Instrumentation Cable 1tx1.5mm2

Instrumentation Cable 1tx1.5mm2

Instrumentation Cable 1tx1.5mm2

Insulated

Solid

Underground

Copper

PE

ISO9001

Telephone Cable(Twisted Cable,Armoured Type)

Yifang

Drum, Reel or According to Customers' Request

IEC, BS, NFC, GOST, DIN, etc.

Zhengzhou, Henan, China

8544492100

Product Description

1.Standard
 
The control cable can be produced according to the standard GB9330-1988,IEC,DIN,BS,and the factory can also manufacture the cables in accordance with other standards.
 
2.Scope of Application
 
The control cable are suitable for the wiring of electrical controlling equipments and instrument, monitoring and controlling return circuit, electrical protection and measurement in power distribution unit under the circumstance that the rated voltage is up to 450/750V AC.
 
3.Type& Specification
 

Type Name Section Area(mm2) No. of Core Application Site
KVV Copper Conductor, PVC Insulated and Sheathed Control Cable 0.75 1.0 1.5 2.5 2-16 Permanent installation indoors, in cable ditches or pipes
4 6 2-14
10 2-10
KVVP Copper Conductor, PVC Insulated and Sheathed, Braiding Shielded  Control Cable 0.75 1.0 1.5 2.5 2-61 Permanent installation indoors, in cable ditches or pipes where shielding is required
4 6 2-14
10 2-10
KVVP2 Copper Conductor, PVC Insulated and Sheathed, Copper-tape Screened Control Cable 0.75 1.0 1.5 2.5 4-10 Permanent installation indoors, In cable ditches or pipes where shielding is required
4 6 7-61
10 4-10
KVV22 Copper Conductor, PVC Insulated and Sheathed, Steel tape Armored Control Cable 0.75 1.0 1.5 2.5 7-61 Permanent installation indoors, in cable ditches, Be able to withstand stronger external mechanical force
4 6 4-14
10 4-14
KVVR Copper Conductor, PVC Insulated and Sheathed, Flexible Control Cable 0.5-2.5 4-61 Installation indoors where flexibility and movability are required
KVVRP Copper Conductor, PVC Insulated and Sheathed, Braiding shielded Flexible Control Cable 0.5 0.75 1.0 4-61 Installation indoors where flexibility shielding and movability are required
1.5 2.5 4-48
KYJV Copper Conductor, XLPE Insulated and PVC Sheathed Control Cable 0.75 1.0 1.5 2.5 2-16 Permanent installation indoors, in cable ditches or pipes
4 6 2-14
10 2-10
KYJVP Copper Conductor, XLPE Insulated, Braiding Shielded, PVC Sheathed Control Cable 0.75 1.0 1.5 2.5 2-61 Permanent installation indoors, in cable ditches or pipes where shielding is required
4 6 2-14
10 2-10
KYJV22 Copper Conductor, XLPE Insulated, Steel-tape Armored, PVC Sheathed Control Cable 0.75 1.0 1.5 2.5 7-61 Permanent installation indoors, in cable ditches, pipes or underground Be cable to with stand stronger external mechanical force
4 6 4-14
10 4-10
KYJVP2 Copper Conductor, XLPE Insulated, Copper tape Screened, PVC Sheathed Control Cable 0.75 1.0 1.5 2.5 7-61 Permanent installation indoors, in cable ditches or pipes where shielding is required
4 6 4-14
10 4-10
KYJVR Copper Conductor,XLPE Insulated,PVC Sheathed Flexible Control Cable 0.5-2.5 4-61 Installation indoors where flexibility and movability are required
KYJVRP Copper Conductor,XLPE Insulated,Braiding Shielded,PVC Sheathed Flexible Control Cable 0.5 0.75 1.0 4-61  Installation indoors where flexibility shielding and movability are required
1.5 2.5 4-48

 
 
4.Service Conditions
 
(1) The long-time working temperature of conductor of PVC insulated cable is 70oC
      The long-time working temperature of conductor of XLPE insulated cable is 90oC
(2) The temperature for laying the cables cannot be lower than 0oC.
(3) Permissible bending radius(r):unarmored cable:r≥6D;(D: outer diameter of the cable);armored or               copper-tape screened cable:r≥12D;shielded flexible cable:r≥6D