Product Description

Copper Conductor XLPE Insulated Bare Neutral 4mm 6mm 10mm 16mm Airdac Cable Concentric Cable

Polyethylene Sheath, SANS 1507, NRS 063 & NRS 017
 
Conductor: Hard Drawn Copper Conductor – Class 2
Insulation: LV-XLPE
Phase Color Code(SNE): Red, Black & Bare Copper
Phase Color Code (CNE): Red & Bare Copper
Application: Used for house connections , with or without coms wire.
 Technical Data
4mm², AIRDAC II CNE Cable

  Electrical Properties
Cable size: 4mm²
Phase Conductor Resistance (Ohm/km) DC @ 20 °C: 4,80
Phase Core Impedance (Z) (Ohm/km): 5,88
Current Rating (A)*: 30
Symmetrical Short Circuit Rating for 1s in kA: 0,572
* Note: – In air, with 30 °C ambient with maximum conductor temperature 90 °C
Mechanical Properties
Cable size: 4mm²
Phase Conductor (No.xOD): 7×0.92mm
Nominal Insulation Thickness: 1.0mm
Earth size: 4mm²
Earth Conductor (No.xOD): 8×0.85mm
Nominal Sheath Thickness: 1.4mm
Approximate Cable OD: 9.0mm
Approximate Cable Mass: 121 kg/km
Installation Data (SAG* mm):
Span 10(mm) :40
Span 20(mm) :165
Span 30(mm) :370
Span 40(mm) :650
Span 50(mm) :1020
Based on
UTS** :1480
MWT*** :370

 
10mm², AIRDAC II CNE Cable

  Electrical Properties
Cable size: 10mm²
Phase Conductor Resistance (Ohm/km) DC @ 20 °C: 1,90
Phase Core Impedance (Z) (Ohm/km): 2,34
Current Rating (A)*: 50
Symmetrical Short Circuit Rating for 1s in kA: 1,431
* Note: – In air, with 30 °C ambient with maximum conductor temperature 90 °C
Mechanical Properties
Cable size: 10mm²
Phase Conductor (No.xOD): 7×1.45mm
Nominal Insulation Thickness: 1.0mm
Earth size: 10mm²
Earth Conductor (No.xOD): 18×0.85mm
Nominal Sheath Thickness: 1.4mm
Approximate Cable OD: 11.0mm
Approximate Cable Mass: 249 kg/km
Installation Data (SAG* mm):
Span 10(mm) :35
Span 20(mm) :140
Span 30(mm) :310
Span 40(mm) :550
Span 50(mm) :870
Based on
UTS** :3600
MWT*** :900

 

Separate Neutral and Earth (SNE) Airdac 600/1000V

Cable
Size
Neutral
Size
Earth
Size
Pilot
Cores
Overall
Diameter
Cable
Mass
Current
Rating
Phase Core
Impedance
mm² mm² mm² mm mm kg/m amps ohms/km
10 10 7.5 2 x 0.5 12.8 0.32 90 2.34
16 16 10 2 x 0.5 14.5 0.485 125 1.47

Combined Neutral and Earth (CNE) Airdac 600/1000V

Cable
Size
Earth
Size
Overall
Diameter
Cable
Mass
Current
Rating
Phase Core
Impedance
mm² mm² mm kg/m amps ohms/km
4 4 8.7 0.121 47 5.88
10 10 11 0.249 86 2.34
 

Tags: , ,