Fire Resistant PVC XLPE Copper Aluminium Power Cable
Product Description
Technical Performance
1. PVC insulated cable conductor maximum temperature rating of 70 ºC, when a short circuit occurs (the longest duration of no more than 5S), the conductor temperature does not exceed 160 ºC.
2. The maximum rated temperature of XLPE insulated cable conductor is 90 ºC, short (the longest duration of no more than 5S) occurs, the conductor temperature does not exceed 250 ºC.
3. when installing PVC insulated or jacketed cable ambient temperature not below 0 ºC.
4. Perfect chemical stability, resistant against acids, alkali, grease and organic solvents, and flamer retardant.
PVC XLPE Cable Minimum Bending Radius
1. Mounting the cable minimum bend radius:
Single core Armored cable 15D, Unarmored 20D
Multi-core cable Armored cable 15D, Unarmored 12D
2. Minimum bending radius near the connection box and termination cable:
Single core Armored cable 15D, Unarmored 12D
Multi-core cable Armored cable 12D, Unarmored 10D
Power Cables Advantages
1. Occupies a small area.
It is usually buried in the soil or laid indoors.
In trenches and tunnels, the insulation distance between the lines is small, no towers are used, it occupies less land, and basically does not occupy space on the ground.
2. High reliability.
Affected by climatic conditions and surrounding environment, transmission performance is stable and reliability is high.
3. It has more favorable conditions for the development of ultra-high voltage and large capacity, such as low temperature and super- conducting cables.
4. Large distributed capacitance.
5. Low maintenance workload.
6. The possibility of electric shock is small.
Standard
IEC 60502, IEC60332, IEC 60754
Model | Application | |
Copper | Aluminum | |
VV | VLV | Lay indoors, pipes, tunnels |
VY | VLY | |
VV22 | VLV22 | |
VV23 | VLY23 | Lay underneath, able to withstand external mechanical forces |
YJV | YJLV | Laying aerial, indoor, cable trench, tunnel, underground |
YJY | YJLY | Laying indoor, cable trench, tunnel, underground |
YJV22 | YJLV22 | Fixedly laid in the place with external pressure |
YJV23 | YJLV23 | Fixedly laid in places where external forces are often applied |
YJV32 | YJLV32 | Fixed installation in places that can withstand tensile forces |
YJV33 | YJLV33 | |
YJV42 | YJLV42 | Fixedly laid underwater, in a shaft or in a place that can withstand tensile forces |
YJV43 | YJLV43 | Fixed installation in places that can withstand large tensile forces |
ZR-VV | ZR-VLV | Lay indoors, tunnels, pipes |
ZR-VV22 | ZR-VLV22 | Laid indoors, in tunnels, directly buried in the soil, able to withstand pressure and other external forces |
ZR-VV32 | ZR-VLV32 | Laid indoors, mines, can withstand considerable tension |
- Next: IEC60502 Electrical Cable Cu-Conductor/XLPE Insulated/ PVC Sheathed Unarmored Power Cable
- Previous: 4 Core 10mm Underground Copper Electric PVC Cable
Contact us
Similar Or Related
-
15kV 3 Core 4/0AWG Aluminum Conductor XLPE Insulated SWA Armored MV Power Cable
-
XLPE Insulated Aerial Service Drop Cable Conductor #3AWG Duplex ICEA S-66-524 NEMA WC7
-
3Cx185mm2 XLPE Insulated Copper Tape Screened Galvanized Steel Wire Armored Power Cable 33kV
-
0.6/1kV 4Cx500mm2 Copper Conductor PVC Insulated SWA Armored LV Power Cable IEC 60502-1
-
Low Voltage Single Core Power Cable 1X300 mm2 N2XCH CU/XLPE/CWS/LSF 0.6/1kV