Copper Condcutor Insulated DC Cathodic Protection Cable

Copper Condcutor Insulated DC Cathodic Protection Cable

Copper Condcutor Insulated DC Cathodic Protection Cable

CPVV

Insulated

Stranded

Cathodic Protecthino System

Copper

Hmwpe or PVC

PVC, Hmwpe, Kynar, PVDF etc

Round Wire

Cathodic Protection System

ISO9001, CCC

Yifang

1

YIFANG

Drum or as Per Customer's Request

10mm2 to 70mm2

China

8544492100

Product Description

Copper Condcutor insulated DC Cathodic Protection Cable

1. Applications
The cathodic protection cable mainly used for impressed current cathodic protection system.
It has excellent electrical properties, mechanical behavior, heat aging property, resistance to environment stress and chemical corrosion resistance ability, very low water absorption and simple structure ,easy to use and not retain by laying fall etc.
The products is equivalent to the national standards GB16702 and the national petroleum company of Saudi Arabia 17-SAMSS-017<Impressed current cathodic protection cable procurement norms>of our corporate standard to organize production. The company also may require the user or by other standards, designing and manufacturing some special functions of cathodic protection cable.

2. Cable type, core number and conductor cross section
 1. Cable type and name

Type Name
CPVV Copper core PVC insulated and sheathed cathodic protection cable
(Cu/PVC/PVC)
CPY Copper core HMWPE insulated cathodic protection cable
(Cu/HMWPE)
CPFY Copper core fluorine plastic insulated HMWPE sheathed cathodic protection cable
(Cu/PVDF/HMWPE; Cu/ KYNAR/HMWPE)
CPFY33 Copper core fluorine plastic insulated fine-steel-wire-armored HMWPE sheathed cathodic protection  cable(Cu/PVDF/SWA/HMWPE; Cu/ KYNAR/SWA/HMWPE)

2. Core number: 1 core
 3. Conductor cross section: 10, 16, 25,35,50,70

4. Characteristics
1. Rated voltage: DC600V
2. Long-term permissible working temperature of cable conductor:
  PVC insulated cable: 70ºC
  HMWPE insulated cable: 90ºC
  PVDF/ KYNAR insulated cable: 135ºC
 3. The layout temperature of cable shall not be lower than -20ºC
 4. The bending radius: 20D,(D is outer diameter cable )
5. Technical Requirements
1. DC Resistance: the resistance value of finished cable at 20ºC is not more than the following table provides.

Cross section (mm2) 10 16 25 35 50 70
Resistance (Ω/km) 1.83 1.15 0.727 0.524 0.387 0.268

2. AC voltage withstand test:
The cable impose 50Hz, 3500V AC, sustainable 5 min, during the test, the insulation should not occur breakdown.
3. Insulation-resistanca test
Insulation resistance at 20ºC should be greater than 1500MΩ/km