Duplex Service Dropcable, ABC Cable 70sqmm

Duplex Service Dropcable, ABC Cable 70sqmm

Duplex Service Dropcable, ABC Cable 70sqmm

70sqmm

70sqmm

90 Centigrade

XLPE

Self Supporting or Supporting Core

Yifang Cable

Wooden Drum or Wooden-Steel Drum

CE SABS RoHS SGS UL CCC

Zhengzhou, China

8544492100

Product Description

Duplex cable
Service Drop cable
Aluminum Conductors. Polyethylene or Crosslinked Polyethylene Insulation.

APPLICATIONS

Primarily used for 120 volt overhead service applications such as street lighting, outdoor lighting, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75ºC for polyethylene insulated conductors or 90ºC for crosslinked polyethylene (XLP) insulated conductors.

SPECIFICATIONS

duplex service drop cable meets or exceeds the following ASTM specifications:

B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-231 Aluminum Conductors, Concentric-Lay-Stranded.
B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire.

duplex service drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.

CONSTRUCTION

Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or crosslinked
polyethylene (XLP). Neutral messengers are concentrically stranded 6201, AAC, or ACSR.

Duplex Service Drop

Code Phase Conductor Bare Weight Allowable
Word Neutral Messenger Per 1000 ft. (lbs.) Ampacities+
Size Strand- Insul. Equiv. Size Strand- Rated XLP POLY XLP POLY
(AWG) ing Thick. Dia. (kcmil) ing Strength
(mils) (AWG)++ (lbs.)
6201 ALLOY NEUTRAL-MESSENGER
Chihuahua 6 1 45 6 30.58 7 1110 65 65 85 70
Vizsla 6 7 45 6 30.58 7 1110 68 68 85 70
Harrier 4 1 45 4 48.69 7 1760 99 99 115 90
Whippet 4 7 45 4 48.69 7 1760 103 103 115 90
Schnauzer 2 7 45 2 77.47 7 2800 157 157 150 120
Heeler 1/0 9 60 1/0 123.3 7 4460 250 250 205 160
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).
+ Conductor temperature of 90 for XLP, 75 for Poly; ambient temperature of 40; emissivity 0.9; 2 ft./sec. wind in sun.
++ Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.

Duplex Service Drop

Code Phase Conductor Bare Weight Allowable
Word Neutral Messenger Per 1000 ft. (lbs.) Ampacities+
Size Strand- Insul. Equiv. Size Strand- Rated XLP POLY XLP POLY
(AWG) ing Thick. Dia. (kcmil) ing Strength
(mils) (AWG)++ (lbs.)
6201 ALLOY NEUTRAL-MESSENGER
Chihuahua 6 1 45 6 30.58 7 1110 65 65 85 70
Vizsla 6 7 45 6 30.58 7 1110 68 68 85 70
Harrier 4 1 45 4 48.69 7 1760 99 99 115 90
Whippet 4 7 45 4 48.69 7 1760 103 103 115 90
Schnauzer 2 7 45 2 77.47 7 2800 157 157 150 120
Heeler 1/0 9 60 1/0 123.3 7 4460 250 250 205 160
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).
+ Conductor temperature of 90 for XLP, 75 for Poly; ambient temperature of 40; emissivity 0.9; 2 ft./sec. wind in sun.
++ Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.

Code* Phase Conductor Bare Weight Allowable
Word Neutral Messenger Per 1000 ft. (lbs.) Ampacities+
Size Strand- Insul. Size Strand- Rated XLP POLY XLP POLY
(AWG) ing Thick. (AWG) ing Strength
(mils) (lbs.)
AAC NEUTRAL-MESSENGER
Pekingese 6 1 45 6 7 563 61 61 85 70
Collie 6 7 45 6 7 563 64 64 85 70
Dachshund 4 1 45 4 7 881 92 92 115 90
Spaniel 4 7 45 4 7 881 96 96 115 90
Doberman 2 7 45 2 7 1350 147 147 150 120
Malemute 1/0 9 60 1/0 7 1990 234 234 205 160
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).
+ Conductor temperature of 90 for XLP, 75 for Poly; ambient temperature of 40; emissivity 0.9; 2 ft./sec. wind in sun.

