Copper Conductor PVC Insulated Flexible Power Wire.

Copper Conductor PVC Insulated Flexible Power Wire.

Copper Conductor PVC Insulated Flexible Power Wire.

building cable

Insulated

Solid

Overhead

Copper

PVC

Round Wire

ISO9001, CE

SABS

Jiapu

ASTM, IEC, DIN, CSA, BS…

0.1-36kv

as Your Request

JP

Export Wooden Drum or Wooden Steel Drum

China

8544601200

Product Description

1 Applying Standard
GB/T5023.1~.7-2008 JB/T8734.1~.5-2016 equivalent to IEC60227
GB/T19666-2005 GB/T18380.12-2008
2 Product Application
2.1 The B series is used for fixed installation for power unit with AC rated voltage 450/750V and below, R series is copper core PVC insulation flexible power cable(wires) used for home appliances, small electric tool, instrument, power lighting. with AC rated voltage 300/500V and below.
2.2 Long-term working temperature
The long-term working temperature of cable conductor for model BV-90, RV-90, the Max temperature is 90ºC,for the rest model, the Max temperature is 70ºC.
2.3 Environmental temperature:
The lowest environment temperature is 0 ºC for cable & wires laying.
3 Model & execution standard

Model No. Conductor Insualtion Jacket
Cores × Nom. Area Max. Resistance at 20°C Thickness Min. Resistance at 70°C Thickness Min. Dia. Max.
mm² MΩ/km mm MΩ/km mm mm mm
RVV2×0.75 2×0.75 26 0.6 0.011 0.8 6 7.6
RVV2×1.0 2×1.0 19.5 0.6 0.01 0.8 6.4 8
RVV2×1.5 2×1.5 13.3 0.7 0.01 0.8 7.4 9
RVV2×2.5 2×2.5 7.98 0.8 0.009 1 8.9 11
RVV3×0.75 3×0.75 26 0.6 0.011 0.8 6.4 8
RVV3×1.0 3×1.0 19.5 0.6 0.01 0.8 6.8 8.4
RVV3×1.5 3×1.5 13.3 0.7 0.01 0.9 8 9.8
RVV3×2.5 3×2.5 7.98 0.8 0.009 1 9.6 12
RVV4×0.75 4×0.75 26 0.6 0.011 0.8 6.8 8.6
RVV4×1.0 4×1.0 19.5 0.6 0.01 0.9 7.6 9.4
RVV4×1.5 4×1.5 13.3 0.7 0.01 1 9 11
RVV4×2.5 4×2.5 7.98 0.8 0.009 1.1 10.5 13
RVV5×0.75 5×0.75 26 0.6 0.011 0.9 7.4 9.6
RVV5×1.0 5×1.0 19.5 0.6 0.01 0.9 8.3 10
RVV5×1.5 5×1.5 13.3 0.7 0.01 1.1 10 12
RVV5×2.5 5×2.5 7.98 0.8 0.009 1.2 11.5 14