Cu/XLPE/PVC, XLPE Control Cable, 0.6/1 kv (IEC 60502-1)

Cu/XLPE/PVC, XLPE Control Cable, 0.6/1 kv (IEC 60502-1)

Cu/XLPE/PVC, XLPE Control Cable, 0.6/1 kv (IEC 60502-1)

CU/XLPE/PVC

Insulated

Stranded

Indoors

Copper

PVC

XLPE

Round Wire

Refractory

ISO9001, CCC

Boan

IEC 60502-1

0.6/1 KV

1.5-2.5 mm2

1/2

5-61

DingAn or OEM

Fumigated Steel-Wooden Drum/Roll

IEC

Jiangsu Yixing, China

8544492100

Product Description

CU/XLPE/PVC, Control Cable, 0.6/1 KV (IEC 60502-1)
Application
These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Structure
Conductor
Copper or Aluminium conductor, round stranded or Shaped, Class 2 to IEC 60228, BS EN 60228. For smaller sizes, a solid round conductor, Class 1 as per IEC 60228, BS EN 60228 can also be supplied upon request.
Insulation
XLPE material and thickness shall be as per IEC 60502 or BS 5467 rated for 90°C continuous operation.
Colour Code
Colour Code (1) :
Above 5 Cores : Black Cores with White numerals
Colour Code (2) :
Above 5 Cores : Black Cores with White numerals
Outer Sheath
Outer sheath shall be of Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467.
Special type of PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC, Sunlight resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as LLDPE, MDPE, HDPE, LSF, CPE are available on request.
Fire Performance of Cable Sheaths
Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, can also supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1, BS 7211, BS 6724 or other equivalent standards.7211, BS 6724 or other equivalent standards.7211, BS 6724 or other equivalent standards.7211, BS 6724 or other equivalent standards.

Nominal Cross Section Diameter of Conductor (Approx.) Nominal Insulation Thickness Nominal PVC Sheath Thickness Overall Diameter (Approx.) Weight of Cable (Approx.)
mm² mm mm mm mm Kg/Km
5×1.5 1.6 0.7 1.4 14 260
7×1.5 1.6 0.7 1.4 15 310
10×1.5 1.6 0.7 1.4 18 395
12×1.5 1.6 0.7 1.4 18.5 440
14×1.5 1.6 0.7 1.4 19 485
19×1.5 1.6 0.7 1.4 21 600
21×1.5 1.6 0.7 1.4 22 650
24×1.5 1.6 0.7 1.4 24 730
30×1.5 1.6 0.7 1.4 25 860
40×1.5 1.6 0.7 1.4 28 1080
48×1.5 1.6 0.7 1.4 30 1250
61×1.5 1.6 0.7 1.4 33 1570
5×2.5 2 0.7 1.4 15 330
7×2.5 2 0.7 1.4 16 400
10×2.5 2 0.7 1.4 19.5 515
12×2.5 2 0.7 1.4 20 580
14×2.5 2 0.7 1.4 21 650
19×2.5 2 0.7 1.4 23 810
21×2.5 2 0.7 1.4 24 890
24×2.5 2 0.7 1.4 26 1000
30×2.5 2 0.7 1.4 28 1190
40×2.5 2 0.7 1.4 31 1525
48×2.5 2 0.7 1.4 34 1820
61×2.5 2 0.7 1.4 37 2240