Product Description
Construction:
Aluminum 1350 wires are concentrically stranded and wrapped helically around a central wire. Each successive layer has six wires more than the previous underlying layer. Outer layer is right hand lay and reversed in successive layers. AAC(All aluminum conductor) is the most economical bare overhead conductor due to its lighter weight. It offers easier handing during installation and use of simpler fittings. The conductor is corrosion resistant due to its homogeneous construction.
Bare Conductor Types
(1) all aluminum conductor (AAC)
(2) all aluminum alloy conductor(AAAC)
(3) aluminum conductor steel reinforced (ACSR)
(4) anti-corrosion type ACSR
(5) aluminum conductor aluminum clad steel reinforced(ACSR/AW)
(6)rear earth aluminum conductor steel reinforced(ACSR/RE)
(7)aluminum conductor aluminum alloy reinforced(ACAR)
If your have any interested products, Please feel free to contact our sales team
Description | Bidder’s offer | ||
Name of Manufacturer | Jinyuan Cable Inc. | ||
Manufacturer’s Address & Country of Manufacture | China | ||
1 | Type and Size | Conductor 50mm2 AA HD BARE | |
2 | Service Conditions | Altitudes of up to 2200m Humidity of up to 90% Average ambient temperature of +30ºC |
|
3 | Materials | Aluminium | Aluminium 1350-H9 |
PVC covering | N/A | ||
4 |
Construction & Standard | Bare conductor | Bare Conductor |
PVC covered conductor | N/A | ||
5 | Nominal area of aluminium, mm² | 50 | |
6 | Overall diameter of bare conductor, mm | 9.3 | |
7 | Overall diameter of covered conductor, mm | N/A | |
8 | Stranding, No./diameter in mm | Aluminium | 7/3.1 |
Tolerance on diameter | ±0.03 | ||
9 | Calculated maximum d.c. resistance at 20°C, ohm/km | 0.5419 | |
10 | Calculated minimum breaking load, kN | 8.28 | |
11 | Mass of conductor, kg/km | 145 | |
12 | Current carrying capacity, A (State applicable condicitons) | 45 | |
13 | Packing, Marking & Length on drum | Packing & wood lagging | Wood drum with Wood Lagging |
Marking on conductor & drum | Only mark on Drum flange | ||
Continuous length of conductor on drum | 5000m | ||
14 | List test reports submitted (indicate test report numbers, date, Testing Institution and their contact address | yes | |
15 | Manufacturer’s ISO 9001:2008 Certificate, Guarantee and Warranty | yes | |
16 | List catalogues, brochures, technical data, drawings, customer sales records, customer reference letters, manufacturer’s experience and capacity submitted to support the offer | yes | |
17 | Acceptance Tests to be witnessed by KPLC Engineers at the factory | yes | |
18 | Statement of compliance to specification or deviations | N/A |