Low Vlotage ABC Cable, Urd Cable, Twisted Cable
Product Description
APPLICATION
ABC cable is suitable for transmitting line and distributing line of rated voltage 0.6/1KV and others.It is widely used at tall buildings,traveling development area and rural area or other place the cost of underground network is expensive.
—————————————————————————————————————————–
Basic Information
Code Name
ABC
Rated Voltage (Uo/U)
0.6/1KV
Temperature Range
-15ºC-90ºC
—————————————————————————————————————————–
CONSTRUCTION
Conductor: Copper or Aluminium
Insulation: XLPE
Normally,ABC Cable(ABC Bundled Cable-Aerial Cable) do not use copper,because Aluminium Cost is high,most of our customers use aluminium.
—————————————————————————————————————————–
CABLE STANDARDS
Chinese National Standards, IEC,SANS 1418-1, SANS1418-2, ASTMB230, ASTMB231,ASTM B398,ASTM B399, NF C33-209 and etc. upon request.
—————————————————————————————————————————–
Aerial Bundle Conductor-ABC(South Africa Standard Sizes)-SANS 1418-1
Table 01 Aerial Bundled Cable-ABC-BS 7870-5
ABC Cables without Street Lighting | |||||||
1+1 Structure | |||||||
Phase Conductor | Neutral Conductor | Completed Cable | |||||
Section | Insulation Thickness | Electrical Resistance | Section | Insulation Thickness | Electrical Resistance | Overall Diameter | Cable Weight |
DC.20°C | DC.20°C | ||||||
No.xmm2 | mm | Ω/km | mm2 | mm | Ω/km | mm | kg/km |
1×25 | 1.3 | 1.20 | 25 | 1.3 | 1.20 | 17.6 | 210 |
1×35 | 1.3 | 0.868 | 35 | 1.3 | 0.868 | 19.6 | 270 |
1×50 | 1.5 | 0.641 | 50 | 1.5 | 0.641 | 23 | 360 |
1×70 | 1.5 | 0.443 | 70 | 1.5 | 0.443 | 26.4 | 500 |
1×95 | 1.7 | 0.320 | 95 | 1.7 | 0.320 | 30.6 | 680 |
3+1 Structure | |||||||
Phase Conductor | Neutral Conductor | Completed Cable | |||||
Section | Insulation Thickness | Electrical Resistance | Section | Insulation Thickness | Electrical Resistance | Overall Diameter | Cable Weight |
DC.20°C | DC.20°C | ||||||
No.xmm2 | mm | Ω/km | mm2 | mm | Ω/km | mm | kg/km |
3×25 | 1.3 | 1.20 | 25 | 1.3 | 1.20 | 21.2 | 410 |
3×35 | 1.3 | 0.868 | 35 | 1.3 | 0.868 | 23.7 | 550 |
3×50 | 1.5 | 0.641 | 50 | 1.5 | 0.641 | 27.8 | 730 |
3×70 | 1.5 | 0.443 | 70 | 1.5 | 0.443 | 31.9 | 1000 |
3×95 | 1.7 | 0.320 | 95 | 1.7 | 0.320 | 36.9 | 1370 |
3×120 | 1.7 | 0.253 | 120 | 1.7 | 0.253 | 40.6 | 1690 |
ABC Cables with Street Lighting | |||||||
3+1+1 Structure | |||||||
Phase Conductor | Neutral Conductor | Street Lighting Conductor | Completed Cable | ||||
Section | Insulation Thickness | Section | Insulation Thickness | Section | Insulation Thickness | Overall Diameter | Cable Weight |
No.xmm2 | mm | mm2 | mm | mm2 | mm | mm | kg/km |
3×50 | 1.5 | 50 | 1.5 | 25 | 1.3 | 29.8 | 830 |
3×70 | 1.5 | 70 | 1.5 | 25 | 1.3 | 33.6 | 1100 |
3×95 | 1.7 | 95 | 1.7 | 25 | 1.3 | 38.2 | 1470 |
- Next: VV Electric Cable Copper Conductor 3X120+1X70 Power Cable
- Previous: AAC Conductor with BS 215, DIN48201, CSA C49, ASTM B231