1. Operating Characteristics
Rated voltage: 0.6/1(1.2)kV
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 15 times of the diameter of cable
For multi-core cable: Not less than 12 times of the diameter of cable
When the armored single core cable used for Alternative Current(AC) system, the armoring material should be non-magnetic.
2. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or direct in ground, able to bear external mechanical force, but unable to bear large pulling force.
3. Manufacturing Standards
IEC 60502-1 & Chinese national standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
KINDLY NOTE: If you want to know more details about this kind of products, please visit our website:jytopcable for further information. Thanks.
Cable size | Conductor type | Nominal thickness of XLPE insulation(mm) | Nominal thickness of steel tape(mm) |
Nominal thickness of PVC or PE sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 20 0 C (Ω/km) | |||
Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
||||
3×2.5+2×1.5mm 2 | RE | RE | 0.7 | 0.7 | 0.2 | 1.8 | 15.1 | 7.41 | 12.1 |
3×4+2×2.5mm 2 | RE | RE | 0.7 | 0.7 | 0.2 | 1.8 | 16.3 | 4.61 | 7.41 |
3×6+2x4mm 2 | RE | RE | 0.7 | 0.7 | 0.2 | 1.8 | 17.7 | 3.08 | 4.61 |
3×10+2x6mm 2 | RM | RE | 0.7 | 0.7 | 0.2 | 1.8 | 20.3 | 1.83 | 3.08 |
3×16+2x10mm 2 | RM | RM | 0.7 | 0.7 | 0.2 | 1.8 | 23.4 | 1.15 | 1.83 |
3×25+2x16mm 2 | SM | RM | 0.9 | 0.7 | 0.2 | 1.8 | 25.5 | 0.727 | 1.15 |
3×35+2x16mm 2 | SM | RM | 0.9 | 0.7 | 0.2 | 1.8 | 26.9 | 0.524 | 1.15 |
3×50+2x25mm 2 | SM | SM | 1.0 | 0.9 | 0.5 | 2.0 | 31.6 | 0.387 | 0.727 |
3×70+2x35mm 2 | SM | SM | 1.1 | 0.9 | 0.5 | 2.1 | 35.4 | 0.268 | 0.524 |
3×95+2x50mm 2 | SM | SM | 1.1 | 1.0 | 0.5 | 2.3 | 39.9 | 0.193 | 0.387 |
3×120+2x70mm 2 | SM | SM | 1.2 | 1.1 | 0.5 | 2.4 | 43.9 | 0.153 | 0.268 |
3×150+2x70mm 2 | SM | SM | 1.4 | 1.1 | 0.5 | 2.5 | 46.9 | 0.124 | 0.268 |
3×185+2x95mm 2 | SM | SM | 1.6 | 1.1 | 0.5 | 2.7 | 52.3 | 0.0991 | 0.193 |
3×240+2x120mm 2 | SM | SM | 1.7 | 1.2 | 0.5 | 2.9 | 57.9 | 0.0754 | 0.153 |
3×300+2x150mm 2 | SM | SM | 1.8 | 1.4 | 0.5 | 3.1 | 63.6 | 0.0601 | 0.124 |