Fully Enclosed Resin Casting Waterproof Busway

Fully Enclosed Resin Casting Waterproof Busway

Fully Enclosed Resin Casting Waterproof Busway

Enclosed busway

CE, ASTM, ISO9001, ISO14000

Copper

Solid

Bare

Busbar

Distribution Cabinet Basbar ; Transformer

Hard,Soft,Semi-Hard

50, 60Hz

-5/+40ºC

20mΩ

SanWu Cable

Ply-Wooden Case or as Required

as per the spec

China

8544422900

Product Description

Luoyang SanWu Cable Factory Co., Ltd. is founded in the Sept. 2011 with registered fund 200 million RMB which is
the subsidiary of Luoyang Asian Sun Industrial Group Co., Ltd. We can produce all kinds of high and low voltage
electric wire and cables, and have been one of the new technology development enterprise made scientific, industry,
trading as a whole.
Main products include power cables, PV cable, control cables, branching cables, aerial cables, Most important thing is
that we also produce the raw material-aluminium wire rod coperated with Ls Group etc. Seven big series, more than 300 varieties,
nearly 2000. Specifications. 

Product details                                                                                                 

Casting Type Fireproof and Waterproof Busway
Enclosed busway is suitable for AC three-phase four-wire, three-phase five-wire system, with a frequency of 50 ~ 60Hz, a rated voltage of 690V,
and a rated working current of 250 ~ 5000A. Auxiliary equipment for power distribution equipment.
Enclosed busway (referred to  Busway) is a bus system composed of a metal plate (steel plate or aluminum plate) as a protective shell,
a conductive bar, insulating materials and related accessories.
Enclosed busway is widely used in power plants, substations, industrial and civil power leads. Its appearance is a change to traditional power
transmission technology.

Busway Specification Sheet:

Current A 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000 6300
Resistance R20 μΩ/m 82.3 64.5 62 60.1 58.6 53.5 49.7 43.7 38.3 28.8 25.4 20.6 17.1 10.5 7.8 7.5
Reactance X μΩ/m 29.3 27.4 26.7 25.1 24.7 23.6 19.4 16.4 13.1 15.9 13.8 11.1 8.9 7.8 6.6 5.9
Total Reactance μΩ/m 87.4 70.1 67.5 65.1 63.6 58.5 53.4 46.7 40.5 32.9 28.9 23.4 19.3 13.1 10.2 9.5
Total pressuredrop V/m 0.064 0.063 0.062 0.061 0.059 0.058 0.056 0.054 0.051 0.049 0.048 0.049 0.047 0.046 0.045 0.043
Icw kA 20 20 35 20,35,50 50 65 65 80 80 100 120
Ipk kA 40 40 73.5 40,73.5,105 105 143 143 176 176 220 264
Type XLC/3F,XLC/4F,XLC/5F
Execution standard IEC60439.1-1999;IEC60439.2-2000;GB7251.6-2015
Ambient temperature ºC -5/+40
Rated voltage kV AC 380/690
Insulation voltage kV AC 660/1000
Frequency Hz 50,60
Altitude m Under 2000
IP Rating   IP54,IP65
Length m 0.5-6m