Flexible Copper Wire PVC Insulated Electrical Cable

Flexible Copper Wire PVC Insulated Electrical Cable

Flexible Copper Wire PVC Insulated Electrical Cable

Flexible cable

Insulated

Solid or Stranded

Underground

House and Building

Copper or Aluminium or Aluminium Alloy

PVC

Round Wire

Flame Retardant

ISO9001, CCC

Rmjt

Flexible Copper Wire PVC Insulated Electrical Cabl

300/300V 300/500V 450/750V

Red, Black, Yellow, Blue, Green, Grey and So on

IEC, UL, BS, VDE, AS/NZS or According to You.

Calss 1, Class2, Class 5, Class6

RMJT

100m/Roll or Bag

170mm*170mm*68mm

China

8544492100

Product Description
Flexible copper wire PVC Insulated Electrical Cable

1.Application:
These cables are used for general wiring, unenclosed, enclosed in conduit, buried direct or in underground ducts for domestic, commercial and industrial aaplications where not subject to mechanical damage.
2.Standard:
GB/T 5023-2008, BS 6004, IEC 60227, VDE ,UL

3.Specification:
Reference No 6192y
Flat Twin

Notes
1.Conductor of high conductivity copper wires insulated with PVC compound.sheathed with PVC compound
2.Color of sheath:gray or white,
450/750V PVC Insulated (Non-Sheathed) Flexible Conductor General Purpose Cables to BS 6004
Single Core PVC Insulated

Notes
1.Conductor of high conductivity copper wires insulated with PVC compound.
2.Colors of standard:red, black, brown, gray,orange, white, violet, pink,green/yellow, yellow

Size of conductor Nominal thickness of insulation mm Mean overall diameter Upper limit mm Approx.net weight per km kg
Nominal cross-sectional area mm2 Number and diameter of wires no./mm
1.0 32/0.20 0.6 3.0 16
1.5 30/0.25 0.7 3.5 21
2.5 50/0.25 0.8 4.2 33
4 56/0.30 0.8 4.8 50
6 84/0.30 0.8 6.3 70
10 80/0.40 1.0 7.6 120
16 126/0.40 1.0 8.8 175
25 196/0.40 1.2 11.0 290
35 276/0.40 1.2 12.5 400
50 396/0.40 1.4 14.5 565
70 360/0.50 1.4 17.0 770
95 475/0.50 1.6 19.0 1010
120 608/0.50 1.6 21.0 1260
150 756/0.50 1.8 23.5 1580
185 925/0.50 2.0 26.0 1900
240 1221/0.50 2.2 29.5 2500

Size of conductor Nominal thickness of insulation mm Mean overall dimensions Approx. net weight per km kg
Nominal cross-sectional area mm2 Number and diameter of wires no/mm Lower Limit mm Upper Limit Mm
0.5 28/0.15 0.8 2.5×5.0 3.0×6.0 24
0.75 42/0.15 0.8 2.7×5.4 3.2×6.4 29
Size of conductor Nominal thickness of insulation mm Mean overall diameter Upper limit mm Approx. net weight per km kg
Nominal cross-sectional area mm2 Number and diameter of wire no/mm
0.5 16/0.20 0.6 2.6 10
0.75 24/0.20 0.6 2.8 13
1.0 32/0.20 0.6 3.0 16
1.5* 30/0.25 0.7 3.5 20
2.5* 50/0.25 0.8 4.2 32
4.0* 56/0.30 0.8 4.8 49

Size of conductor Nominal thickness of insulation mm Nominal thickness of sheath mm Mean overall dimensions Approx. net weight per km kg
Nominal cross- sectional area mm2 Number and diameter of wires No./mm Upper Limit mm Upper Limit mm
0.5 16/0.20 0.5 0.6 3.0×4.8 3.6×6.0 27
0.75 24/0.20 0.5 0.6 3.2×5.2 3.9×6.4 34
Size of conductor Nominal thickness of insulation mm Nominal thickness of sheath mm Mean overall dimensions Approx. net weight per km kg
Nominal cross- sectional area mm2 Number and diameter of wires No./mm Upper Limit mm Upper Limit mm
0.5 16/0.20 0.5 0.6 4.8 6.0 36
0.75 24/0.20 0.5 0.6 5.2 6.4 45

Size of conductor Nominal thickness of insulation mm Nominal thickness of Sheath mm Mean overall dimensions Approx. net weight per km kg
Nominal cross- sectional area mm2 Number and diameter of wires no/mm Lower Limit mm Upper Limit mm
0.5 16/0.2 0.5 0.6 5.0 6.2 44
0.75 24/0.2 0.5 0.6 5.4 6.8 55
Size of conductor Nominal thickness of insulation mm Nominal thickness of sheath mm Mean overall dimensions Approx. net weight per km kg
Nominal cross- sectional area mm2 Number and diameter of wires no/mm Lower Limit mm Upper Limit mm
0.75 24/0.20 0.6 0.8 6.0 7.6 63
1.0 32/0.20 0.6 0.8 6.4 8.0 73
1.25 40/0.20 0.7 0.8 7.0 8.6 84
1.5 30/0.25 0.7 0.8 7.4 9.0 95
2.5 50/0.25 0.8 1.0 8.9 11.0 145
Size of conductor Nominal thickness of insulation mm Nominal thickness of sheath mm Mean overall dimensions Approx. net weight per km kg
Nominal cross- sectional area mm2 Number and diameter of wires no/mm Lower limit mm Upper limit mm
0.75 24/0.20 0.6 0.8 6.8 8.6 78
1.0 32/0.20 0.6 0.9 7.6 9.4 110
1. 5 30/0.25 0.7 1.0 9.0 11.0 150
2.5 50/0.25 0.8 1.1 10.5 13.0 220

4.Packing in plastic reel, paper reel ,wooden drum or as customer’s requirement.

5.Our factory:
People’s Cable Group Co., Ltd. was founded in 2007, located in Zhengzhou Gongyi economic development zone. Our company has 2 factories (Zhitian factory and Zhulin factory), occupies total area of more than 300,000 square meters, with building area 230,000 square meters.

6.Certificate:
As first rank of the cable supplier in China, we have obtained CCC, ISO9001, ISO14001, OHSAS certificates, passed the SGS and BV test, and our brand "RMJT" be given China famous brand.

7.Customer Visit:
We have a professional sales team with each of them has engaged in this job for 3-10 years, so that we can provide the comprehensive and professional technology for you. With the perfect quality and after sales service, till now we have exported to more than 80 countries, welcome to visit us and establish win-win establish relationship!

8.Contact:
Dear friends, welcome to our store. We will provide you with china wholesale market market products, excellent service and reasonable price.Please contact us if have any questions about the product. we will answer the questions carefully.At last,I wish you a pleasant purchase.
Factrory ADD:No.13th,YongDing Road, Goingyi,Zhengzhou city, Henan province, China.
Tel:+86-371-55367868
Fax:+86-371-55367868
Mobile:+86-18339931106
Sky:Tinaleeran

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.