Duplex Service Drop

Code* Phase Conductor Bare Weight Allowable
Word Neutral Messenger Per 1000 ft. (lbs.) Ampacities+
Size Strand- Insul. Size Strand- Rated XLP POLY XLP POLY
(AWG) ing Thick. (AWG) ing Strength
(mils) (lbs.)
ACSR NEUTRAL-MESSENGER
Setter 6 1 45 6 6/1 1190 72 72 85 70
Shepherd 6 7 45 6 6/1 1190 75 75 85 70
Eskimo 4 1 45 4 6/1 1860 110 110 115 90
Terrier 4 7 45 4 6/1 1860 115 115 115 90
Chow 2 7 45 2 6/1 2850 176 176 150 120
Bull 1/0 9 60 1/0 6/1 4380 280 280 205 160
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP).
+ Conductor temperature of 90 for XLP, 75 for Poly; ambient temperature of 40; emissivity 0.9; 2 ft./sec. wind in sun.

CONSTRUCTION
1 Conductor: Al phase – conductor
2 Insulation: XLPE

SPECIFICATION

Type Standard
X00-A JUS N.C5.250
NFA2X HD 626 S1 P 4F
N1XD4-AR HD 626 S1 P 4E

APPLICATION
These cables are intended for distribution in power grids for industry, towns, and street illumination. They are also connection
cables for hanging on electric poles, consoles, walls, on both wooden and steel construction.

70mm abc cable/AAC/AAAC and ACSR cable

Specifications
1.Conductor: aluminum or copper
2. Insulation: XLPEor PVC
3.Stranded or solid conductor
4. IECstandard
5. abc cables
low voltage overhead bundled cable ABC
Specifications
ABC aerial bundle cable withAluminium stranded conductor(compacted or non- compacted), AAAC or ACSR messenger core.
Aluminium stranded conductor(compacted or non- compacted), AAAC messenger core(or ACSR messenger core), XLPE(or HDPE) insulated, Twisted (or Parallel)power cable
The product is a new type of aerial cable for power transmitting, It is extensively used in overhead power transmission line, It improves the safety and reliance of electrified wire netting.

SPEC mm2 conductor structure Approx.
Phase Neutral(Bare ACSR) insulation insulation Overall Approx. packing
(Compacted AL) Aluminium Steel material Thickness Diameter Weight Meters Per
(No./mm) (No./mm) (No./mm) (mm) (mm) (kg/km) Drum
1×16+1×16 7/1.72 6/1.72 1/1.72 XLPE 1.2 12.5 121.9 250-4000m
1×25+1×25 7/2.15 6/2.15 1/2.15 1.2 14.9 182.2 250-4000m
1×35+1×35 7/2.54 6/2.54 1/2.54 1.4 17.5 254.7 250-3500m
1×50+1×50 7/2.92 6/2.92 1/2.92 1.4 20.1 333.9 250-3000m
1×70+1×70 19/2.15 12/2.15 17/2.15 1.4 23.6 382.2 250-3000m
1×95+1×95 19/2.54 12/5.24 17/5.24 1.6 27.6 528.2 250-3000m
2×16+1×16 7/1.72 6/1.72 1/1.72 (HDPE) 1.2 14.2 187.6 250-4000m
2×25+1×25 7/2.15 6/2.15 1/2.15 1.2 16.7 273.8 250-3500m
2×35+1×35 7/2.54 6/2.54 1/2.54 1.4 19.7 386.9 250-3500m
2×50+1×50 7/2.92 6/2.92 1/2.92 1.4 22.5 506 250-3000m
2×70+1×70 19/2.15 12/2.15 7/2.15 1.4 26.1 617.2 250-3000m
2×95+1×95 19/2.54 12/5.24 7/5.24 1.6 30.5 850.9 250-3000m
3×16+1×16 7/1.72 6/1.72 1/1.72 1.2 16.3 253.3 250-3500m
3×25+1×25 7/2.15 6/2.15 1/2.15 1.2 19.1 371.9 250-3500m
3×35+1×35 7/2.54 6/2.54 1/2.54 1.4 22.5 519.1 250-3000m
3×50+1×50 7/2.92 6/2.92 1/2.92 1.4 25.7 678.1 250-3000m
3×70+1×70 19/2.15 12/2.15 7/2.15 1.4 29.7 1024.3 250-3000m
2×95+1×95 19/2.54 12/2.54 7/2.54 1.6 34.6 1413.7 250-3000m