High Voltage Limit Current Fuse for Full Range Protection

High Voltage Limit Current Fuse for Full Range Protection

High Voltage Limit Current Fuse for Full Range Protection

IEC600282

Discoloration

F

Insert

High Voltage

Current Fuse

High

SASUN

Carton

3.6KV /6KV, 12KV, 24KV, 33KV, 36KV

China

8535100000

Product Description

This product is suitable for indoor ac 50 hz, rated voltage 12 kv system, it can be reliably cut between minimum breaking current and open circuit current rating of any fault current, the product not only with the current limiting fuse with relatively high breaking capacity, and have the unlimited streaming fuse have the characteristics of low current protection is good, can get a full range of open circuit is good protective properties. 
Type instruction:
Sheet :CHART 1
Basic parameters:

 Rated voltage (KV) Rated current of the fuse (A) Rated current of the fuselink(A) Rated bredk current KA
12 63 10,16,20,25,25,31.5,40,50,63 50

Selecting principles:
 

12KV primary voltage of the transformer 12KV
Transformer capacity KVA  Fuse rated current (A)  Fuse type
<125 10  
160 16
200-250 20
315 25
400 31.5
500 40
630 50
800 63