Freetox Halogen-Free N2xoh 0, 6/1 Kv 3X120+1X70 mm2 Multipolar Cable

Freetox Halogen-Free N2xoh 0, 6/1 Kv 3X120+1X70 mm2 Multipolar Cable

Freetox Halogen-Free N2xoh 0, 6/1 Kv 3X120+1X70 mm2 Multipolar Cable

N2XOH

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC & AC

XLPE

LSZH

Round Wire

Red Copper Wire

ISO, CCC

SGS

Cable N2xoh

Hongda

0.6/1kv

Hongda/OEM

500m/1000m Per Drum

2.5 to 630mm2

China

8544492100

Product Description

Freetox halogen-free N2XOH 0,6/1 kV 3×120+1×70 mm2 Multipolar Cable

DESCRIPTION
Application:

In electrical networks of low voltage distribution. Special application in those areas with little ventilation, direct application in places with a high influx of people. It can be installed in ducts or directly buried in dry and wet places. Not recommended for outdoor installations.

Construction:

1. Conductor: Soft copper, class 2.
2. Insulation: XLPE crosslinked polyethylene.
3. Insulated ground conductor: Soft copper, class 2 – XLPE.
4. Filler: HFFR halogen-free thermoplastic compound (when applicable).
5. Outer sheath: HFFR halogen-free thermoplastic compound.

Main features:

The cable has excellent electrical properties. The cross-linked polyethylene insulation allows greater current capacity in any operating condition, minimum dielectric losses, high insulation resistance. The external cover has the following characteristics: It does not spread the fire, low emission of dense smoke and free of halogens. Adequate resistance to oils.

Section:
From 2.5 mm2 to 400 mm2.

Packaging:
On non-returnable wooden reels.

National standards
NTP-IEC 60228: Conductors for isolated cables.
NTP-IEC 60502-1: Power cables with extruded insulation and their applications for nominal voltages from 1 kV and 3 kV.

CONSTRUCTION CHARACTERISTICS

Conductor material Copper Soft
Insulation material XLPE
External cover Halogen Free Thermoplastic Compound
Cover color Black
Free of halogens IEC 60754-1
Halogen Free Yes

DIMENSIONAL CHARACTERISTICS

Number of phases 3
Section of Conductor 120mm2
Earth conductor. Section 70mm2
Conductor diameter 13.0mm
Minimum insulation thickness 1.2
Minimum Thickness insulation Conductor. Earth 1.1
Minimum thickness of cover 1.6
Diameter on cover 39.1
Total number of wires 37
Approximate weight 4901kg/km

ELECTRICAL CHARACTERISTICS

Nominal service voltage Uo / U 0.6/1kV
Test Voltage 3.5kV
Maximum conductor resistance in DC at 20º C 0,153Ohm/km
Duct Amperage at 20ºC 295A
Amperage buried at 20ºC 345A
Amperage in air at 30ºC 355A

USE CHARACTERISTICS
Maximum operating temperature 90 ° C
Emergency overload temperature 130 ° C
Maximum temperature of the conductor in short-circuit 250 ° C

 