High Voltage Power Cables Insulated Down Conductor 50mm2 for Lightning Protection System

1. Basic information

Standard: IEC 62561-8
Application: Lightning Protection System
Lightning impulse voltage: 250kV and 750kV
Color of outer sheath: Black or grey

2. Specification

Technical Particulars of High Voltage Insulated Down Conductor
No. Description Unit Particular
Model #1 Model #2
1 System Application Lightning Protection System
2 Reference Standard IEC 60502, IEC 60230, IEC62561-8
3 Conductor Particulars
3.1 Nominal cross sectional area mm2 50 50
3.2 Diameter of Concuctor(approx.) mm 8.4 8.4
3.3 Number and diameter of individual wire Nos/mm 7/3.06 7/3.06
3.4 Material Copper Copper
3.5 Shape Round Round
3.6 Type
3.6.1 Solid / Standed Standed Standed
3.6.2 Compacted or uncompacted Compacted Compacted
3.7 Max. DC resistance of conductor at 20ºC Ω 0.387 0.387
4 Conductor Screen Particulars
4.1 Material (Compound / Tape) Semi-conductive Compound
4.2 Thickness mm 1 1
4.3 Method of Application Lapped / Extruded Extruded Extruded
5 Insulation Particulars
5.1 Materal High-dieletric Compound
5.2 Minimum Thickness mm 6.5 19
6 Insulation Screen Particulars
6.1 Material (Compound / Tape) Semi-conductive Compound
6.2 Thickness 2.0 2.0
6.3 Method of Application Lapped / Extruded Extruded Two layered Extruded
7 Outer Sheath
7.1 Material Grey PE ( color code 424 C ) refer to IEC 304
7.2 Character UV-resistance
7.3 Thickness mm 1.5 1.5
8 Approximate overall diameter of the cable mm 30.4 55.4
9 Approximate weight of cable kg/km 970 2560
10 Minimum Bending radius during installation mm 608 1108
11 Lightning Impulse withstand Votage kV 250 750
12 Reference Drawing : See cable drwaing