 181.6 | 181.6 | 37 | 2.5 | 17.5 | 59.03 | 0.1831 | 500.3 |
ASTER 228 | 227.8 | 37 | 2.8 | 19.6 | 74.04 | 0.146 | 627.6 |
ASTER 288 | 288.3 | 37 | 3.15 | 22.1 | 93.71 | 0.1154 | 794.3 |
ASTER 366 | 366.2 | 37 | 3.55 | 24.9 | 115.36 | 0.0908 | 1008.9 |
ASTER 570 | 570.2 | 61 | 3.45 | 31.1 | 185.33 | 0.0585 | 1576 |
ASTER 851 | 850.7 | 91 | 3.45 | 38 | 276.47 | 0.0394 | 2360.7 |
ASTER 1144 | 1143.5 | 91 | 4 | 44 | 360.22 | 0.0293 | 3173.4 |
ASTER 1600 | 1595.9 | 127 | 4 | 52 | 502.72 | 0.021 | 4427.5 |
AAAC (Characteristics of A2 Conductors) IEC 61089
Code number | Area | Number of wires | Diameter | Linear mass | Rated strength | D.C resistance | |
Wire | Cond | ||||||
mm2 | mm | mm | kg/km | kN | Ohm/km | ||
16 | 18.4 | 7 | 1.83 | 5.49 | 50.4 | 5.43 | 1.7896 |
25 | 28.8 | 7 | 2.29 | 6.86 | 78.7 | 8.49 | 1.1453 |
40 | 46 | 7 | 2.89 | 8.68 | 125.9 | 13.58 | 0.7158 |
63 | 72.5 | 7 | 3.63 | 10.9 | 198.3 | 21.39 | 0.4545 |
100 | 115 | 19 | 2.7 | 13.9 | 316.3 | 33.95 | 0.2877 |
125 | 144 | 19 | 3.1 | 15.5 | 395.4 | 42.44 | 0.2302 |
160 | 184 | 19 | 3.51 | 17.6 | 506.1 | 54.32 | 0.1798 |
200 | 230 | 19 | 3.93 | 19.6 | 632.7 | 67.91 | 0.1439 |
250 | 288 | 19 | 4.39 | 22 | 790.8 | 84.88 | 0.1151 |
315 | 363 | 37 | 3.53 | 24.7 | 998.9 | 106.95 | 0.0916 |
400 | 460 | 37 | 3.98 | 27.9 | 1268.4 | 135.81 | 0.0721 |
450 | 518 | 37 | 4.22 | 29.6 | 1426.9 | 152.79 | 0.0641 |
500 | 575 | 37 | 4.45 | 31.2 | 1585.5 | 169.76 | 0.0577 |
560 | 645 | 61 | 3.67 | 33 | 1778.4 | 190.14 | 0.0516 |
630 | 725 | 61 | 3.89 | 35 | 2000.7 | 213.9 | 0.0458 |
710 | 817 | 61 | 4.13 | 37.2 | 2254.8 | 241.07 | 0.0407 |
800 | 921 | 61 | 4.38 | 39.5 | 2540.6 | 271.62 | 0.0361 |
900 | 1036 | 91 | 3.81 | 41.8 | 2861.1 | 305.68 | 0.0321 |
1000 | 1151 | 91 | 4.01 | 44.1 | 3179 | 339.53 | 0.0289 |
1120 | 1289 | 91 | 4.25 | 46.7 | 3560.5 | 380.27 | 0.0258 |
1250 | 1439 | 91 | 4.49 | 49.4 | 3973.7 | 424.41 | 0.0231 |
Contacts
Vivian Wong
T: 86-371-55367868
M: 86-18339931106
- Next: Elecrtric Aluminum Cable with PVC Insulated
- Previous: Electric Overhead Bare Aluminum AAAC Conductor for Power Transmission Line
Contact us
Similar Or Related
-
Aster Cable 366mm2 37 Strands AAAC Bare Conductor for 90kV HV Substation
-
AAAC Bare Conductor 100mm2 7/4.26mm for Uganda 33kV Distribution Line
-
AAAC Bare Conductor 50mm2 7/3.02mm for Uganda 11kV Distribution Line
-
Aerial Bundled Conductor 70mm2 Hard drawn Aluminum ABC Cable for 400V Distribution Line
-
50mm2;AAAC PVC Covered Hazel Conductor BS 3242 for 11kV Distribution Line
-
Manufacture Bare Aluminium Alloy Conductor AAAC Conductor for ASTM B399