H07V-K H05V-K French Standard Insulated Wires

H07V-K H05V-K French Standard Insulated Wires

H07V-K H05V-K French Standard Insulated Wires

H07V-K / H05V-K

Insulated

Flexible

Heating, Underground

Indoor Lighting

Copper

No

PVC

Round or Flat

Flame Retardant

ISO9001, CE, CCC

Yifang

NF C 32-201-3

YIFANG

Treated Wooden Drums

16AWG TO 500MCM

China

8544492100

Product Description

 

H07V-K H05V-K French Standard Insulated Wires
 

H05V-K

Application and Description

These insulated wires are determined for installation to the inside of apparatus as well as for the protective laying to the lightings, in dry rooms, in production facilities, switch and distributors boards, in tubes, under and surface mounting of plasters.

Standard and Approval

  • NF C 32-201-3
  • CE Low Voltage Directive 73/23/EEC and 93/68/EEC

Cable Construction

Fine bare copper strands
Strands to VDE-0295 Class-5, IEC 60228 Class-5
Special PVC TI1 core insulation
Cores to VDE-0293 colors on chart

 

Technical Characteristics

Working voltage 300/500v
Test voltage 2000 volts
Flexing bending radius 12.5 x O
Static bending radius 12.5 x O
Flexing temperature -5oC to +70oC
Static temperature -30oC to +80oC
Flame retardant NF C 32-070
Insulation resistance 10 MΩ x km

Cable Parameter

AWG No. of Cores x Nominal Cross Sectional Area Nominal Thickness of Insulation Nominal Overall Diameter Nominal Copper Weight Nominal Weight
  # x mm^2 mm mm kg/km kg/km
20(16/32) 1 x 0.5 0.6 2.1 4.9 10
18(24/32) 1 x 0.75 0.6 2.4 7.2 13
17(32/32) 1 x 1 0.6 2.6 9.6 15

H07V-K
 

Application and Description

These are not suitable to be installed for laying in tubes, under and surface mounting of plaster and also in closed installation conduits.

These are not allowed to install for direct laying on cable trays, channel or tanks. These types are permitted for the inner wiring of equipment, distributor and switchboards and also for protective laying to the lightings with a nominal voltage up to 1000 V alternating current or up to 750 V direct current against earth.

Standard and Approval

  • NF C 32-201-3
  • CE Low Voltage Directive 73/23/EEC and 93/68/EEC

Technical Characteristics

Working voltage 450/750V
Test voltage 2500 volts
Flexing bending radius 12.5 x O
Static bending radius 12.5 x O
Flexing temperature -5o C to +70o C
Static temperature -30o C to +80o C
Short circuit temperature +160o C
Flame retardant NF C 32-070
Insulation resistance 10 MΩ x km

Cable Parameter

AWG No. of Cores x Nominal Cross Sectional Area Nominal Thickness of Insulation Nominal Overall Diameter Nominal Copper Weight Nominal Weight
  # x mm^2 mm mm kg/km kg/km
16(30/30) 1 x 1.5 0,7 3.1 14.4 20
14(50/30) 1 x 2.5 0,8 3.6 24.0 31
12(56/28) 1 x 4 0,8 4.3 38.0 48
10(84/28) 1 x 6 0,8 4.9 58.0 69
8(80/26) 1 x 10 1,0 6.4 96.0 121
6(128/26) 1 x 16 1,0 8.1 154.0 211
4(200/26) 1 x 25 1,2 9.8 240 303
2 (280/26) 1 x 35 1,2 11.1 336 417
1 (400/26) 1 x 50 1,4 13.1 480 539
2/0 (356/24) 1 x 70 1,4 15.5 672 730
3/0 (485/24) 1 x 95 1,6 17.2 912 900
4/0 (614/24) 1 x 120 1,6 19.7 1152 1135
300 MCM (765/24) 1 x 150 1,8 21.3 1440 1410
350 MCM (944/24) 1 x 185 2,0 23.4 1776 1845
500MCM(1225/24) 1 x 240 2,2 27.1 2304 2270

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.