LV Aerial Bundle Cable (600/1000V) 1X16 AAC/XLPE+16mm2 AAAC

LV Aerial Bundle Cable (600/1000V) 1X16 AAC/XLPE+16mm2 AAAC

LV Aerial Bundle Cable (600/1000V) 1X16 AAC/XLPE+16mm2 AAAC

1×16 AAC/XLPE+16mm2 AAAC

Insulated

Stranded

Overhead

Aluminum

None

XLPE

Round Wire

UV-Resistand

ISO9001, CE, CCC

Jinshui

0.6/1kv

Multicores

JINSHUI

Drum

CE, ASTM, BS

P. R. China

8544492100

Product Description

Quick Details
Place of Origin: Henan, China (Mainland)
Brand Name: JNSHUI CABLE
Model Number: Service Drop Cable
Insulation Material: XLPE
Type: 0.6/1kv – 33kv
Application: Overhead
Conductor Material: AAC
Jacket: XLPE
cable meets: ICEA S-76-474
Standard: ASTM BS IEC and so on
Certicificate: ISO9001:2000
Price: Best price in china
Quality: good quality
Packaging & Delivery

Packaging Details: Standard export wooden drums Export Wooden Drums. Coil.reel
Delivery Detail: 45 days

Ref. No. Description Unit Data
8.1 LV AERIAL BUNDLE CABLE (600/1000V)
1x16+16mm2
1 Manufacturer HENAN JISNHUI CABLE GROUP CO.,LTD
2 Standards IEC 60502
3 Nominal voltage (Uo/U) KV 0.6/1kv
4 Phase conductor
4.1 Phase conductor material AAC
4.2 Cross-section of phase conductor. mm2 16
4.3 No. Of strands wires/Single wire diameter 6/1.7
4.4 Diameter of phase conductor mm 5.1
4.5 Thickness of insulation XLPE mm 1.2
4.6 External diameter of individual core mm 7.5
4.7 Modulus of elasticity N/mm2 59000
5 Netural conductor
5.1 Netural conductor material AAAC
5.2 Cross sectional of neutral wire mm² 16
5.3 No. Of strands wires/Single wire diameter 1/1.7
5.4 Diameter of neutral wire mm 5.1
5.5 Ultimate tensile strength of suspension wire KN 4.69
5.6 Thickness of suspension wire covering mm Bare
6 Overall diameter of bundle mm 12.6
7 Total weight of bundle per km kg/km 110
8 Maximum DC resistance / km at 20°C

  • Phase conductors
  • Neutral conductor

Ω /km
Ω /km

1.91
2.217
9 Working inductance MH/km 0.23
10 Working capacitance mF/km 0.60*10-3
11 1 sec. Thermal short circuit current (maximum conductor temperature 130°C, final conductor temperature.
KA

0.9
12 Maximum continuous current at 35°C ambient temperature 0.6m/sec wind and 90°C conductor temperature.

  • Phase conductors
  • Neutral conductor

A
A

110
105

13 Zero sequence impedance Ω/km N/A
14 Modulus of elasticity N/mm2 60000
15 Standard unjointed length on drum m 3000